YORK INTERNATIONAL
12
YCAS 310 380 DIMENSIONS
(SI Units)
LD01600
LD01599
NOTES:
1. Clearances - Recommended YORK clearances for peak performance, reliable operation and maintenance:
Side to wall 2438 mm*; Rear to wall 2438 mm; Control Panel End to wall 1524 mm*; Over the top - No obstructions allowed; Distance
between adjacent units 3658 mm, (Walls should be no higher than the unit.)
*No more than one high wall can be higher than the top of the unit. The area within the clearances shown above and area under the unit
must be kept clear of all obstructions or clutter that would impede air flow to the unit. In installations where winter operation is intended and
snow accumulations are expected, additional unit height must be provided to insure air flow.
NOTE: Reduced clearances may be used due to jobsite restrictions or competitive recommendations. The unit will unload to prevent the
condenser pressure and motor current from exceeding the maximum limits and will continue to operate without nuisance high pressure or
motor current cutouts even though the air flow will be restricted at these conditions.
2. Cooler liquid connection sizes (inlet and outlet) 10" victaulic for all models.
3. Spring isolators (OPTIONAL) will increase overall height of unit.
Summary of Contents for Millennium YCAS 310
Page 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Page 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Page 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Page 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Page 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Page 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Page 48: ...YORK INTERNATIONAL 48 LD02021...
Page 54: ...YORK INTERNATIONAL 54 LD02027...