background image

4

Unitary Products Group

RE–ASSEMBLING, BRAZING AND 
CLEANING OF JOINT CONNECTIONS

When using hard solder, an inert gas such as dry ni-
trogen must be introduced and permitted to flow
through tubing during brazing to displace air and
prevent oxidation.

Remove the Schrader valve cores from the service
valves. Remove the plugs from the service valve field
tubing connections. Clean the joints to be brazed.

NOTE:  Do not overheat the connection to be brazed as

this can cause improper flow of solder, resulting
in a weak and leaking joint. Never apply heat
directly to face of fitting. Do not heat solder by
direct contact with flame of the torch.

When brazing copper tubing it is very important to pre-
heat the entire joint before applying the solder. This is
done by sweeping the flame steadily and evenly around
the fitting, to bring both fitting and tubing up to equal tem-
perature before applying the solder.

Reassemble groups of tubing and fittings, brazing sever-
al joints instead of one joint at a time. This reduces the
chance for error in the alignment of the assembly. Re-
place schrader valve cores. DO NOT OPEN SERVICE
VALVES AT THIS TIME.

NOTE:  Do not heat solder by direct contact with flame of

the torch.

INSULATION OF VAPOR LINE

Insulate vapor line with 3/8” (or that required by local
code) closed cell insulation.

Slide tubing insulation onto the vapor line so that it is cov-
ered completely from the indoor coil to the outdoor unit.
Be sure that the tubing is capped before sliding on insula-
tion.

It is not necessary to insulate the liquid line.

FIGURE 2 – INSULATION OF VAPOR LINE

INCORRECT

CORRECT

LIQUID
LINE

TAPE

SHEET METAL HANGER

INSULATED VAPOR LINE

ÎÎÎ

ÎÎÎ

ÎÎÎ

ÎÎÎ

ÎÎÎ

ÎÎÎ

ÉÉ

ÉÉ

ÎÎ

ÎÎ

ÎÎÎ

ÎÎÎ

ÎÎÎ

ÎÎÎ

NOTE:  In areas of extreme temperatures and humidity,

additional insulation may be required to prevent
excessive condensation and loss of capacity.

Do not insulate liquid line and vapor line together. Liquid
line should not be in contact with the vapor line. See Fig-
ure 2.

REFRIGERANT LINE SUPPORT

Refrigerant lines should be supported in a way that no
dips or sags occur. We recommend four feet between
supports. If refrigerant lines are to be attached to the
home structure, care should be taken to eliminate the
transmission of vibrations. Attach the refrigerant lines to
the indoor coil first. Remove plugs from the indoor coil,
then clean joints to be brazed. Braze refrigerant lines to
the indoor coil. Attach refrigerant lines to the outdoor unit.

CHARGING AND LEAK TESTING

On systems with or without service valves the refrigerant
should be recovered or recycled in accordance with EPA
regulations. In some cases this may require putting pierc-
ing valves on both the high and low sides of the system.

DO NOT vent refrigerant to the outdoors.

When recovering refrigerant from a system, with a burn-
out, follow a safe procedure due to possible contamina-
tion.

Avoid getting the refrigerant in the eyes or on the
skin.

Contaminated refrigerant must be recovered and re-
turned to the local refrigeration supply house for proper
disposition.

TOTAL LINE LENGTH

Units should be installed only with approved system com-
bination (indoor/outdoor) as specified in the Technical
Guide.

For systems with total line length exceeding 50 feet, see
APPLICATION DATA, 690.01–AD1V(1296) and work-
sheet 690.01–AD1.1V(791) “General Piping Recom-
mendations and Refrigerant Line Length” for vapor and
liquid line sizing, calibration of liquid line pressure loss or
gain, determination of vapor line velocity, elevation limita-
tions, orifice connections, system charging, traps, etc.

System with liquid line pressure loss or gain grater than
11 psi must be provided with corrected orifice size as
noted in Form 690.01 – AD1V (1296).

ORIFICE SELECTION

NOTE:  The proper orifice must be installed in the indoor

coil liquid line connection prior to the connection
of the refrigerant lines.

The indoor coil is under 35 psig (inert gas) pressure.

Summary of Contents for H1RA036

Page 1: ...t Category H Air Conditioning Outdoor Unit Product Generation 1 2 Design Level Product Identifier RA 10 Seer Split System Air Conditioner Refrigerant Line Connections S Sweat connect Voltage Code 25 208 230 3 60 46 460 3 60 Nominal Cooling Capacity 036 36 000 BTUH 048 48 000 BTUH 060 60 000 BTUH 076 76 000 BTUH 090 90 000 BTUH LIMITATIONS The manufacturer is not responsible for the perfor mance of...

Page 2: ...ee Figure 1 The length of the refrigerant tubing between the outdoor unit and indoor coil should be as short as possible to avoid capacity and efficiency loss Excessive spacing of the outside unit from the home can lead to the refrigerant lines being restricted by trampling or by being punctured by lawn mowers Locate unit away from bedroom windows or other rooms where sound might be objectionable ...

Page 3: ... all joints 8 Evacuate refrigerant lines and indoor coil 9 Charging refrigeration system if the line length is other than 15 feet See Table 2 Table 2 Refrigerant Line Charges Liquid OD Vapor OD R 22 Charge OZ FT 3 8 5 8 0 66 3 8 3 4 0 68 3 8 7 8 0 70 3 8 1 1 8 0 76 1 2 1 1 8 1 26 Use only ACR grade copper tubing and keep ends sealed until joints are made The correct diameters of the refrigerant li...

Page 4: ...acity Do not insulate liquid line and vapor line together Liquid line should not be in contact with the vapor line See Fig ure 2 REFRIGERANT LINE SUPPORT Refrigerant lines should be supported in a way that no dips or sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibrations Attac...

Page 5: ... and worksheet 690 01 AD1 1V 791 General Piping Recommendations and Refriger ant Line length Check the system for correct charge after all components of the system have been installed connected and wired correctly Connect service gauges to low pressure port and dis charge service ports Allow unit to operate until system pressures and temper atures have stabilized making sure that the pressure and ...

Page 6: ...stallation in structions Pig tail connector wires are provided from the low volt age pull in coil on the contractor to a section of the con trol box A fingered bushing is provided in the low volt age knockout hole If 1 2 conduit is used for the low voltage wiring the bushing is to be removed 1 Route the low voltage cable through the fingered bushing in the low voltage junction box See Figure 3 or ...

Page 7: ...OR 1 TERMINALS ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY JUNCTION BOX R B Y O W X 53 G 60 66 R G OUTDOOR UNIT RED 24 VAC BROWN COMMON YELLOW 1ST STAGE COOLING ORANGE 2ND STAGE COOLING RED YEL BRN ORG 090 ONLY Y R AND Y FIELD WIRING CONNECTED TO THESE DUMMY TERMINALS ON 4TB CAN BE ROUTED DIRECTLY FROM THE OUTDOOR UNIT TO THE THERMOSTAT IF DESIRED FIGURE 7 TYPICAL FIELD WIRI...

Page 8: ...been secured and iso lated properly Is the indoor coil drain hooked up and draining freely Pour water in drain pan Is air filter installed and clean Is blower motor speed set correctly SYSTEM OPERATION CHECK OUT Step 1 With thermostat set to the OFF position close disconnect switch or switches to complete circuits to condensing unit furnace or air handler Set thermostat to call for cooling Step 2 ...

Reviews: