GUIDE SPECIFICATIONS

EVAPORATOR - LA300, LB180, 240, 360, 480 & 600

EACH UNIT SHALL BE:

covered by a 1-year limited parts warranty on the com-
plete unit.

In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance,
and equipped with a V-belt drive option that will permit
the blower RPM to be adjusted to meet the exact CFM
requirement of the system.

EACH UNIT SHALL HAVE:

a steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation;

exterior panels of 18 gauge steel, finished with baked
enamel to provide a long-lasting quality appearance;

removable panels to provide easy access to the internal
components for maintenance and service; and, 

A filter rack with 2” filters

THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED
THOSE SPECIFIED.

THE BLOWER MOTOR SHALL:

be mounted within the insulated cabinet t minimize the
transmission of sound to the surrounding space, and

Have a service factor of 1.15.

THE EVAPORATOR COIL SHALL:

Consist of copper tubes arranged in staggered rows,
mechanically expanded into aluminum fins, be draw-
through, and

include factory-mounted distributors, expansion valves
and solenoid valves for both capacity reduction and
pump down.

THE BLOWER WHEELS SHALL BE:

Dynamically balanced to minimize the levels of sound and
vibration generated by the unit.

CONDENSER - LA300, LB180, 240, 360, 480 & 600

EACH UNIT SHALL BE:

ETL and cETL approved.

completely assembled for one-piece shipping and rig-
ging.

leak pressure and functionally tested at the factory to
assure a trouble-free start-up after installation.

covered by a 1-year limited parts warranty on the com-
plete unit.

EACH UNIT SHALL HAVE:

a steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation.

zinc-coated steel that has been finished by a powder
paint process to provide a long-lasting, quality appear-
ance.

removable panels for easy access to all internal compo-
nents during maintenance and service.

THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED 
THOSE SPECIFIED IN THE PLANS.

EACH COMPRESSOR SHALL BE:

mounted on isolators to minimize the transmission of
vibration.

ALL CONDENSER COILS SHALL BE:

draw thru design.

constructed of copper tubes arranged in staggered rows
and mechanically expanded into aluminum fins.

THE CONDENSER FAN MOTOR(S) SHALL:

be directly connected to the condenser fans.

have permanently lubricated ball bearings.

have inherent overload protection.

be three phase.

be arranged for vertical discharge of the condenser air.

THE WIRING FOR EACH UNIT SHALL INCLUDE:

a crankcase heater (one per compressor).

all 24-volt temperature control circuit.

both high and low pressure cutouts.

Solid-state or internal line break compressor motor pro-
tection.

Condenser fan motor control to assure stable operation
at ambient temperature down to 40 °F.

THE REFRIGERANT PIPING OF EACH SYSTEM SHALL
INCLUDE:

a filter-drier shipped separately for field installation.

a liquid line, moisture-indicating, sight glass shipped
separately for field installation. 

liquid line and suction line valve shipped separately for
field installation.

Summary of Contents for HB 240

Page 1: ...ce port connections Refrigerant 22 holding charge Five minute compressor anti short cycle timer Two independent control circuits Compressor operation to 40 F Field installed Low Ambient VFD Control to...

Page 2: ...0 22 13 LB180 SUPPLY AIR PLENUM DIMENSIONS 23 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS 23 LIST OF TABLES Tbl Pg 1 UNIT APPLICATION DATA 7 2 ARI RATINGS COOLING AND SOUND 7 3 ELECTRICAL DATA COMPRESSO...

Page 3: ...vertical applications the air velocity across the indoor coil keeps the condensate from dripping off the finned surface onto the filters NOTE On horizontal applications the unit must be installed with...

Page 4: ...ad operation Field installed Pump Out Kit for applications where liquid slugging could be an issue FIGURE 2 INDOOR PRODUCT NOMENCLATURE YORK INDOOR PRODUCT NOMENCLATURE H A 120 C 0 0 A 2 A A A 1 A Mod...

Page 5: ...Base Sections are available to raise vertical indoor units above the floor Outdoor air may be introduced through these bases by cutting an access opening for the out door air duct connection These ba...

Page 6: ...Unitary Products Group FIGURE 4 VERTICAL ARRANGEMENTS LB180 AND LB240 FIGURE 5 HORIZONTAL ARRANGEMENTS LB180 AND LB240 CERTAIN BLOWER POSITIONS ARE NOT RECOMMENDED BECAUSE THE BLOWER MOTOR SHOULD NOT...

Page 7: ...rd 370 TABLE 3 ELECTRICAL DATA COMPRESSORS Model Number Compressors Power Supply System 1 System 2 RLA LRA RLA LRA HB180 208 230 3 60 25 6 190 0 25 6 190 0 HB180 460 3 60 12 8 95 0 12 8 95 0 HB180 575...

Page 8: ...ctly connected to the condenser fans Motor rotation is counterclockwise when viewing the lead end which is opposite the shaft end 3 The amount of charge in the unit as shipped from the factory 4 Total...

Page 9: ...er Wiring 2 1 8 KO 2 1 8 KO Control Wiring 7 8 KO 7 8 KO TABLE 9 UNIT CLEARANCES Location Dimensions Overhead Top 1 1 Units must be installed outdoors Overhanging structures or shrubs should not obstr...

Page 10: ...ON LOCATIONS TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES CONNECTION ENTRY SIZE A SUCTION LINE SYS 1 1 1 8 ID 15 Ton 1 3 8 ID 20 Ton B LIQUID LINE SYS 1 5 8 ID C SUCTION LINE SYS 2 1 1 8 ID 15 Ton...

Page 11: ...check the following 1 Suction line pressure drop due to friction at full capacity 2 Liquid line pressure drop due to friction at full capacity 3 Suction line velocity for oil return at part capacity a...

Page 12: ...should be sized for a friction loss equivalent to a 2 F change in saturation temperature or approximately 3psi sizing the lines for the proper return of oil is more important 5 These friction losses...

Page 13: ...145 7 123 4 101 0 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AIR...

Page 14: ...0 2 127 8 105 5 83 1 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AI...

Page 15: ...5 127 3 112 1 97 0 81 8 57 150 4 22 0 150 4 147 6 138 6 123 5 108 3 93 1 78 0 6000 72 174 2 23 3 129 7 112 2 94 7 77 2 59 7 N A N A 67 160 1 22 7 159 4 141 9 124 4 106 9 89 4 71 9 54 4 62 149 2 22 1 1...

Page 16: ...89 8 162 4 134 9 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR O...

Page 17: ...MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 115 CFM W B GROSS INPUT GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR...

Page 18: ...3 1 2 91 972 3 6 3 36 5600 688 1 9 1 76 776 2 4 2 24 859 2 9 2 68 924 3 3 3 05 981 3 8 3 56 5800 696 2 0 1 85 785 2 5 2 36 873 3 0 2 83 931 3 4 3 2 990 4 0 3 75 6000 647 1 9 1 78 704 2 1 1 95 794 2 7...

Page 19: ...N BLOWER PERFORMANCE 15 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 4200 4700 5200 5700 6200 6700 7200 7700 CFM ESP FIGURE 9 20 TON BLOWER PERFORMANCE 20 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2...

Page 20: ...8 1LD0437 800 1000 2LR04605032 184 230 460 1LD0437 800 1000 2LP04605058 184 575 1LD0437 800 1000 1LD0439 700 830 LB240 5 2LR04605023 184 208 1LD0438 580 720 1LD0439 700 830 2LR04605032 184 208 230 460...

Page 21: ...Ton Indoor Vertical 720 830 198 224 217 191 89 5 29 5 20 Ton Indoor Horizontal 990 1115 212 195 340 368 100 74 20 Ton Indoor Vertical 990 1115 281 254 276 305 100 36 5 FIGURE 10 HORIZONTAL APPLICATIO...

Page 22: ...TION D D D E LESS BOTTOM PANEL BLOWER SECTION J L K K KNOCKOUT FOR SUCTION PIPING KNOCKOUT FOR LIQUID PIPING KNOCKOUT FOR DRAIN PIPING 4 9 16 10 3 16 2 7 32 19 3 32 3 1 2 5 25 64 3 3 8 5 1 3 8 Knockou...

Page 23: ...036 21323 002 C 0206 Unitary Products Group 23 FIGURE 13 LB180 SUPPLY AIR PLENUM DIMENSIONS1 1 Shipped knocked down for field assembly FIGURE 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS...

Page 24: ...bration generated by the unit CONDENSER LA300 LB180 240 360 480 600 EACH UNIT SHALL BE ETL and cETL approved completely assembled for one piece shipping and rig ging leak pressure and functionally tes...

Reviews: