If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided on the access panel of the unit.

SUPERHEAT CHARGING METHOD - 

PISTON INDOOR

1.

Set the system running in cooling mode by setting the thermostat
at least 6°F below the room temperature and operate system for at
least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended airflow and ver-
ify indoor airflow (it should be about 400 SCFM per ton).

3.

Measure and record the outdoor ambient (DB) temperature and
the suction pressure at the suction service valve.

4.

Using the charging chart located on the unit, find the intersection
of the outdoor ambient dry bulb and the suction pressure obtained
in step 3. This is the recommended suction tube temperature at
the service valve.

5.

Measure and record the suction tube temperature at the service
valve and compare to the recommended temperature obtained in
step 4.

6.

Add charge if the measured suction temperature in step 5 is above
the recommended value. Remove / recover refrigerant if the mea-
sured suction temperature is below the recommended value.

SUBCOOLING CHARGING METHOD - TXV INDOOR

1.

Set the system running in cooling mode by setting the thermostat
at least 6°F below the room temperature and operate system for at
least 10 – 15 minutes.

2.

Refer to the technical guide for the recommended indoor airflow
and verify it is correct (it should be about 400 SCFM per ton).

3.

Measure and record the indoor wet bulb (WB) and the outdoor
ambient dry bulb (DB) temperature.

4.

Using the charging chart located on the unit, find the intersection
of the indoor wet bulb and the outdoor dry bulb. This is the recom-
mended liquid pressure (and subcooling value).

5.

Measure and record the pressure at the liquid valve pressure port
and compare to the value obtained in step 4.

6.

Add charge if the measured liquid pressure is lower than the rec-
ommended value. Remove / recover charge if the measured liquid
pressure is above the recommended value.

Condenser subcooling is obtained by calculating the difference of the
saturated refrigerant temperature of the pressure measured at the liquid
base valve and the liquid tube temperature as measured at the liquid
base valve.

Subcooling Temp. (TC) = Saturated Temp. (TS) – Liquid Temp. (T).

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The suction tube temperature listed on the table at the 
intersection of the outdoor DB and the suction pressure is 63°F. 
Temperature of the suction tube at the service valve is 68°F. It would 
be necessary to add refrigerant to drop the suction tube temperature 
to 63°F.

Example: The liquid pressure listed at the intersection of the indoor 
WB and the outdoor DB 320 psig. Pressure at the liquid valve is 305 
psig. It would be necessary to add refrigerant to increase the liquid 
pressure to 320 psig.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL
OF THIS UNIT.

TABLE 2: 

R-22 Saturation Properties

Press

Temp

Press

Temp

Press

Temp

Press

Temp

Press

Temp

Press

Temp

Press

Temp

psig

°F

psig

°F

psig

°F

psig

°F

psig

°F

psig

°F

psig

°F

70

41

100

59

130

74

160

87

190

98

220

108

250

117

72

42

102

60

132

75

162

88

192

99

222

109

252

118

74

44

104

61

134

76

164

88

194

99

224

109

254

118

76

45

106

62

136

77

166

89

196

100

226

110

256

119

78

46

108

63

138

78

168

90

198

101

228

111

258

119

80

48

110

64

140

78

170

91

200

101

230

111

260

120

82

49

112

65

142

79

172

91

202

102

232

112

262

121

84

50

114

66

144

80

174

92

204

103

234

112

264

121

86

51

116

67

146

81

176

93

206

103

236

113

266

122

88

52

118

68

148

82

178

94

208

104

238

114

268

122

90

54

120

69

150

83

180

94

210

105

240

114

270

123

92

55

122

70

152

84

182

95

212

105

242

115

272

123

94

56

124

71

154

84

184

96

214

106

244

115

274

124

96

57

126

72

156

85

186

97

216

107

246

116

276

125

98

58

128

73

158

86

188

97

218

107

248

117

278

125

Summary of Contents for GCGA SERIES

Page 1: ...ndoor out door unit combinations elevation differences or total line lengths Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number 247077 SECTION II...

Page 2: ...ion must be observed to ensure a system that will give maximum performance with minimum service 4 The unit should not be operated at outdoor temperatures below 50 F without an approved low ambient ope...

Page 3: ...for approved system combinations as specified in tabular data sheet The initial charge given is applicable for total tubing lengths up to 15 feet 4 6 m See Application Data Part Number 247077 for inst...

Page 4: ...one quarter turn counterclockwise to open Do not overturn or the valve stem may break or become damaged See PRECAU TIONS DURING BRAZING SERVICE VALVE 8 Replace the Schrader core in the liquid and vap...

Page 5: ...s as a reservoir c Bulb should be insulated using thermal insulation provided to protect it from the effect of the surrounding ambient tempera ture Cover completely to insulate from air stream SECTION...

Page 6: ...r than the rec ommended value Remove recover charge if the measured liquid pressure is above the recommended value Condenser subcooling is obtained by calculating the difference of the saturated refri...

Page 7: ...75 49 90 57 105 65 120 72 135 79 150 85 165 90 76 49 91 58 106 66 121 73 136 79 151 85 166 91 77 50 92 58 107 66 122 73 137 80 152 86 167 91 78 50 93 59 108 67 123 74 138 80 153 86 168 91 79 51 94 60...

Page 8: ...lace it on an out side wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2...

Page 9: ...WER WIRING CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROO...

Page 10: ...actor R 24 Volt Hot Heat XFMR R 24 Volt Hot Heat XFMR E W1 Emergency Heat E W1 Emergency Heat AUX Auxiliary Heat R 24 Volt Hot Cool XFMR Y2 Second Stage Compressor Connection of the C terminal 24 Volt...

Page 11: ...terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 1 1 Heat 1 Cool Conventional Refer to AH documentation for W1 and W2 electric he...

Page 12: ...ct the owner on proper operation and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as o...

Page 13: ...TORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC O...

Page 14: ...2 T1 24 VAC CTRL CIRCUIT 20VA MIN BLU BLU RED BLK BRN RED BLK GND LUG GND CONTACTOR OPTIONAL LOW VOLTAGE WIRING 2 3 FIELD WIRING CTRL CIRCUIT BLK YEL PNK YEL PNK HPS COLOR CODE BLK BLACK BLU BLUE BRN...

Page 15: ...LL BE REMOVED IF LOW AMBIENT KIT IS INSTALLED YELLOW WIRE WILL BE REMOVED IF PRESSURE SWITCH KIT IS INSTALLED IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED W...

Page 16: ...548086 XIM C 0814 16 Johnson Controls Unitary Products NOTES...

Page 17: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 18: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: