background image

548086-XIM-C-0814

Johnson Controls Unitary Products

3

GROUND INSTALLATION

The unit should be installed on a solid base that is 2” (5.1 cm) above
grade and will not shift or settle, causing strain on the refrigerant lines
and possible leaks. Maintain the clearances shown in Figure 1 and
install the unit in a level position. The base pad should not come in con-
tact with the foundation or side of the structure because sound may be
transmitted to the residence.

The length of the refrigerant tubing between the outdoor unit and indoor
coil should be as short as possible to avoid capacity and efficiency
losses. Excessive spacing of the outdoor unit from the home can result
in the refrigerant lines being restricted by trampling or being punctured
by lawn mowers. Locate the outdoor unit away from bedroom windows
or other rooms where sound might be objectionable.

Adverse effects of snow or sleet accumulating on the outdoor coil can
be eliminated by placing the outdoor unit where the prevailing wind
does not blow across the unit. Trees, shrubs, corners of buildings, and
fences standing off from the coil can reduce capacity loss due to wind
chill effect.

Provide ample clearance from shrubs to allow adequate air to pass
across the outdoor coil without leaves or branches being pulled into the
coil.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

WALL MOUNT INSTALLATION

Care must be taken to mount the outdoor unit on a solid base that is
sloped to shed water, secure from settlement, and is isolated from the
structural foundation or walls to prevent sound and vibration transmis-
sion into the living space. In addition heat pump units must be elevated
above anticipated snow accumulation levels to allow for proper defrost
drainage and airflow. 

On occasion, site conditions may require direct wall mounted brackets
to be used to locate and support the outdoor unit. In these applications,
care must be taken to address unit base pan support, structural integ-
rity, safe access and serviceability, as well as the possible sound and
vibration transmission into the structure. These applications are best
served by a properly engineered solution. 

LIQUID LINE FILTER-DRIER

The air conditioning unit’s filter/dryer is located on the liquid line.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade (ACR) copper tubing that is

internally clean and dry. Units should be installed only with the tubing
sizes for approved system combinations as specified in tabular data
sheet. The initial charge given is applicable for total tubing lengths up to
15 feet (4.6 m). See Application Data Part Number 247077 for installing
tubing of longer lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2” foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humid-
ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow
tube metal-to-metal contact. See Figure 2.

6.

Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown.

7.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

8.

For systems with total line length exceeding 70 feet (21.3 m), see
APPLICATION DATA and worksheet “General Piping Recommen-
dations and Refrigerant Line Length” for vapor and liquid line siz-
ing, calibration of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice connections, sys-
tem charging, traps, etc.

Replacements for the liquid line drier must be exactly the same as
marked on the original factory drier. See Source1 for O.E.M.
replacement driers.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

S1-02922156000

18, 24, 30, 36

S1-02922157000

48, 60

S1-02614777712

76

NOTICE

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" (2.5 cm) every 20 feet (6.1 m) toward the out-
door unit to facilitate proper oil return.

 FIGURE 2:  

Installation of Vapor Line

 FIGURE 3:  

Underground Installation

NOTICE

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

A0151-001

TO INDOOR COIL

TO OUTDOOR UNIT

LIQUID LINE

CAP

PVC
CONDUIT

INSULATED

VAPOR LINE

A0152-001

Summary of Contents for GCGA SERIES

Page 1: ...ndoor out door unit combinations elevation differences or total line lengths Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number 247077 SECTION II...

Page 2: ...ion must be observed to ensure a system that will give maximum performance with minimum service 4 The unit should not be operated at outdoor temperatures below 50 F without an approved low ambient ope...

Page 3: ...for approved system combinations as specified in tabular data sheet The initial charge given is applicable for total tubing lengths up to 15 feet 4 6 m See Application Data Part Number 247077 for inst...

Page 4: ...one quarter turn counterclockwise to open Do not overturn or the valve stem may break or become damaged See PRECAU TIONS DURING BRAZING SERVICE VALVE 8 Replace the Schrader core in the liquid and vap...

Page 5: ...s as a reservoir c Bulb should be insulated using thermal insulation provided to protect it from the effect of the surrounding ambient tempera ture Cover completely to insulate from air stream SECTION...

Page 6: ...r than the rec ommended value Remove recover charge if the measured liquid pressure is above the recommended value Condenser subcooling is obtained by calculating the difference of the saturated refri...

Page 7: ...75 49 90 57 105 65 120 72 135 79 150 85 165 90 76 49 91 58 106 66 121 73 136 79 151 85 166 91 77 50 92 58 107 66 122 73 137 80 152 86 167 91 78 50 93 59 108 67 123 74 138 80 153 86 168 91 79 51 94 60...

Page 8: ...lace it on an out side wall or where it is exposed to the radiant effect from exposed glass or appliances drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2...

Page 9: ...WER WIRING CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROO...

Page 10: ...actor R 24 Volt Hot Heat XFMR R 24 Volt Hot Heat XFMR E W1 Emergency Heat E W1 Emergency Heat AUX Auxiliary Heat R 24 Volt Hot Cool XFMR Y2 Second Stage Compressor Connection of the C terminal 24 Volt...

Page 11: ...terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 1 1 Heat 1 Cool Conventional Refer to AH documentation for W1 and W2 electric he...

Page 12: ...ct the owner on proper operation and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as o...

Page 13: ...TORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C THERMOPLASTIC O...

Page 14: ...2 T1 24 VAC CTRL CIRCUIT 20VA MIN BLU BLU RED BLK BRN RED BLK GND LUG GND CONTACTOR OPTIONAL LOW VOLTAGE WIRING 2 3 FIELD WIRING CTRL CIRCUIT BLK YEL PNK YEL PNK HPS COLOR CODE BLK BLACK BLU BLUE BRN...

Page 15: ...LL BE REMOVED IF LOW AMBIENT KIT IS INSTALLED YELLOW WIRE WILL BE REMOVED IF PRESSURE SWITCH KIT IS INSTALLED IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED W...

Page 16: ...548086 XIM C 0814 16 Johnson Controls Unitary Products NOTES...

Page 17: ...f applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is conn...

Page 18: ...th the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting a...

Reviews: