background image

CHECK ELECTRICAL POWER SUPPLY

The electrical power should be checked to determine if ade-
quate power is available, and near constant voltage can be
maintained. If there is any question concerning the power
supply, contact the local power company for corrections; other-
wise, unsatisfactory performance may result.

SELECTING THE BEST  LOCATION

Several important factors must be considered before selecting
the site for the outdoor unit:

Distance to indoor coil

Proximity to the structure

Proximity to vents and exhaust systems

Ability to service

Sound transmission

Air circulation

Wind direction

Relationship between structure, sun, and unit

Distance from power source

Defrost drainage

Water drainage

Average winter snow depth

Local codes

Locate the outdoor unit near enough to the indoor coil vicinity
to eliminate lengthy refrigerant line runs. Do not locate the
outdoor unit so it discharges air under eaves or gutters. Rain
or snow melt-off should not be able to run off a roof and down
upon the unit. Be sure vents are not located upwind from the
outdoor unit.

A minimum clearance of 18 inches is required for service at the
control panel and compressor compartment access. A 10 inch
clearance is required for the air inlet to the outdoor coil around
the perimeter of the unit. The air discharge of the unit requires
a 60 inch clearance between the top of the unit and any
obstruction. See Figure 1.

The length of the refrigerant tubing, between the outdoor unit
and indoor coil, should be as short as possible to avoid capacity
and efficiency loss. Excessive spacing of the outdoor unit from
the home can lead to the refrigerant lines being restricted by
trampling or by being punctured by lawn mowers. Locate the
outdoor unit away from bedroom windows or other rooms
where sound might be objectionable.

Adverse effects of prevailing winds, blowing snow or sleet onto
the outdoor coil can be eliminated by placing the outdoor unit
where the wind does not blow across the unit. Trees, shrubs,
corners of buildings and fences standing off from the coil can
reduce capacity loss due to wind chill effect.

Provide ample clearance from shrubs to allow adequate air to
pass across the outdoor coil without leaves or branches being
pulled into the coil. The outdoor unit may never go into the
defrost cycle, even with minor frost build up, during the daytime
in some areas of the United States if it is placed on the south
side of the residence with no shade. However, the heat pump
may lose some efficiency at a south side location with no shade
during the summer while trying to cool the residence.

Consideration should be given to the distance and routing of
electrical service that would have to be run to connect the
outdoor unit.

It is recommended the outdoor unit be mounted upon a solid
base that will not shift or settle. Top of  base should be two
inches above grade. This allows enough height for normal
defrost ice build up below the unit in freezing weather. Thought
should be given to water drainage away from the outdoor unit
in summer and when the defrost ice melts on warmer winter
days. Drain holes in the base pan must be kept clear.

In areas where snowfall is significant, the height of the unit base
above grade should be two to three inches higher than the
anticipated snowfall. This clearance is required to provide am-
ple drainage during the defrosting of the outdoor coil. Soil
grading around the heat pump should provide drainage away
from the unit to prevent slippery conditions that may cause
personal injury. See Figure 2.

AMBIENT AIR TEMPERATURE

ON OUTDOOR COIL

AIR TEMPERATURE

 ON INDOOR COIL

Min. °DB

Max. °DB

Min.

Max.

Cool

Heat

Cool

Heat

°WB
Cool

°DB

Heat

°WB
Cool

°DB

Heat

50

10*

120

70

57

50**

72

80

* If ambient will be below this, Accessory Kit 2LT06700224 must be installed to cutoff

 heat pump.

** Operation below this temperature is permissible for a short period of time when required to

  bring the heating area up to 50°F.

TABLE 1 - APPLICATION LIMITATIONS

CONTROL ACCESS PANEL

10" CLEARANCE 
COIL AREA

60" OVERHEAD
CLEARANCE

18" SERVICE 
ACCESS CLEARANCE

WEATHERPROOF
DISCONNECT
SWITCH

NEC CLASS 1 WIRING

THERMOSTAT

TO FURNACE OR AIR HANDLER
TERMINAL BLOCK

NEC CLASS 2 WIRING

TO INDOOR COIL

NOTE: ALL OUTDOOR WIRING MUST
BE WEATHERPROOF

SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT

FIGURE 1 - OUTDOOR  UNIT LOCATION

515.16-N3Y

2

Unitary Products Group

Summary of Contents for E*RC Series

Page 1: ...or in the Directory of Certified Unitary Heat Pumps published by the Air Conditioning and Refrigeration Institute Using unmatched com ponents may not only affect the performance of the system but may...

Page 2: ...ue to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into the coil The outdoor unit may never go in...

Page 3: ...bing must be done with care to obtain reliable trouble free operation 1 Selection of proper refrigerant tubing grade and size 2 Refrigerant line routing cutting and fitting 3 Insulating the vapor line...

Page 4: ...Recommendations and Refrigerant Line Length for vapor and liquid line sizing cali bration of liquid line pressure loss or gain determination of vapor line velocity elevation limitations orifice connec...

Page 5: ...for volts frequency phase maxi mum fuse size and minimum branch circuit ampacity Refer to the wiring diagram inside the unit control box cover before connecting to power supply 1 The line voltage ser...

Page 6: ...TAGE BOX FAN MOTOR PLUG FIGURE 4 OUTDOOR UNIT CONTROL BOX SINGLE PHASE 10 12 SEER CONTACTOR DUAL RUN FAN CAPACITOR GROUND LUG ADJUSTABLE HIGH VOLTAGE CONDUIT PLATE DEFROST CONTROL BOARD FINGERED BUSHI...

Page 7: ...FIGURE 6 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 036 and 048 Models FIGURE 7 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 060 Model 515 16 N3Y Unitary Products Group 7...

Page 8: ...D O O R U N I T T H E R M O S T A T I N D O O R U N I T P O W E R W I R I N G 2 0 8 2 3 0 3 6 0 4 6 0 3 6 0 P O W E R W I R I N G 2 4 V C O N T R O L W I R I N G N E C C L A S S 2 L O W V O L T A G E...

Page 9: ...FROST SAFETY LOCKOUT MODE The lock out control opens the circuits to the compressor contactor stopping the compressor in response to 400 High Pressure limit switch opening for more than one second The...

Page 10: ...l remain in defrost until the defrost thermostat opens or 10 minutes expires If the thermostat is open when the short is removed the heat pump will exit defrost immediately 14 SEER WITH DEMAND DEFROST...

Page 11: ...DRYER solid core SHOWN IN COOLING POSITION ORIFICE heating FIGURE 13 FLOW DIAGRAM 060 10 12 SEER Single Phase INDOOR COIL COMPRESSOR 4 WAY REVERSING VALVE SUCTION ACCUMULATOR OUTDOOR COIL COOLING CYCL...

Page 12: ...low the unit to go into a defrost cycle if the compressor is operating When the short is removed the heat pump will remain in defrost until the coil temperature reaches 75 F or 14 minutes expires If t...

Reviews: