813517-YTG-E-0114
Johnson Controls Unitary Products
3
COOLING CAPACITY - COIL ONLY
1
Model Coil
Rated CFM
Entering Air °F
(Dry/Wet Bulb)
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5
40 / 68.5
45 / 76.0
50 / 84.0
FULL-CASED “A” TYPE MULTI-POSITION
MC18A
550
85/72 25.8 23.5 21.0 18.2
80/67 23.7 21.5 19.0 16.4
75/62 19.5 17.3 14.9 12.6
70/57 15.8 13.5 11.5 9.0
MC18B
650
85/72 28.7 26.1 23.3 20.2
80/67 26.4 23.9 21.1 18.2
75/62 21.6 19.2 16.6 14.0
70/57 17.5 15.2 12.8 10.0
MC24(A,B)
850
85/72 36.3 33.0 29.5 25.6
80/67 33.4 30.2 26.7 23.1
75/62 27.4 24.3 21.0 17.7
70/57 22.2 19.3 16.2 12.6
MC30(A,B)
MC32A
1025
85/72 41.5 37.8 33.7 29.5
80/67 36.2 32.4 28.6 24.5
75/62 29.1 25.3 24.0 19.2
70/57 24.1 21.5 18.7 15.8
MC35(B,C)
MC37A
1200
85/72 59.9 51.5 42.9 33.9
80/67 48.0 40.3 32.8 25.1
75/62 37.4 29.8 24.3 20.3
70/57 32.1 28.1 22.9 19.2
MC36A
1150
85/72 46.8 42.6 38.1 33.6
80/67 37.5 33.1 29.1 24.7
75/62 29.3 24.6 26.8 20.0
70/57 25.1 23.2 21.4 20.0
MC36B
1250
85/72 52.0 47.3 42.3 37.3
80/67 41.7 36.8 32.3 27.4
75/62 32.5 27.3 29.8 22.2
70/57 27.9 25.8 23.8 22.2
MC36C
1250
85/72 53.4 48.6 43.4 38.3
80/67 42.8 37.8 33.1 28.2
75/62 33.4 28.1 30.6 22.8
70/57 28.7 26.5 24.5 22.8
MC42(B,C)
1400
85/72 74.6 64.1 53.4 42.2
80/67 59.8 50.1 40.8 31.2
75/62 46.6 37.1 30.2 25.2
70/57 40.0 35.0 28.5 23.9
MC43(B,C)
1400
85/72 78.3 67.4 56.1 44.3
80/67 62.7 52.6 42.9 32.8
75/62 48.9 38.9 31.7 26.5
70/57 42.0 36.8 29.9 25.1
MC48(C,D)
1650
85/72 83.9 72.1 60.1 47.4
80/67 67.2 56.4 45.9 35.1
75/62 52.4 41.7 33.9 28.4
70/57 45.0 39.4 33.0 27.0
MC60D
1825
85/72
102.9 86.7 70.3 53.3
80/67 82.4 68.0 53.7 39.4
75/62 64.2 50.3 39.6 31.8
70/57 55.1 47.5 38.1 30.3
MC62D
2000
85/72
107.0 90.2 73.1 55.5
80/67 85.7 70.7 55.8 40.9
75/62 66.7 52.3 41.2 33.1
70/57 57.4 49.4 39.7 31.6
1 See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.