background image

2

Unitary Products Group

 The maximum and minimum conditions for operation
must be observed to assure a system that will give maxi-
mum performance with minimum service.

Table 1 – Application Limitations

Ambient Air Temperature
on Outdoor Coil

Air Temperature on 
Indoor Coil

Min.

°

DB

Max. 

°

DB

Min. 

WB

Max. 

WB

50

120

57

72

CHECK ELECTRICAL POWER SUPPLY

The electrical power should be checked to determined if
adequate power is available, and near constant voltage
can be maintained. If there is any question concerning
the power supply, contact the local power company for
corrections; otherwise, unsatisfactory performance may
result.

SELECTING EQUIPMENT LOCATIONS

Several important factors must be considered before se-
lecting the best site for the air conditioning outside unit:

Distance to indoor coil

Proximity to the structure

Proximity to vents and exhaust systems

Ability to service

Sound transmission

Air circulation

Wind direction

Relationship between structure, sun, and unit

Distance from power source

Water drainage

Local codes

Locate the outside unit near enough to the indoor coil vi-
cinity to eliminate lengthy refrigerant line runs. Do not lo-
cate the outside unit so it discharges air under eaves or
gutters. Rain or snow melt–off should not be able to run
off a roof and down upon the unit. Be sure vents are not
located upwind from the outside unit.

A minimum clearance of 18 inches is required for service
at the control panel and compressor compartments ac-
cess. A 10 inch clearance is required for the air inlet to the
outdoor coil around the perimeter of the unit. The air dis-
charge of the unit requires a 60 inch clearance between
the top of the unit and any obstruction. See Figure 1.

The length of the refrigerant tubing, between the outdoor
unit and indoor coil, should be as short as possible to
avoid capacity and efficiency loss. Excessive spacing of
the outside unit from the home can lead to the refrigerant
lines being restricted by trampling or by being punctured
by lawn mowers. Locate unit away from bedroom windows
or other rooms where sound might be objectionable.

Adverse effects of prevailing winds, blowing snow or
sleet on the outdoor coil can be eliminated by placing the
outside unit where the wind does not blow across the unit.
Trees, shrubs, corners of buildings and fences standing
off from the coil can reduce capacity loss due to wind chill
effect.

Provide ample clearance from shrubs to allow adequate
air to pass across the outdoor coil without leaves or
branches being pulled into the coil.

Consideration should be given to the distance and rout-
ing of electrical service that would have to be run to con-
nect the outside unit.

It is recommended the outside unit be mounted on a con-
crete pad. Top of pad should be two inches above grade.

OUTDOOR UNIT

After the site has been selected a concrete base pad
should be provided. The concrete pad should not come in
contact with the foundation or side of the structure be-
cause sound may be transmitted to the residence. The
concrete pad need  not be any larger than the outside di-
mensions of the outdoor unit. The concrete pad should
be located far enough away from the structure so the out-
side unit is not closer than its minimum distances. See
Figure 1. Set the outside unit upon the pad with care to
avoid damage.

Do not remove the protective caps or plugs from the
unit refrigerant connections until the refrigerant lines
are run and ready for final connection. If this proce-
dure is not observed, dirt and other particles will get
into the system and plug various orifices and small
tubes.

Summary of Contents for H1RA036

Page 1: ...t Category H Air Conditioning Outdoor Unit Product Generation 1 2 Design Level Product Identifier RA 10 Seer Split System Air Conditioner Refrigerant Line Connections S Sweat connect Voltage Code 25 208 230 3 60 46 460 3 60 Nominal Cooling Capacity 036 36 000 BTUH 048 48 000 BTUH 060 60 000 BTUH 076 76 000 BTUH 090 90 000 BTUH LIMITATIONS The manufacturer is not responsible for the perfor mance of...

Page 2: ...ee Figure 1 The length of the refrigerant tubing between the outdoor unit and indoor coil should be as short as possible to avoid capacity and efficiency loss Excessive spacing of the outside unit from the home can lead to the refrigerant lines being restricted by trampling or by being punctured by lawn mowers Locate unit away from bedroom windows or other rooms where sound might be objectionable ...

Page 3: ... all joints 8 Evacuate refrigerant lines and indoor coil 9 Charging refrigeration system if the line length is other than 15 feet See Table 2 Table 2 Refrigerant Line Charges Liquid OD Vapor OD R 22 Charge OZ FT 3 8 5 8 0 66 3 8 3 4 0 68 3 8 7 8 0 70 3 8 1 1 8 0 76 1 2 1 1 8 1 26 Use only ACR grade copper tubing and keep ends sealed until joints are made The correct diameters of the refrigerant li...

Page 4: ...acity Do not insulate liquid line and vapor line together Liquid line should not be in contact with the vapor line See Fig ure 2 REFRIGERANT LINE SUPPORT Refrigerant lines should be supported in a way that no dips or sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibrations Attac...

Page 5: ... and worksheet 690 01 AD1 1V 791 General Piping Recommendations and Refriger ant Line length Check the system for correct charge after all components of the system have been installed connected and wired correctly Connect service gauges to low pressure port and dis charge service ports Allow unit to operate until system pressures and temper atures have stabilized making sure that the pressure and ...

Page 6: ...stallation in structions Pig tail connector wires are provided from the low volt age pull in coil on the contractor to a section of the con trol box A fingered bushing is provided in the low volt age knockout hole If 1 2 conduit is used for the low voltage wiring the bushing is to be removed 1 Route the low voltage cable through the fingered bushing in the low voltage junction box See Figure 3 or ...

Page 7: ...OR 1 TERMINALS ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY JUNCTION BOX R B Y O W X 53 G 60 66 R G OUTDOOR UNIT RED 24 VAC BROWN COMMON YELLOW 1ST STAGE COOLING ORANGE 2ND STAGE COOLING RED YEL BRN ORG 090 ONLY Y R AND Y FIELD WIRING CONNECTED TO THESE DUMMY TERMINALS ON 4TB CAN BE ROUTED DIRECTLY FROM THE OUTDOOR UNIT TO THE THERMOSTAT IF DESIRED FIGURE 7 TYPICAL FIELD WIRI...

Page 8: ...been secured and iso lated properly Is the indoor coil drain hooked up and draining freely Pour water in drain pan Is air filter installed and clean Is blower motor speed set correctly SYSTEM OPERATION CHECK OUT Step 1 With thermostat set to the OFF position close disconnect switch or switches to complete circuits to condensing unit furnace or air handler Set thermostat to call for cooling Step 2 ...

Reviews: