background image

4.

The liquid temperature measured by the defrost coil sen-
sor must be below the defrost initiation temperature for 4.5
minutes continuously.

The defrost mode is identical to the cooling mode except that
the outdoor fan motor stops and the first stage of heat is turned
on through "66" to continue warming the conditioned space.

The defrost cycle will terminate when the defrost coil sensor
reaches 75 

°

 F or after 14 minutes defrost time.

NOTE: Under certain low ambient conditions normal initiation

of a normal defrost cycle may not occur. Therefore as
a precautionary measure a "Forced Defrost" is initiated
every six hours to ensure compressor longevity by
returning oil back to the sump of the compressor.

TEST PINS ON DEMAND DEFROST:

The test pins labeled "speed-up" and "defrost" are provided to
aid in field servicing of the heat pump. See Figure 11. The pins
are designed to be temporarily shorted together either by a
screwdriver or with a 1/4" female spade connector.

When the "speed-up" pins are shorted together. All timings are
speeded up by a factor of 64. This reduces the anti-recycle
compressor timer from 5 minutes to about 5 seconds and the
defrost terminate time from 14 minutes to 13 seconds: addition-
ally, the 39 minute minimum run time would be shorted to about
40 seconds or less if the system has operated for some period
of time since last defrost.

When the "defrost" pins are shorted together, the control will
allow the unit to go into a defrost cycle if the compressor is

operating. When the short is removed, the heat pump will
remain in defrost until the coil temperature reaches 75 

°

 F or

14 minutes expires.

If the liquid (coil) temperature happens to be above 75 

°

 F, the

short must be maintained to keep the unit in a defrost cycle. It
should be used since the unit WILL REMAIN in defrost until the
short is removed regardless of coil temperature. This could
cause a lockout due to high discharge pressure!

NOTE: Anytime the "defrost" shorting pins are jumpered, it

automatically resets all timing cycles. After a power
failure, all timing cycles would also reset except one
that is the 5 minute delay for compressor restart. It can
be reduced, however by jumpering the "speed-up" pins
on the control board.  

INSTALLER

After installation is complete, place unit data sheet and instal-
lation instructions in customer envelope and give to home
owner.

OPTIONAL OUTDOOR THERMOSTAT KIT

The function of the outdoor thermostat kit is to prevent unnec-
essary use of auxiliary electric heat. At temperatures above the
setting of the outdoor thermostat, the electric heat is locked out
and all of the heat is provided by the heat pump.

The setting or the outdoor thermostat is important and is ideally
selected at the home “balance point”, when the heat pump
capacity is equal to the heat loss of the home. See instructions
packed with these kits.

Unitary Products Group
P.O. Box 1592, York, Pennsylvania USA 17405-1592
Subject to change without notice.   Printed in U.S.A.
Copyright

 

 by York International Corporation 1998.  All Rights Reserved.

Code: SBY

                           515.16-N3Y (298)

Summary of Contents for E*RC Series

Page 1: ...or in the Directory of Certified Unitary Heat Pumps published by the Air Conditioning and Refrigeration Institute Using unmatched com ponents may not only affect the performance of the system but may...

Page 2: ...ue to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into the coil The outdoor unit may never go in...

Page 3: ...bing must be done with care to obtain reliable trouble free operation 1 Selection of proper refrigerant tubing grade and size 2 Refrigerant line routing cutting and fitting 3 Insulating the vapor line...

Page 4: ...Recommendations and Refrigerant Line Length for vapor and liquid line sizing cali bration of liquid line pressure loss or gain determination of vapor line velocity elevation limitations orifice connec...

Page 5: ...for volts frequency phase maxi mum fuse size and minimum branch circuit ampacity Refer to the wiring diagram inside the unit control box cover before connecting to power supply 1 The line voltage ser...

Page 6: ...TAGE BOX FAN MOTOR PLUG FIGURE 4 OUTDOOR UNIT CONTROL BOX SINGLE PHASE 10 12 SEER CONTACTOR DUAL RUN FAN CAPACITOR GROUND LUG ADJUSTABLE HIGH VOLTAGE CONDUIT PLATE DEFROST CONTROL BOARD FINGERED BUSHI...

Page 7: ...FIGURE 6 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 036 and 048 Models FIGURE 7 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 060 Model 515 16 N3Y Unitary Products Group 7...

Page 8: ...D O O R U N I T T H E R M O S T A T I N D O O R U N I T P O W E R W I R I N G 2 0 8 2 3 0 3 6 0 4 6 0 3 6 0 P O W E R W I R I N G 2 4 V C O N T R O L W I R I N G N E C C L A S S 2 L O W V O L T A G E...

Page 9: ...FROST SAFETY LOCKOUT MODE The lock out control opens the circuits to the compressor contactor stopping the compressor in response to 400 High Pressure limit switch opening for more than one second The...

Page 10: ...l remain in defrost until the defrost thermostat opens or 10 minutes expires If the thermostat is open when the short is removed the heat pump will exit defrost immediately 14 SEER WITH DEMAND DEFROST...

Page 11: ...DRYER solid core SHOWN IN COOLING POSITION ORIFICE heating FIGURE 13 FLOW DIAGRAM 060 10 12 SEER Single Phase INDOOR COIL COMPRESSOR 4 WAY REVERSING VALVE SUCTION ACCUMULATOR OUTDOOR COIL COOLING CYCL...

Page 12: ...low the unit to go into a defrost cycle if the compressor is operating When the short is removed the heat pump will remain in defrost until the coil temperature reaches 75 F or 14 minutes expires If t...