![background image](http://html.mh-extra.com/html/york/jvoh080vpembq/jvoh080vpembq_installation-and-maintenance-manual_947512030.webp)
26
6.4.1 JVOH080VPEMBQ~JVOH240VPEMBQ Piping Specifications (Base Module)
a
Outdoor unit
Refrigerant piping
To indoor unit
(Ømm)
Model
JVOH080VPEMBQ JVOH100VPEMBQ JVOH120VPEMBQ JVOH140VPEMBQ
Pipe size
a
Gas
pipe
19.05
19.05~22.2
22.2
22.2~25.4
25.4
25.4~28.58
25.4
25.4~28.58
Liquid
pipe
9.52
9.52~12.7
9.52
9.52~12.7
12.7
12.7~15.88
12.7
12.7~15.88
Model
JVOH160VPEMBQ JVOH180VPEMBQ JVOH200VPEMBQ JVOH220VPEMBQ JVOH240VPEMBQ
Pipe size
a
Gas
pipe
28.58
28.58~31.75
28.58
28.58~31.75
28.58
28.58~31.75
28.58
28.58~31.75
28.58
28.58~31.75
Liquid
pipe
12.7
12.7~15.88
15.88
15.88~19.05
15.88
15.88~19.05
15.88
15.88~19.05
15.88
15.88~19.05
6.4.2 JVOH260VAEMBQ~JVOH480VAEMBQ Piping Specifications (2-Module Combinations)
(Indoor unit on the left)
(Indoor unit on the right)
To indoor unit
Branch pipe
Branch pipe
To indoor unit
a
a
b
b
c
c
Outdoor unit A
Outdoor unit A
Outdoor unit B
Outdoor unit B