INVERTER-DRIVEN 

MULTI-SPLIT SYSTEM HEAT PUMP

AIR CONDITIONERS

INSTALLATION&MAINTENANCE 

MANUAL

New Release

P01373Q

Models

< Outdoor Units >

JVOH080VPEMBQ

JVOH380VAEMBQ

JVOH680VAEMBQ

JVOH100VPEMBQ

JVOH400VAEMBQ

JVOH700VAEMBQ

JVOH120VPEMBQ

JVOH420VAEMBQ

JVOH720VAEMBQ

JVOH140VPEMBQ

JVOH440VAEMBQ

JVOH740VAEMBQ

JVOH160VPEMBQ

JVOH460VAEMBQ

JVOH760VAEMBQ

JVOH180VPEMBQ

JVOH480VAEMBQ

JVOH780VAEMBQ

JVOH200VPEMBQ

JVOH500VAEMBQ

JVOH800VAEMBQ

JVOH220VPEMBQ

JVOH520VAEMBQ

JVOH820VAEMBQ

JVOH240VPEMBQ

JVOH540VAEMBQ

JVOH840VAEMBQ

JVOH260VAEMBQ

JVOH560VAEMBQ

JVOH860VAEMBQ

JVOH280VAEMBQ

JVOH580VAEMBQ

JVOH880VAEMBQ

JVOH300VAEMBQ

JVOH600VAEMBQ

JVOH900VAEMBQ

JVOH320VAEMBQ

JVOH620VAEMBQ

JVOH920VAEMBQ

JVOH340VAEMBQ

JVOH640VAEMBQ

JVOH940VAEMBQ

JVOH360VAEMBQ

JVOH660VAEMBQ

JVOH960VAEMBQ

JO2017062E

Original Instruction

Summary of Contents for JVOH080VPEMBQ

Page 1: ...AEMBQ JVOH160VPEMBQ JVOH460VAEMBQ JVOH760VAEMBQ JVOH180VPEMBQ JVOH480VAEMBQ JVOH780VAEMBQ JVOH200VPEMBQ JVOH500VAEMBQ JVOH800VAEMBQ JVOH220VPEMBQ JVOH520VAEMBQ JVOH820VAEMBQ JVOH240VPEMBQ JVOH540VAEMBQ JVOH840VAEMBQ JVOH260VAEMBQ JVOH560VAEMBQ JVOH860VAEMBQ JVOH280VAEMBQ JVOH580VAEMBQ JVOH880VAEMBQ JVOH300VAEMBQ JVOH600VAEMBQ JVOH900VAEMBQ JVOH320VAEMBQ JVOH620VAEMBQ JVOH920VAEMBQ JVOH340VAEMBQ JV...

Page 2: ...witch Install the unit at least 3 meters away from electromagnetic wave such as a radio Do not install the unit in the place where the breeze directly blows to the animals and plants It could adversely affect the animals and plants The installation and service engineering should be in accordance with the local laws and regulations If you have any questions contact your distributor or dealer The in...

Page 3: ...y voltage and frequency and accessories to determine if they are correct The standard utilization of the unit shall be explained in these instructions Therefore the utilization of the unit other than those indicated in these instructions is not recommended Please contact your local agent as the occasion arises The company s liability shall not cover defects arising from the alteration performed by...

Page 4: ...dation 16 5 5 Condensation Water Treatment 18 6 The Refrigerant Piping Construction 19 6 1 Piping Material 19 6 2 Flare and Joints 22 6 3 Precautions for Installation of Outdoor Unit 23 6 4 System Piping Connection 25 7 Electrical Wiring 39 7 1 General Check 39 7 2 Wiring 42 7 3 Outdoor Unit Wiring 44 7 4 Electrical Wiring for Indoor and Outdoor Unit 46 7 5 Outdoor DIP Switch Setting 48 8 Addition...

Page 5: ...ant leakage can cause difficulty with breathing due to insufficient air If a refrigerant leakage is found immediately turn OFF the main power supply extinguish any open flame and then contact the service dealer Make sure to perform air tight testing The refrigerant R410A used in this product fluorocarbon is not flammable non toxic and odourless If there is refrigerant leakage exposure to open flam...

Page 6: ...wise it will cause an electrical malfunction or fire Make sure that the terminals are tightened with the specified torque Otherwise it will cause a fire or electrical fault at the terminal block If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard If there is fire please cut off the power supply immediatel...

Page 7: ...er Power supply for high power equipment is too close to the power wire of the air conditioner Device Ex Lift container crane rectifier for electric railway inverter power device arc furnace electric furnace large sized induction motor and large sized switch It consumes a large quantity of electrical power In the case mentioned above the power wire of the air conditioner generates a large induced ...

Page 8: ...r for Wires 3 Vacuum pump 8 Pipe cutter 13 Manifold valve 18 Hoist for indoor unit 4 Charging hose 9 Brazing tools 14 Wire cutter 19 Ammeter 5 Megohmmeter 10 Hex wrench 15 Leakage detector 20 Voltage meter NOTE While touching to refrigerant directly use special installation tools and instruments for the new refrigerant R410A DANGER The pressure of the new refrigerant R410A is 1 4 times that of the...

Page 9: ... prevent the pipe line is contaminated brazing blowing nitrogen to prevent oxidation Prevent oxidation Lubricating oil applied to flaring surface Use the same lubricating oil as the refrigeration system Oil is easy to absorb water Lubricate the flaring surface Refrigerant charging vacuum drying Refrigerant cylinder Confirm the corresponding refrigerant in the cylinder Non azeotropic mixed refriger...

Page 10: ...VPEMBQ JVOH180VPEMBQ JVOH200VPEMBQ JVOH220VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ HP 66 68 70 72 74 Model JVOH660VAEMBQ JVOH680VAEMBQ JVOH700VAEMBQ JVOH720VAEMBQ JVOH740VAEMBQ Combination JVOH180VPEMBQ JVOH200VPEMBQ JVOH220VPEMBQ JVOH240VPEMBQ JVOH160VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH240VPEMBQ JVOH160VPEMBQ JVOH240VPEMBQ JVOH240...

Page 11: ... Floor Concealed Fresh Air Ducted Indoor Unit Model Standard Capacity 100 W 90 100 112 125 140 160 224 280 335 450 560 Compact Ducted Mid ESP Ducted High ESP Ducted Round way Cassette High Wall 2 way Cassette Floor Concealed Fresh Air Ducted Allowed NOTE The number of indoor units that can be connected to the outdoor unit is shown in the table below Please follow this rule when installing the appl...

Page 12: ...MBQ 53 32 JVOH340VAEMBQ 56 32 JVOH360VAEMBQ 59 32 JVOH380VAEMBQ 64 38 JVOH400VAEMBQ 64 38 JVOH420VAEMBQ 64 38 JVOH440VAEMBQ 64 38 JVOH460VAEMBQ 64 38 JVOH480VAEMBQ 64 38 JVOH500VAEMBQ 64 38 JVOH520VAEMBQ 64 38 JVOH540VAEMBQ 64 38 JVOH560VAEMBQ 64 38 JVOH580VAEMBQ 64 38 JVOH600VAEMBQ 64 38 JVOH620VAEMBQ 64 38 JVOH640VAEMBQ 64 38 JVOH660VAEMBQ 64 38 JVOH680VAEMBQ 64 38 JVOH700VAEMBQ 64 38 JVOH720VAE...

Page 13: ...oor fresh air handling the number of indoor units must be within the recommended number of connectable indoor units If the indoor unit capacity exceeds 100 but less than 130 please refer to the Technical Bulletin for details If the temperature in the installation place of the outdoor unit sustainably exceeds 48 C the total connection capacity of the indoor units should be less than the total capac...

Page 14: ...aper frame and packing belt Wooden base Wire rope 4 2 Lifting Method When lifting the machine ensure the balance of the machine confirm the safety and then lift it smoothly 1 It is strictly forbidden to remove any packing filler 2 As shown in Figure 4 1 lift the machine with a bundle of two slings Figure 4 1 Lifting Diagram ...

Page 15: ...tom of the machine Otherwise the bottom of the machine maybe deformed Prohibit to use the forklift to push the bottom of the machine Prohibit to use rollers and so on Opening of unit side Fork Do not apply force to this location front and rear NOTE If you want to carry out transport handling after unpacking please protect the machine with veneer fabric and so on WARNING Before installation and com...

Page 16: ...58 Liquid Side Connecting Piping Ø9 52 Ø12 7 Silencer Ø28 58 Ø28 58 Refrigerant Label Magnet Ring Filter Tie IOM Accessory 18HP 20HP 22HP 24HP Remarks Piping Accessories Gas side Connecting Piping Ø25 4 Ø28 58 Ø25 4 Ø28 58 Ø25 4 Ø28 58 Ø25 4 Ø28 58 Liquid Side Connecting Piping Ø12 7 Ø15 88 Silencer Ø28 58 Ø28 58 Refrigerant Label Magnet Ring Filter Tie IOM NOTE More informations about accessories...

Page 17: ...r at the top of the outdoor unit and the inlet of the heat exchanger 8 When performing heating and defrosting operation the outdoor unit discharges condensate Provide a suitable drain around the foundation If the outdoor unit installed on the roof balcony or corridor and other places prevent condensate from dropping to the people walking on the road Otherwise during the winter condensates freezes ...

Page 18: ... must be met If the appliance is surrounded by more than 2 walls ensure to meet the following installation space When the upper obstacle and the unit is less than 1 5 meters or no space above the air outlet side of the air duct to prevent short circuit When there is an obstacle above in principle it is required that there are no obstacles around the unit Front rear left right 1 When both sides hav...

Page 19: ...rrounded by walls at 4 sides Min 200 Min 200 Top View Front Side Min 800 Opening No limit for this side wall height No limit for this side wall height Min 300 h1 2 Min 500 h2 2 mm Top View Front Side No limit for this side wall height Min 200 Min 200 Min 500 h2 2 Min 200 Min 200 Front Side Min 900 Min 300 h1 2 Top View Front Side Min 200 Min 200 Min 200 Min 500 h2 2 Front Side Min 1600 Min 200 Sid...

Page 20: ...n conditions and the calculation of outdoor unit return airflow 5 When multiple outdoor units are installed in the same direction you can install a maximum of six outdoor units The minimum distance between two adjacent outdoor units should be at least 1m 1 Group Max 6 Outdoor Units Min 1m 5 4 Foundation Concrete Foundation 1 The foundation should be 150 mm higher than the ground 2 Set the drain di...

Page 21: ...t get toppled by earthquake or strong winds 5 When installing the outdoor unit use the field supplied anchor bolts to mount the machine Refer to Figure 5 1 to confirm the position of mounting hole 8 12HP mm 16 5 16 5 729 4 20X15 688 131 131 Hole for anchor bolt 4 80X80 Vibration proof mat 16 5 729 948 131 131 4 20X15 Hole for anchor bolt 6 80X80 Vibration proof mat 16 5 16 5 16 5 729 1340 131 131 ...

Page 22: ...ay drip onto the pedestrian Setup an additional water tray if you have to install it in such places 3 When the outdoor unit needs a drain pipe use a drain pipe joint device optional model DC 01Q In cold areas do not use the drain pipe on the water tray as the condensed water may freeze inside the pipe resulting in drain pipe burst Drain Ø26X2 Drain pipe outlet position optional 113 367 267 114 720...

Page 23: ...system Do not allow oxygen acetylene or other flammable and toxic gases to fill the refrigerant pipe during leakage and air tightness test These gases are very dangerous and may cause an explosion It is recommended to use nitrogen Ensure that there is no pressure inside the stop valve when removing the cap on the stop valve CAUTION Make sure that the refrigerant piping is connected in the same ref...

Page 24: ...s pipe After the job is completed check for leakages NOTE Refrigeration oil should be supplied on site Model FV68H 3 If the temperature and relative humidity inside the ceiling are more than 27 C 80 apply a layer of insulation pipe about 10 mm in thickness to the outer surface of the original insulation pipe The insulation pipe attached to the refrigerant pipe to prevent the formation of condensed...

Page 25: ... 78 JVOH780VAEMBQ 50 8 22 2 34 JVOH340VAEMBQ 31 75 19 05 80 JVOH800VAEMBQ 50 8 22 2 36 JVOH360VAEMBQ 38 1 19 05 82 JVOH820VAEMBQ 50 8 22 2 38 JVOH380VAEMBQ 38 1 19 05 84 JVOH840VAEMBQ 50 8 22 2 40 JVOH400VAEMBQ 38 1 19 05 86 JVOH860VAEMBQ 50 8 22 2 42 JVOH420VAEMBQ 38 1 19 05 88 JVOH880VAEMBQ 50 8 22 2 44 JVOH440VAEMBQ 38 1 19 05 90 JVOH900VAEMBQ 50 8 25 4 46 JVOH460VAEMBQ 38 1 19 05 92 JVOH920VAE...

Page 26: ...e as shown in the table below 900 20 450 20 0 4 0 8R ØA Ød mm Diameter Ød A 0 0 4 R410A 6 35 9 1 9 52 13 2 12 7 16 6 15 88 19 7 19 05 It is impossible to perform the flaring work with 1 2H material In this case use an accessory pipe with a flare Joint selection If you use 1 2H material pipe it cannot be flared In this case the joints shown in the table below can be used Minimum wall thickness of t...

Page 27: ...r unit D Outdoor unit B Outdoor unit C Outdoor unit D LA LB LC LD Indoor unit side Maximum lift difference between outdoor unit height is 100mm 2 Take 4 module combination of outdoor units as an example Installation position of branch pipe at outdoor unit side should be lower than the position of outdoor unit piping outlet If the installation position of the branch pipe is higher than the position...

Page 28: ... the outdoor unit piping in a horizontal plane or with the indoor side of the pipe connected to the downward tilt state otherwise the system may accumulate cooling oil in the pipeline Indoor unit side Indoor unit side refrigerant oil accumulate in pipe 5 Take 3 module combination of outdoor units as an example For maintenance if the piping is installed in front of the outdoor unit ensure that the ...

Page 29: ...Refrigerant piping can be connected in three directions of the outdoor unit Front Connect the piping from the piping entrance at the unit chassis and then run it through the front opening of the chassis Bottom Directly connect the piping from the piping entrance at the unit chassis Rear Connect the piping from the piping entrance at the unit chassis and then run it through the rear opening of the ...

Page 30: ... 88 Model JVOH160VPEMBQ JVOH180VPEMBQ JVOH200VPEMBQ JVOH220VPEMBQ JVOH240VPEMBQ Pipe size a Gas pipe 28 58 28 58 31 75 28 58 28 58 31 75 28 58 28 58 31 75 28 58 28 58 31 75 28 58 28 58 31 75 Liquid pipe 12 7 12 7 15 88 15 88 15 88 19 05 15 88 15 88 19 05 15 88 15 88 19 05 15 88 15 88 19 05 6 4 2 JVOH260VAEMBQ JVOH480VAEMBQ Piping Specifications 2 Module Combinations Indoor unit on the left Indoor ...

Page 31: ...e The outdoor unit A JVOH220 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ The outdoor unit B JVOH160 VPEMBQ JVOH160 VPEMBQ JVOH180 VPEMBQ JVOH200 VPEMBQ JVOH220 VPEMBQ JVOH240 VPEMBQ Branch Pipe JM 46SNQ Piping Size a Gas pipe 38 1 38 1 44 45 38 1 38 1 44 45 38 1 38 1 44 45 38 1 38 1 44 45 38 1 38 1 44 45 38 1 38 1 44 45 Liquid pipe 19 05 19 05 22 2 19 05 19 05...

Page 32: ...12 7 12 7 12 7 12 7 3 Module Combination Table Ømm Model JVOH620 VAEMBQ JVOH640 VAEMBQ JVOH660 VAEMBQ JVOH680 VAEMBQ JVOH700 VAEMBQ JVOH720 VAEMBQ Combination Mode The outdoor unit A JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ The outdoor unit B JVOH220 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ JVOH240 VPEMBQ The outdoor unit C...

Page 33: ...VOH160 VPEMBQ JVOH160 VPEMBQ JVOH160 VPEMBQ JVOH200 VPEMBQ JVOH200 VPEMBQ JVOH200 VPEMBQ The outdoor unit D JVOH160 VPEMBQ JVOH160 VPEMBQ JVOH160 VPEMBQ JVOH200 VPEMBQ JVOH200 VPEMBQ JVOH200 VPEMBQ Branch Pipe 1 JM 68SNQ Branch Pipe 2 JM 30SNQ Branch Pipe 3 JM 30SNQ Piping Size a Gas pipe 50 8 50 8 50 8 50 8 50 8 50 8 Liquid pipe 22 2 22 2 25 4 22 2 22 2 25 4 22 2 22 2 25 4 22 2 22 2 25 4 22 2 22 ...

Page 34: ...28 58 28 58 28 58 28 58 28 58 Liquid pipe 15 88 15 88 15 88 15 88 15 88 15 88 e Gas pipe 28 58 28 58 28 58 28 58 28 58 28 58 Liquid pipe 15 88 15 88 15 88 15 88 15 88 15 88 f Gas pipe 28 58 28 58 28 58 28 58 28 58 28 58 Liquid pipe 15 88 15 88 15 88 15 88 15 88 15 88 g Gas pipe 28 58 28 58 28 58 28 58 28 58 28 58 Liquid pipe 15 88 15 88 15 88 15 88 15 88 15 88 Outdoor unit pipe constructing as per...

Page 35: ... Service port Only for refrigerant charge Valve close torque 15 N m Cap Tightening torque b N m O ring Refrigerant pressure Hexagon wrench Counter clockwise open Clockwise close Tightening torque a N m Refrigerant pipe Stop Valve Torque Outdoor Unit Model Liquid Side Stop Valve Gas Side Stop Valve Torque a N m Torque b N m Torque a N m Torque b N m JVOH080VPEMBQ 7 9 33 42 18 22 49 58 JVOH100VPEMBQ...

Page 36: ...kness mm Tightening torque N m Metric series mm Imperial series mm in 6 0 8 14 18 6 35 1 4 0 80 14 18 7 94 5 16 0 80 33 42 8 0 80 33 42 9 52 3 8 0 80 33 42 10 0 80 33 42 12 0 80 50 62 12 7 1 2 0 80 50 62 15 0 80 63 77 15 88 5 8 0 95 63 77 18 1 00 90 110 19 06 3 4 1 00 90 110 Pipe valve connection details JVOH 080 200 JVOH 120 180 JVOH 140 160 220 240 JVOH 100 Liquid side stop valve Liquid side pip...

Page 37: ... 2 Liquid Branch pipe 1 Liquid Branch pipe 1 Gas Branch pipe 3 Liquid Branch pipe 3 Gas Liquid piping Field Supplied Gas piping Liquid piping Field Supplied Gas piping Field Supplied Field Supplied Base Note Branch piping should be installed with the ground level horizontal tilt angel 15 degrees For Piping from Lower Side Note Branch piping should be installed with the ground level horizontal tilt...

Page 38: ...pe L1 100 Liquid Pipe L1 100 Gas Pipe L1 100 Liquid Pipe L1 100 8 22 4 19 05 9 52 22 2 12 7 10 28 0 22 2 9 52 25 4 12 7 12 33 5 25 4 12 7 28 58 15 88 14 40 0 25 4 12 7 28 58 15 88 16 45 0 28 58 12 7 31 75 15 88 18 50 0 28 58 15 88 31 75 19 05 20 56 0 28 58 15 88 31 75 19 05 22 61 5 28 58 15 88 31 75 19 05 24 68 0 28 58 15 88 31 75 19 05 26 73 0 31 75 19 05 38 1 22 2 28 78 5 31 75 19 05 38 1 22 2 3...

Page 39: ... Gas Pipe Liquid Pipe Compact Ducted Indoor Unit Medium ESP Ducted Indoor Unit High ESP Ducted Indoor Unit Floor Concealed Indoor Unit 18 45 12 7 6 35 5 50 56 15 88 6 35 5 63 160 15 88 9 52 Round way Cassette Indoor Unit 2 way Cassette Indoor Unit High Wall Indoor Unit 22 63 12 7 6 35 5 71 160 15 88 9 52 Fresh Air Ducted Indoor Unit 65 108 15 88 9 52 168 19 05 9 52 210 22 2 9 52 300 400 25 4 12 7 ...

Page 40: ...and 16 28 58 12 7 18 28 58 15 88 20 28 58 15 88 22 28 58 15 88 24 28 58 15 88 26 31 75 19 05 28 31 75 19 05 30 31 75 19 05 32 31 75 19 05 34 31 75 19 05 36 38 1 19 05 38 38 1 19 05 40 38 1 19 05 42 38 1 19 05 44 38 1 19 05 46 38 1 19 05 48 38 1 19 05 50 38 1 19 05 52 38 1 19 05 54 38 1 19 05 56 44 45 19 05 58 44 45 19 05 60 44 45 19 05 62 44 45 19 05 64 44 45 19 05 66 44 45 19 05 68 44 45 22 2 70 ...

Page 41: ...ch pipe is larger than the piping size of the pipe before the branch pipe adjust it to the same size as the size of the piping after the branch pipe 4 The pipe diameter is same as the piping diameter of indoor units 5 When the length of the liquid pipe is longer than 15m use Ø9 52 pipe and reducer 6 Please keep the linear distance of 500mm or more from the branch pipe of outdoor unit 7 The install...

Page 42: ...ranch pipe should not be less than 40m g h j b d 40m b a c e d f i j k h g L2 L2 The length of the piping from the end of first branch pipe to the end indoor unit is more than 40 meters and less than 90m First branch multi kit The nearest indoor unit from the first branch The farthest indoor unit from the first branch Terminal indoor unit Terminal indoor unit Example 2 From the first branch of the...

Page 43: ...1 Ensure that the electrical components main power circuit breakers wires electrical conduit connections and terminals used in the installation site are selected as per the requirements specified in technical manual The specifications are compliant with national electrical code Power on each outdoor unit Each outdoor unit should use earth leakage circuit breakers circuit breakers and main switches...

Page 44: ...utdoor unit communication wire Grounding screw Crimp cable fixing power wire 8 12HP Communication terminal Power supply terminal Grounding screw Crimp cable fixing power wire Shield grounding Indoor unit outdoor unit communication wire Outdoor unit outdoor unit communication wire Cable ties for fixing communication wires Strap for fixing communication wires 14 16HP ...

Page 45: ...ties for fixed communication wires Crimp cable fixing power wire 18HP Grounding screw Power supply terminal Grounding screw Communication terminal Shield grounding Indoor unit outdoor unit communication wire Outdoor unit outdoor unit communication wire Cable ties for fixing communication wires Crimp cable fixing power wire Power supply terminal 20 24HP Figure 7 1 Wire connection ...

Page 46: ...t Ground wires outdoor unit Communication wire outdoor Indoor unit Communication cable outdoor outdoor unit Power wire indoor unit Ground wire indoor unit Outdoor Unit power unit Supply 380 415V 3N 50Hz Indoor unit Power supply 2 Recommended wire ELB and switching capacity is shown in Table 7 1 Table 7 1 Electrical Parameters And Recommendations Wires ELB Earth Leakage Breaker capacity per outdoor...

Page 47: ...mm 7 If the power wire is damaged must contact the professional of dealer or the designated service for repairing and exchanging 8 When installing the power wire the ground wire should be longer than the current carrying wire Table 7 2 Power Wire Selection Principle Current A Wire size mm i 6 2 5 6 i 10 2 5 10 i 16 2 5 16 i 25 4 25 i 32 6 32 i 40 10 40 i 63 16 CAUTION To install multi stage master...

Page 48: ...ed Tightening Torque Size Tightening Torque M4 1 0 1 3 N m M5 2 0 2 4 N m M6 4 0 5 0 N m M8 9 0 11 0 N m M10 18 0 23 0 N m Communication terminal Indoor unit outdoor unit Add magnet ring which is winded with 3 loops by communcation wire outdoor unit outdoor unit communication wire Cable ties for fixing communication wires Ground terminal Grounding screw Cable clamp fixing power wire For power wire...

Page 49: ...e 20 24HP Refer to 18HP TB2 1 3 2 4 Indoor unit outdoor unit Outdoor unit outdoor unit Grounded Shield Grounded Shield Shielded communication wire between outdoor units Shielded communication wire between indoor and outdoor units PCB3 Power wire Ø65 knockout hole Communication wire Ø33 knockout hole Communication wire Tie Ground terminal Install insulated sheath Ground wire Cable clamp TB1 Power t...

Page 50: ...t system connect the communication cable to the same indoor unit in the case where the refrigerant pipe of the indoor unit is connected to the outdoor unit If you connect the refrigerant pipe and communication wires to different refrigerant circulation system malfunction may be caused 5 Use 2 core cable communication wire such as shielded twisted pair Do not use 3 core or 3 more core wire 6 Use th...

Page 51: ... refrigerant groups with one central controller is 64 For H Link II Maximum number of indoor unit connectable is 160 6 Wire specifications Transmission Wire 2 Wire Polarity of Transmission Wire Non Polar Wire Maximum Wiring Length Total 1 000m Recommended Cable Twist Pair Cable with Shield over 0 75mm2 Voltage DC5V TB1 TB1 TB2 L1L2 L3 N L1 L2 L3 N TB2 1 2 3 4 1 2 3 4 TB1 1 2 A B 1 2 A B TB2 TB2 TB...

Page 52: ...t 1 digit single RSW1 Refrigerant system single digit setting Setting before shipment JVOH080VPEMBQ JVOH100VPEMBQ JVOH120VPEMBQ JVOH140VPEMBQ JVOH160VPEMBQ JVOH180VPEMBQ JVOH200VPEMBQ JVOH220VPEMBQ JVOH240VPEMBQ Test run service setting Setting before shipment 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 1 ON 2 3 4 5 6 Setting before shipment Cooling test run Heating test run Reverse phase overcurrent detection ...

Page 53: ...efrigerant no for the outdoor unit and indoor unit should be set to the same 3 2 1 4 ON 5 6 DSW1 RSW1 RSW Refrigerant system single digit setting Setting Refrigerant system ten digit setting before shipment Setting before shipment DSW1 and RSW1 factory set to the 0 The maximum number of refrigerant system is set to 63 Terminal resistance setting At the factory position 1 of the DSW10 is set to ON ...

Page 54: ...LINK II H LINK or H LINK II H LINK or H LINK II indoor unit indoor unit indoor unit indoor unit Terminal resistance setting Function Setting 1 External Input Output and Function Setting 1 External Input Output and Function Setting Method 1 Setting start When unit is stopped set DSW4 No 4 to ON and set DSW4 No 6 to ON 2 Setting end Set DSW4 No 6 to OFF and Set DSW4 No 4 to OFF 2 External Input Outp...

Page 55: ...se setting 1 12 Low noise setting 2 13 Low noise setting 3 0 No Setting No setting Same input output function cannot be set to different input output terminal Otherwise the larger function number setting will be invalid 2 Function selection Setting 1 Function selection Setting Method 1 Setting start When unit is stopped set DSW4 No 4 to ON and set DSW4 No 5 to ON 2 Setting end Set DSW4 No 5 to OFF...

Page 56: ... 34 Compressor Maximum Frequency Suppression 11 Indoor Expansion Valve Target Value Control for Heating 35 Convert Unit in Checking Mode 12 Indoor Expansion Valve Opening Control During Heating Operation Stoppage 36 Indoor Fan ON OFF Setting during Forced Stoppage 13 Indoor Expansion Valve Opening Control During Heating Thermo Off 37 N A 14 Indoor Expansion Valve Initial Opening Control During Hea...

Page 57: ...k specially to the test joint of the liquid valve Conduct air tightness test Connect the regulating valve to the check joint of the outdoor liquid side valve and do not open the liquid side stop valve Ensure that the nitrogen pressure is 4 15MPa DANGER Ensure that you carry out air tightness test only with nitrogen If other gases such as oxygen acetylene or carbon hydrocarbon gas are used for airt...

Page 58: ... hold for 1 hour Make sure that the pressure on the regulating valve does not go high 3 After vacuuming tighten the inspection joint valve cap of liquid side stop valve torque 14 18 N m Prompt 1 In case of direct touch with the new refrigerant R410A use specified tools and instruments 2 If the pressure for vacuum cannot reach 0 1MPa 756mm Hg indicates that there may be leakage In this case perform...

Page 59: ...19 05 m x 0 28 kg ø22 2 m x 0 36 kg ø25 4 m x 0 52 kg ø28 58 m x 0 67 kg Total additional charge of liquid pipe kg kg NOTE If the indoor units are all Cassette in addition the models are JDCK028H0PAGQ JDCK040H0PAGQ JDCK080H0PAGQ JDCK090H0PAGQ the minimum amount of additional refrigerant W1 is shown in the table below Outdoor Unit HP 8 10 12 14 18 20 24 26 28 34 36 42 44 48 W1 the minimum amount of...

Page 60: ... 0 JVOH100VPEMBQ 5 0 JVOH120VPEMBQ 7 2 JVOH140VPEMBQ 8 9 JVOH160VPEMBQ 9 9 JVOH180VPEMBQ 10 7 JVOH200VPEMBQ 11 3 JVOH220VPEMBQ 11 3 JVOH240VPEMBQ 12 6 The additional total amount of refrigerant W kg Total amount of refrigerant kg Charge date year month day Note Wo is the refrigerant charging amount at factory With the base module combination need to calculate the total refrigerant charging amount ...

Page 61: ...refrigerant in system kg Critical concentration 0 42 kg m Control space of indoor unit m The critical concentration value is determined by national laws and regulations For example IS05149 and EN378 If the detected concentration is greater than 0 42 kg m take the following measures 1 Prepare a leak detector and exhaust fan used for operation control 2 Open the ventilation openings in the walls or ...

Page 62: ...e is low the units do not run immediately stop code d1 22 If starting operation within 2hours of power on follow the steps below to lift the protection 1 Turn on the power to the outdoor unit 2 Wait for 30 seconds 3 Press and hold the PSW5 button on the outdoor unit for more than 3 seconds to release the protection code d1 22 5 Identification of master unit With the combination of base modules to ...

Page 63: ...on on the remote control for more than 5 seconds enables the test mode For other optional wired controllers wireless remote controller and micro controller refer to the installation and operation manual attached to the wired controller If a wired controller controls multiple indoor units operational at the same time check the number of units connected to the indoor unit on the LCD screen If the nu...

Page 64: ...ther ensure that the refrigerant line and electrical wire are set in the same system d During the run temperature control is invalid though the protection device is valid If an alarm comes please figure out the cause of the abnormality according to alarm code shown in table 9 2 and re start the test run after the failure being solved As per the spot check label attached on the back surface of the ...

Page 65: ...pressure Mpa Intake pressure Mpa 9 Inspect voltage Rated voltage V Operation voltage L1 L2 V L1 L3 V L2 L3 V Start voltage V Imbalance between phrases 1 V Vm _____________ 10 Inspect compressor input operation current Input power kW Operation current A 11 Is the charge amount of refrigerant appropriate 12 Is the operation control device correct 13 Does the safety device act correctly 14 If the sys...

Page 66: ...cient refrigerant expansion valve lock wiring piping connection error thermistor fault valve room outdoor unit refrigerant electrical system connection error 0A Communication Communication abnormal between outdoor units Communication wire connection error wire disconnected terminal loosening 0b The Outdoor Unit The outdoor unit address is incorrect The same system has two sets of the same set of o...

Page 67: ...cient refrigerant pipe clogged expansion valve locked in the open position loose wiring 48 Overload operation protection action Overload operation compressor abnormalities 51 Sensor Inverter current sensor is abnormal Current sensor failure 53 Frequency Converter The inverter signal detection is incorrect IC driver program detects errors over current low voltage short circuit protection 54 Inverte...

Page 68: ... 0 05 0 15 Cut in Mpa 3 20 0 15 3 20 0 15 3 20 0 15 Fuse capacity A 25 32 32 Crankcase heating capacity W 40 2 40 2 40 2 CCP timer setting time min 3 3 3 Model JVOH140VPEMBQ JVOH160VPEMBQ JVOH180VPEMBQ Compressor Automatic reset not adjustable Pressure Switch 1 pcs per compressor High Pressure Cut out Mpa 4 15 0 05 0 15 4 15 0 05 0 15 4 15 0 05 0 15 Cut in Mpa 3 20 0 15 3 20 0 15 3 20 0 15 Fuse ca...

Page 69: ...Demo ...

Page 70: ...Demo ...

Page 71: ...Demo ...

Page 72: ...erant label 1 pc Filter 1 pc Insulated cotton 1 pc Tie some Qingdao Hisense Hitachi Air conditioning Systems Co Ltd Add Hisense Information Industry Park 218 Qianwangang Road Qingdao Economic Development Zone China Specifications in this catalogue are subject to change without notice in order that Hisense may bring the latest innovations to their customers P01373Q 2017 12 1098429 ...