295421-YTG-B-0707

4

Unitary Products Group

ACCESSORIES

Refer to Price Manual for specific model numbers.

VERTICAL SUSPENSION KIT

 - The suspension kit is

designed to be used with all sizes of fan coil units whenever
the application requires vertical suspension of the unit.

ELECTRIC HEATERS -

 Models shown under Electrical Data

include sequencers and temperature dual limit switches for
safe, efficient operation. Circuit breakers are provided where
shown.

BOLT-ON THERMAL EXPANSION VALVE

 - TXV kits are

available for enhanced efficiency. These fan coil units have
factory installed TXV’s.

LIMITATIONS

These units must be wired and installed in accordance with
all national and local safety codes. Voltage limits are as fol-
lows:

Air flow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units:

Normal Operating voltage Range

1

1. Utilization range “A” in accordance with ARI Std. 110.

187-253

Entering Air Temperature Limits

Wet Bulb Temp. ºF

Dry Bulb Temp. ºF

Min.

Max.

Min.

Max.

57

72

65

95

EXTENDED AIRFLOW DATA

1

 FOR 230 VOLT - HEAT PUMP MODELS

1. Includes Return Air Filter and Largest Electric Heater.

All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

Models

Blower Motor 

Speed

230 Volt

CFM @ External Static Pressure  -  IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

F4FP024H06T2*

High

950

910

865

835

775

730

662

590

502

400

Med

845

815

785

745

705

654

594

524

439

344

Low

650

630

605

575

540

508

450

383

285

158

F4FP030H06T2*

High

1,270

1,210

1,150

1,085

1,015

946

862

769

645

502

Med

1,050

1,040

995

930

855

804

714

624

494

364

Low

855

820

780

735

680

624

550

447

333

190

F4FP036H06T2*

High

-

1,310

1,250

1,175

1,120

1,053

983

894

779

645

Med

1,200

1,150

1,100

1,040

985

933

879

795

711

587

Low

1,060

1,015

970

925

860

809

740

661

572

453

F4FP040H06T2*

High

1,270

1,210

1,150

1,085

1,015

946

802

769

645

502

Med

1,050

1,040

995

930

855

804

714

624

494

364

Low

855

820

780

735

680

624

550

447

333

190

F4FP042H06T2*

High

-

1,575

1,500

1,420

1,350

1,273

1,192

1,102

996

871

Med

1,460

1,395

1,330

1,260

1,190

1,125

1,052

960

842

695

Low

1,250

1,200

1,155

1,100

1,050

1,001

931

851

751

631

F4FP045H06T2*

High

1,575

1,535

1,475

1,390

1,310

1,245

1,147

1,030

897

735

Med High

1,375

1,315

1,255

1,185

1,110

1,040

944

848

732

606

Med Low

1,210

1,160

1,110

1,050

980

921

844

737

640

533

Low

1,035

990

940

890

825

770

698

616

524

432

F5FP048H06T2*

High

2223

2158

2090

2029

1929

1861

1788

1679

1594

1501

Med High

1948

1904

1801

1815

1777

1741

1681

1618

1539

1453

Med

1741

1690

1649

1606

1564

1516

1476

1436

1387

1353

Med Low

1499

1454

1415

1370

1328

1269

1228

1191

1132

1093

Low

1286

1233

1177

1142

1092

1039

987

960

888

842

F5FP060H06T2*

High

2195

2145

2070

2008

1920

1852

1754

1663

1570

1462

Med High

1938

1899

1873

1824

1791

1724

1679

1603

1521

1420

Med

1726

1681

1641

1607

1560

1517

1485

1433

1402

1349

Med Low

1525

1483

1441

1383

1356

1291

1253

1208

1169

1123

Low

1306

1254

1204

1160

1114

1061

1008

980

914

876

F4FV060H06T2*

High

2,285

2,195

2,105

2,015

1,950

1,845

1,770

1,685

1,590

1,485

Med.

2,125

2,020

1,910

1,805

1,705

1,597

1,491

1,386

1,280

1,175

Low

1,655

1,605

1,550

1,500

1,450

1,398

1,326

1,245

1,153

1,052

NOTE: 

Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is 

limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.

Summary of Contents for F*FP

Page 1: ...inch insulation BLOWERS Blowers are sized to circulate air both quietly and efficiently The direct drive multi speed motors provide a selection of air volume to match any application Motor speeds may...

Page 2: ...21 1 2 18 3 8 20 7 8 F4FP045H06T2 50 3 4 24 17 3 8 20 7 8 22 1 2 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 F5FP048H06T2 50 3 4 24 20 7 8 22 1 2 7 8 F5FP060H06T2 50 3 4 24 20 7 8 22 1 2 7 8 F4FV060H06T2 50 3...

Page 3: ...0 50 84 0 Upflow Horizontal Positions Only F4FP024H06T2 830 85 72 80 67 75 62 70 57 36 3 33 4 27 4 22 2 33 0 30 2 24 3 19 3 29 5 26 7 21 0 16 2 25 6 23 1 17 7 12 6 F4FP030H06T2 1050 85 72 80 67 75 62...

Page 4: ...820 780 735 680 624 550 447 333 190 F4FP036H06T2 High 1 310 1 250 1 175 1 120 1 053 983 894 779 645 Med 1 200 1 150 1 100 1 040 985 933 879 795 711 587 Low 1 060 1 015 970 925 860 809 740 661 572 453...

Page 5: ...45H06T2 High 1418 1382 1328 1251 1179 1120 1032 927 807 661 Med high 1238 1184 1130 1067 999 936 850 763 659 545 Med low 1089 1044 999 945 882 829 760 663 576 480 Low 932 891 846 801 743 693 628 554 4...

Page 6: ...of full capacity where it will stay for 60 seconds Then it will ramp down to zero In every case it will take the motor 30 seconds to ramp from one speed to another Temperate The temperate setting is b...

Page 7: ...al RPM 1130 925 1050 1050 1200 Voltage 208 230 230 Amps Full Load 4 4 3 8 3 0 2 7 7 6 7 6 7 8 7 0 Locked Rotor 11 9 10 3 4 8 4 1 Filter1 Type Disposable Permanent Size 20x20x1 22x20x1 22x20x1 22x20x1...

Page 8: ...B Low 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B Low 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B Low 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 F4FP045H06T2 2HK 6500506B...

Page 9: ...10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 F4FP042H06T2 2HK 6500506B 20 8 28 1 30 5 30 35 10 8 2HK 6500806B 31 3 38 9 43 6...

Page 10: ...3 208 230 3 60 Models Heater Model MAX STATIC MIN CFM Total Heat1 1 See Conversion Table below KW Staging2 2 If first stage heat is connected to W1 66 otherwise refer to Table below KW MBH W1 Only W2...

Page 11: ...50 8 8 F4FP036H06T2 2HK06501025B 43 1 48 2 45 50 8 8 2HK06501525B 43 1 48 2 45 50 8 8 F4FP040H06T2 2HK06501025B 42 2 47 4 45 50 8 8 2HK06501525B 42 2 47 4 45 50 8 8 F4FP042H06T2 2HK06501025B 44 2 49 1...

Page 12: ...R CONDITIONING R R W1 W2 C W2 Y C HUMIDISTAT Air Handler Control Wiring Typical A C Cooling only Applications Y Y G G W1 O C HUM X Y1 Y2 CFM selection board only on F4FV model 1 Air Handler Control Wi...

Page 13: ...WER WIRING TO MAIN POWER SOURCE SUPPLY AIR POWER WIRING CONTROL WIRING THERMOSTAT FILTER ACCESS LOUVERED ELECTRIC HOT WATER HEATER Must comply with water heater installation instructions REFRIGERANT L...

Page 14: ...295421 YTG B 0707 14 Unitary Products Group NOTES...

Page 15: ...295421 YTG B 0707 Unitary Products Group 15 NOTES...

Page 16: ...change without notice Printed in U S A 295421 YTG B 0707 Copyright by York International Corp 2007 All rights reserved Supersedes 295421 YTG A 0507 Unitary 5005 Norman Products York OK Group Drive 73...

Reviews: