EXTENDED AIR FLOW DATA - F4FV VARIABLE SPEED MODELS

Normal

The normal setting provides a 30-second ramp-up from zero
airflow to full capacity and a 30-second ramp-down from full
capacity back to zero airflow. Whenever there is a change in
airflow mode, such as a call for cooling or a change from low
heat to high heat, the motor will take 30 seconds to ramp
from one speed to the other.

Humid

The humid setting is best-suited for installations where the
humidity is frequently very high during cooling season, such
as in the southern part of the country. On a call for cooling,
the blower will ramp up to 50% of full capacity and will stay
there for two minutes, then will ramp up to 82% of full capac-
ity and will stay there for five minutes, and then will ramp up
to full capacity, where it will stay until the wall thermostat is
satisfied. In every case, it will take the motor 30 seconds to
ramp from one speed to another. 

Dry

The dry setting is best suited to parts of the country where
excessive humidity is not generally a problem, where the
summer months are usually dry. On a call for cooling the
motor will ramp up to full capacity and will stay there until the
thermostat is satisfied. At the end of the cooling cycle, the
blower will ramp down to 50% of full capacity where it will stay
for 60 seconds. Then it will ramp down to zero. In every case,
it will take the motor 30 seconds to ramp from one speed to
another.

Temperate

The temperate setting is best suited for most of the country,
where neither excessive humidity nor extremely dry condi-
tions are the norm. On a call for cooling, the motor will ramp
up to 63% of full capacity and will stay there for 90 seconds,
then will ramp up to full capacity. At the end of the cooling
cycle, the motor will ramp down to 63% of full capacity and
will stay there for 30 seconds, then will ramp down to zero. In
every case, it will take the motor 30 seconds to ramp from
one speed to another.

CFM/TAP SELECTION - F4FV

1

1. Both the “COOL” and the “ADJ” tap must be set for the cooling CFM.

2. Fan only CFM = 63% of high speed cooling.

3. Low speed cooling used only with two stage outdoor units. 

(Speed is preset to 65% of high speed).

4. Dehumidification speed is 85% of cooling speed.

5. When operating in both heat pump and electric heat modes, the CFM will 

be whichever is greater.

6. CFM indicator light flashes once for every 100 CFM (i.e., 12 Flashes is 

1200 CFM). 

High Speed

Cooling and

Heat Pump CFM

Model

Jumper

Setting

F

4

FV060H06T2*

"COOL” TAP

“ADJ TAP“

2100

“A”

“B"

1980

"B”

"B"

1860

"A”

"A"

1750

"B”

"A"

1675

"A”

"C"

1605

"C”

"B"

1575

"B”

"C"

1510

"D”

"B"

1420

"C”

"A"

1335

"D”

"A"

1280

"C”

"C"

1200

"D”

“C”

NOTE: 

ELECTRIC HEAT CFM

Model

CFM

Tap Selections

F4FV060H06T2*

"HEAT"

1860

"A"

1750

"B"

1420

"C"

1335

"D"

DELAY PROFILE

"DELAY" Tap

Comfort Setting

A

Normal

B

Humid

C

Dry

D

Temperate

Summary of Contents for F*FP

Page 1: ...inch insulation BLOWERS Blowers are sized to circulate air both quietly and efficiently The direct drive multi speed motors provide a selection of air volume to match any application Motor speeds may...

Page 2: ...21 1 2 18 3 8 20 7 8 F4FP045H06T2 50 3 4 24 17 3 8 20 7 8 22 1 2 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 F5FP048H06T2 50 3 4 24 20 7 8 22 1 2 7 8 F5FP060H06T2 50 3 4 24 20 7 8 22 1 2 7 8 F4FV060H06T2 50 3...

Page 3: ...0 50 84 0 Upflow Horizontal Positions Only F4FP024H06T2 830 85 72 80 67 75 62 70 57 36 3 33 4 27 4 22 2 33 0 30 2 24 3 19 3 29 5 26 7 21 0 16 2 25 6 23 1 17 7 12 6 F4FP030H06T2 1050 85 72 80 67 75 62...

Page 4: ...820 780 735 680 624 550 447 333 190 F4FP036H06T2 High 1 310 1 250 1 175 1 120 1 053 983 894 779 645 Med 1 200 1 150 1 100 1 040 985 933 879 795 711 587 Low 1 060 1 015 970 925 860 809 740 661 572 453...

Page 5: ...45H06T2 High 1418 1382 1328 1251 1179 1120 1032 927 807 661 Med high 1238 1184 1130 1067 999 936 850 763 659 545 Med low 1089 1044 999 945 882 829 760 663 576 480 Low 932 891 846 801 743 693 628 554 4...

Page 6: ...of full capacity where it will stay for 60 seconds Then it will ramp down to zero In every case it will take the motor 30 seconds to ramp from one speed to another Temperate The temperate setting is b...

Page 7: ...al RPM 1130 925 1050 1050 1200 Voltage 208 230 230 Amps Full Load 4 4 3 8 3 0 2 7 7 6 7 6 7 8 7 0 Locked Rotor 11 9 10 3 4 8 4 1 Filter1 Type Disposable Permanent Size 20x20x1 22x20x1 22x20x1 22x20x1...

Page 8: ...B Low 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B Low 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B Low 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 F4FP045H06T2 2HK 6500506B...

Page 9: ...10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 F4FP042H06T2 2HK 6500506B 20 8 28 1 30 5 30 35 10 8 2HK 6500806B 31 3 38 9 43 6...

Page 10: ...3 208 230 3 60 Models Heater Model MAX STATIC MIN CFM Total Heat1 1 See Conversion Table below KW Staging2 2 If first stage heat is connected to W1 66 otherwise refer to Table below KW MBH W1 Only W2...

Page 11: ...50 8 8 F4FP036H06T2 2HK06501025B 43 1 48 2 45 50 8 8 2HK06501525B 43 1 48 2 45 50 8 8 F4FP040H06T2 2HK06501025B 42 2 47 4 45 50 8 8 2HK06501525B 42 2 47 4 45 50 8 8 F4FP042H06T2 2HK06501025B 44 2 49 1...

Page 12: ...R CONDITIONING R R W1 W2 C W2 Y C HUMIDISTAT Air Handler Control Wiring Typical A C Cooling only Applications Y Y G G W1 O C HUM X Y1 Y2 CFM selection board only on F4FV model 1 Air Handler Control Wi...

Page 13: ...WER WIRING TO MAIN POWER SOURCE SUPPLY AIR POWER WIRING CONTROL WIRING THERMOSTAT FILTER ACCESS LOUVERED ELECTRIC HOT WATER HEATER Must comply with water heater installation instructions REFRIGERANT L...

Page 14: ...295421 YTG B 0707 14 Unitary Products Group NOTES...

Page 15: ...295421 YTG B 0707 Unitary Products Group 15 NOTES...

Page 16: ...change without notice Printed in U S A 295421 YTG B 0707 Copyright by York International Corp 2007 All rights reserved Supersedes 295421 YTG A 0507 Unitary 5005 Norman Products York OK Group Drive 73...

Reviews: