036-21323-002-C-0206
8
Unitary Products Group
TABLE 6: OUTDOOR UNIT PHYSICAL DATA
Description
Unit Model
HB180
HB240
Compressor
1
Rating - (Qty) Tons
2 X 7.5 = 15 Tons
2 X 10 = 20 Tons
Fans
Quantity
2
2
Diameter - inches
24
24
Blades/Pitch (°)
3/34
3/32
Nominal CFM
12,400
11,400
Fan Motors
2
HP
1
1.5
RPM
1140
1100
Coil
Rows Deep X Rows High
2 X 30
2 X 30
Finned Length - inches each slab
60
78
Face Area - square feet (both slabs)
25
32.5
Tube(Copper) OD - inches
3/8
3/8
Fins(Aluminum) per inch
16
16
Refrigerant - 22 (lbs -oz.)
Holding Charge (sys1/sys2)
3
1 - 0 / 1 - 0 lbs.
1 - 0 / 1 - 0 lbs.
Operating Charge (sys1/sys2)
4
14.0/14.0 lbs.
17.0/17.0 lbs.
Unit Weight (lbs)
Shipping
944
1380
Operating
957
1396
1. These compressors are fully hermetic.
2. The ball bearing, 56 frame, single phase condenser fan motors have internal protection and are directly connected to the condenser fans. Motor
rotation is counterclockwise when viewing the lead end, which is opposite the shaft end.
3. The amount of charge in the unit as shipped from the factory.
4. Total operating charge for the condensing unit, matching indoor unit, and 25 feet of interconnecting pipe.
TABLE 7: INDOOR UNIT PHYSICAL DATA
Description
Unit Model
LB180
LB240
Coil
Rows Deep X Rows High
3 X 32
3 X 40
Finned length- Inches
83
81
Face Area - Square Feet
18.4
22.5
Tube (Copper) OD - Inches
3/8
3/8
Fins (Aluminum) per Inch
13
16
Centrifugal Blower
(Forward Curve - Qty)
Diameter X Width - Inches
15 X 12 - 2
18 X 18 - 2
Blower Motor
1
HP
Field Installed
RPM
--
--
Filters
(Throwaway)
Quantity Per Unit
4/4
10
Size - Inches
20 X 21 X 2 & 22 X 24 X 2
20 X 25 X2
Total Face Area - Square Feet
25.8
34.7
Unit Weight (lbs)
Shipping
720
990
Operating
830
1115
Accessory Operating
Weight (lbs)
Motor & Drive
3HP
47
--
5HP
120
120
Supply Air Plenum
185
N/A
Return Air Grille
25
N/A
Base
140
210