295421-YTG-B-0707
Unitary Products Group
7
Physical and Electrical Data
MODEL
F4FP024H06T2* F4FP030H06T2* F4FP036H06T2* F4FP040H06T2*
–
Blower - Diameter Width
10x6
10x8
10x8
10x8
–
Motor
HP
1/4
1/3
1/2
1/3
–
Nominal RPM
1075
1075
1075
1075
–
Voltage
208/230
AMPS
Full Load
1.6/1.4
2.5/2.2
3.3/2.9
2.5/2.2
–
Locked Rotor
3.3/2.9
6.2/5.5
7.4/6.5
6.2/5.5
–
Filter
1
1. Field Supplied.
Type
Disposable/Permanent
Size
16x20x1
16x20x1
20x20x1
20x20x1
–
Permanent Type Kit
1PF0601BK
1PF0601BK
1PF0602BK
1PF0601BK
–
Shipping/Operating Weight (lbs.)
98/93
105/100
115/109
121/115
–
MODEL
F4FP042H06T2* F4FP045H06T2* F5FP048H06T2* F5FP060H06T2* F4FV060H06T2*
Blower - Diameter x Width
10x8
10x10
11x10
11x10
11x10
Motor
HP
3/4
1/3
1.0
1.0
1.0
Nominal RPM
1130
925
1050
1050
1200
Voltage
208/230
230
Amps
Full Load
4.4/3.8
3.0/2.7
7.6
7.6
7.8/7.0
Locked Rotor
11.9/10.3
4.8/4.1
–
–
–
Filter
1
Type
Disposable/Permanent
Size
20x20x1
22x20x1
22x20x1
22x20x1
22x20x1
Permanent Type Kit
1PF0602BK
1PF0603BK
1PF0603BK
1PF0603BK
1PF0603BK
Shipping/Operating Weight (lbs.)
121/115
150/144
153/147
160/154
160/154
ELECTRICAL DATA - Cooling Only
Models
Total Motor Amps
Minimum Circuit
ampacity
Max. O.C.P.
1
Amps/
Type
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay Fuse.
Minimum Wire
Size A.W.G.
208V
240V
208V
240V
F4FP024H06T2*
1.6
1.5
2.0
1.8
15
14
F4FP030H06T2*
2.5
2.3
3.2
2.8
15
14
F4FP036H06T2*
3.3
3.0
4.2
3.7
15
14
F4FP040H06T2*
2.5
2.3
3.2
2.8
15
14
F4FP042H06T2*
4.4
4.0
5.5
4.8
15
14
F4FP045H06T2*
3.1
2.6
3.9
3.4
15
14
F5FP048H06T2*
7.6
7.6
9.5
9.5
15
14
F5FP060H06T2*
7.6
7.6
9.5
9.5
15
14
VARIABLE SPEED MODEL
F4FV060H06T2*
–
–
–
–
15
14