036-21323-002-C-0206
Unitary Products Group
7
TABLE 1: UNIT APPLICATION DATA
Application Limitations
Minimum
Maximum
Voltage Variation (208/230-3-60) - Volts
187
253
Voltage Variation (460-3-60) - Volts
414
506
Voltage Variation (575-3-60) - Volts
540
630
Ambient Air on Outdoor Coil (Cooling Cycle) - °F
45
115
Ambient Air on Indoor Coil (Cooling Cycle) - °F
68
86
TABLE 2: ARI RATINGS - COOLING AND SOUND
Model
Cooling Capacity
1
Cond. Unit
Sound
2
Rated Airflow
Rated ESP
Outdoor
Unit
Indoor Unit
MBH
EER
IPLV
dB
CFM
IWG
HB180
KB180
180
9.7
10.4
89.0
6000
0.35
HB240
KB240
240
9.7
10.4
90.0
8000
0.40
1. Ratings are in accordance with ARI standard 340/360.
2. Ratings are in accordance with ARI standard 370.
TABLE 3: ELECTRICAL DATA COMPRESSORS
Model
Number
Compressors
Power
Supply
System 1
System 2
RLA
LRA
RLA
LRA
HB180
208/230-3-60
25.6
190.0
25.6
190.0
HB180
460-3-60
12.8
95.0
12.8
95.0
HB180
575-3-60
10.2
75
10.2
75
HB240
208/230-3-60
42.0
239.0
42.0
239.0
HB240
460-3-60
19.2
125.0
19.2
125.0
HB240
575-3-60
13.8
80
13.8
80
TABLE 4: ELECTRICAL DATA FAN MOTORS
Model
Number
Condenser Fans
Power
Supply
Qty.
FLA
ea.
HB180
208/230-3-60
2
3.7
HB180
460-3-60
2
1.85
HB180
575-3-60
2
1.7
HB240
208/230-3-60
2
5.8
HB240
460-3-60
2
2.9
HB240
575-3-60
2
2.2
TABLE 5: ELECTRICAL DATA, OUTDOOR MCA & MAX. FUSE SIZE
Model
Number
Power
Supply
Min. Circuit
Ampacity
Max.
Fuse
Size
1
HB180
208/230-3-60
65.1
90
HB180
460-3-60
32.5
45
HB180
575-3-60
26.4
35
HB240
208/230-3-60
106.1
125
HB240
460-3-60
49.0
60
HB240
575-3-60
35.5
45
1. Maximum fuse or maximum circuit breaker (HACR type per NEC).