036-21323-002-C-0206

Unitary Products Group

3

DESCRIPTION

Both the outdoor and indoor units are completely piped and
wired at the factory and are shipped ready for immediate
installation. Only the interconnecting liquid and suction lines,
control wiring, and the main power wiring are required to
complete the installation. Every outdoor unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig
before being pressurized with a holding charge of refrigerant-
22 for shipment and/or storage.

To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel.
After fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a desert sand
powder paint to assure a quality finish for many years. This
coating system has passed the 750-hour, salt spray test per
ASTM Standard B117. 

APPLICATION FLEXIBILITY OUTDOOR

The outdoor units are lightweight and can be installed on
almost any roof.

Units can be lifted using nylon straps with hooks at the holes
provided in the base rails, or they may be lifted with a forklift
through the slotted openings in the base rails.

A quality appearance and low sound levels make these units
suitable for most ground level locations.

APPLICATION FLEXIBILITY INDOOR

The indoor units are built in a single cabinet with one conden-
sate drain pan. These units can be installed in either the verti-
cal or horizontal position for maximum flexibility.

NOTE:

On vertical applications, the air velocity across the 
indoor coil keeps the condensate from dripping off 
the finned surface onto the filters.

NOTE:

On horizontal applications the unit must be installed 
with the condensate drain pan under the entire 
indoor coil.

NOTE:

The Supply Air Plenum and the Return Air Grille 
accessories can be used on either arrangement.

NOTE:

The Base accessory can only be used on the verti-
cal arrangement.

 

 FIGURE 1 -  TYPICAL INDOOR UNIT 

APPLICATIONS  

B L O W E R   M O T O R

L O C A T I O N

R E T U R N   A I R

D U C T   F L A N G E

B L O W E R

S E C T I O N

A I R   O U T

( S t d .   A r r a n g e m e n t )

B L O W E R

S E C T I O N

R E T U R N   A I R

D U C T   F L A N G E

A I R

I N

F I L T E R S

V E R T I C A L

P O S I T I O N

C O I L

S E C T I O N

E V A P O R A T O R

C O I L

H O R I Z O N T A L

P O S I T I O N

F I L T E R S

A L T E R N A T E   A I R

D I S C H A R G E   A R R A N G E M E N T S

N O T E : C E R T A I N   B L O W E R   P O S I T I O N S   A R E   N O T   R E C O M M E N D E D .

B E C A U S E   T H E   B L O W E R   M O T O R   S H O U L D   N O T   B E   M O U N T E D

U P S I D E   D O W N .

CONDENSER ONLY CAPACITY

*Power consumption includes outdoor fans and compressors only.

PSIG ºF

MBH

KW*

MBH

KW*

MBH

KW*

MBH

KW*

MBH KW* MBH KW*

61.5 35

255

17.2

243

18.6

231

20.1

219

21.9

207

23.9 195

26.2

68.5 40

275

17.6

263

19.0

250

20.6

238

22.4

225

24.4 212

26.7

76

45

296

18.1

283

19.5

270

21.1

257

22.9

243

24.9 230

27.2

84

50

319

18.7

305

20.0

291

21.6

277

23.4

263

25.5 248

27.7

61.5 35

191

12.7

182

13.7

172

14.9

163

16.2

153

17.7 143

19.4

68.5 40

207

13.0

197

14.0

187

15.2

177

16.5

167

18.0 157

19.8

76

45

224

13.3

214

14.4

203

15.5

193

16.9

182

18.4 171

20.2

84

50

241

13.7

230

14.7

219

15.9

208

17.3

197

18.8 186

20.6

240

180

Model HB

Suction 

Press. & 

Temperature of Air on Condenser Coil, ºF

65

75

85

95

105

115

Summary of Contents for HB 240

Page 1: ...ce port connections Refrigerant 22 holding charge Five minute compressor anti short cycle timer Two independent control circuits Compressor operation to 40 F Field installed Low Ambient VFD Control to...

Page 2: ...0 22 13 LB180 SUPPLY AIR PLENUM DIMENSIONS 23 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS 23 LIST OF TABLES Tbl Pg 1 UNIT APPLICATION DATA 7 2 ARI RATINGS COOLING AND SOUND 7 3 ELECTRICAL DATA COMPRESSO...

Page 3: ...vertical applications the air velocity across the indoor coil keeps the condensate from dripping off the finned surface onto the filters NOTE On horizontal applications the unit must be installed with...

Page 4: ...ad operation Field installed Pump Out Kit for applications where liquid slugging could be an issue FIGURE 2 INDOOR PRODUCT NOMENCLATURE YORK INDOOR PRODUCT NOMENCLATURE H A 120 C 0 0 A 2 A A A 1 A Mod...

Page 5: ...Base Sections are available to raise vertical indoor units above the floor Outdoor air may be introduced through these bases by cutting an access opening for the out door air duct connection These ba...

Page 6: ...Unitary Products Group FIGURE 4 VERTICAL ARRANGEMENTS LB180 AND LB240 FIGURE 5 HORIZONTAL ARRANGEMENTS LB180 AND LB240 CERTAIN BLOWER POSITIONS ARE NOT RECOMMENDED BECAUSE THE BLOWER MOTOR SHOULD NOT...

Page 7: ...rd 370 TABLE 3 ELECTRICAL DATA COMPRESSORS Model Number Compressors Power Supply System 1 System 2 RLA LRA RLA LRA HB180 208 230 3 60 25 6 190 0 25 6 190 0 HB180 460 3 60 12 8 95 0 12 8 95 0 HB180 575...

Page 8: ...ctly connected to the condenser fans Motor rotation is counterclockwise when viewing the lead end which is opposite the shaft end 3 The amount of charge in the unit as shipped from the factory 4 Total...

Page 9: ...er Wiring 2 1 8 KO 2 1 8 KO Control Wiring 7 8 KO 7 8 KO TABLE 9 UNIT CLEARANCES Location Dimensions Overhead Top 1 1 Units must be installed outdoors Overhanging structures or shrubs should not obstr...

Page 10: ...ON LOCATIONS TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES CONNECTION ENTRY SIZE A SUCTION LINE SYS 1 1 1 8 ID 15 Ton 1 3 8 ID 20 Ton B LIQUID LINE SYS 1 5 8 ID C SUCTION LINE SYS 2 1 1 8 ID 15 Ton...

Page 11: ...check the following 1 Suction line pressure drop due to friction at full capacity 2 Liquid line pressure drop due to friction at full capacity 3 Suction line velocity for oil return at part capacity a...

Page 12: ...should be sized for a friction loss equivalent to a 2 F change in saturation temperature or approximately 3psi sizing the lines for the proper return of oil is more important 5 These friction losses...

Page 13: ...145 7 123 4 101 0 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AIR...

Page 14: ...0 2 127 8 105 5 83 1 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AI...

Page 15: ...5 127 3 112 1 97 0 81 8 57 150 4 22 0 150 4 147 6 138 6 123 5 108 3 93 1 78 0 6000 72 174 2 23 3 129 7 112 2 94 7 77 2 59 7 N A N A 67 160 1 22 7 159 4 141 9 124 4 106 9 89 4 71 9 54 4 62 149 2 22 1 1...

Page 16: ...89 8 162 4 134 9 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR O...

Page 17: ...MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 115 CFM W B GROSS INPUT GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR...

Page 18: ...3 1 2 91 972 3 6 3 36 5600 688 1 9 1 76 776 2 4 2 24 859 2 9 2 68 924 3 3 3 05 981 3 8 3 56 5800 696 2 0 1 85 785 2 5 2 36 873 3 0 2 83 931 3 4 3 2 990 4 0 3 75 6000 647 1 9 1 78 704 2 1 1 95 794 2 7...

Page 19: ...N BLOWER PERFORMANCE 15 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 4200 4700 5200 5700 6200 6700 7200 7700 CFM ESP FIGURE 9 20 TON BLOWER PERFORMANCE 20 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2...

Page 20: ...8 1LD0437 800 1000 2LR04605032 184 230 460 1LD0437 800 1000 2LP04605058 184 575 1LD0437 800 1000 1LD0439 700 830 LB240 5 2LR04605023 184 208 1LD0438 580 720 1LD0439 700 830 2LR04605032 184 208 230 460...

Page 21: ...Ton Indoor Vertical 720 830 198 224 217 191 89 5 29 5 20 Ton Indoor Horizontal 990 1115 212 195 340 368 100 74 20 Ton Indoor Vertical 990 1115 281 254 276 305 100 36 5 FIGURE 10 HORIZONTAL APPLICATIO...

Page 22: ...TION D D D E LESS BOTTOM PANEL BLOWER SECTION J L K K KNOCKOUT FOR SUCTION PIPING KNOCKOUT FOR LIQUID PIPING KNOCKOUT FOR DRAIN PIPING 4 9 16 10 3 16 2 7 32 19 3 32 3 1 2 5 25 64 3 3 8 5 1 3 8 Knockou...

Page 23: ...036 21323 002 C 0206 Unitary Products Group 23 FIGURE 13 LB180 SUPPLY AIR PLENUM DIMENSIONS1 1 Shipped knocked down for field assembly FIGURE 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS...

Page 24: ...bration generated by the unit CONDENSER LA300 LB180 240 360 480 600 EACH UNIT SHALL BE ETL and cETL approved completely assembled for one piece shipping and rig ging leak pressure and functionally tes...

Reviews: