COOLING

On call for cooling, the thermostat makes 24V circuits: R to O,
R to Y, and R to G. Circuit R to O energizes the reversing valve,
switching it to cooling position. Circuit R to Y energizes the
contactor, starting outdoor fan motor and compressor (after the
anti-short cycle period). Circuit  R to G energizes the indoor
unit blower relay, starting the indoor blower motor.

HEATING

On call for heating, thermostat makes circuits R to Y and R to
G. Circuit R to Y energizes contactor, starting outdoor fan motor
and compressor (after the anti-short cycle period).  Circuit R to
G energizes the indoor blower relay, starting the blower motor.

Should the temperature continue to fall, R to W is made through
the second stage of the thermostat. Circuit R to W energizes
the supplemental electric heat. The field-installed outdoor
thermostat option can be used to turn on only the first stage of
electric heat if the temperature is above the setting tempera-
ture.  If gas/propane furnace is used as the supplemental heat,
add-on control kit (2AC02700701) must be used.  See the
add-on control installation instruction for the system operation.

EMERGENCY HEAT

When switch on thermostat is placed in emergency heat posi-
tion:

1. Emergency light is energized.

2. Compressor circuit is locked out. (No "R" to "Y")

3. Supplemental and standby heaters (if installed) will be

controlled by first stage of heating thermostat.

4. Indoor blower will operate on demand for heat and cycle off

with the last heater element when in “AUTO” position.

10 & 12 SEER  WITH TIME / TEMP. DEFROST

SAFETY LOCKOUT MODE:

The lock out control opens the circuits to the compressor
contactor, stopping the compressor in response to (400 #) High
Pressure limit switch opening for more than one second. The
compressor will remain off until the high pressure switch re-
closes. During the period the switch is open, the control will
provide a pulsed output at the "X" terminal to indicate the
lock-out condition. After  the high pressure switch recloses, the
compressor can restart after a 5 minute anti-short cycle period.
If the unit experiences a second high pressure switch opening
within a six hour period, the control will go into a lockout
condition and will not allow the compressor to restart unless
reset. To reset the lockout, turn the indoor thermostat’s system
switch to “OFF” then, back to the selected mode within 5 second
OR disconnect the power to the transformer for at least two
seconds. Please note that thermostats with anti-short cycle
timers will only be able to reset by disconnecting the power to
the transformer for at least two seconds.

TIME / TEMPERATURE DEFROST:

The defrost control is a time/temp control which includes a
field-selectable (white tap located at board edge) time period
between defrost cycle (30, 60, and 90 minutes). Factory set at
60 minutes. See Figure 10.

Pressure 

Switch

Reversing 

Valve

Defrost 

Thermostat

Compressor 

Relay

Time Selection Tap

Test Pin

FIGURE 10 - TIME/TEMPERATURE DEFROST (10 &
12 SEER Single Phase) and (10 SEER, Three Phase)

Ambient 

Sensor

Reversing 

Valve

Defrost Coil 

Sensor

Compressor 

Relay

High Pressure &

High Temp. Switch

Test 

Pin

B

Y

O

66

R

W

X

BLK

BLK BLU BLU YEL YEL

B

B

M

P

Y

O

Defrost

Speedup

FIGURE 11 - DEMAND DEFROST (14 SEER)

SEQUENCE OF OPERATION

515.16-N3Y

Unitary Products Group

9

Summary of Contents for E*RC Series

Page 1: ...or in the Directory of Certified Unitary Heat Pumps published by the Air Conditioning and Refrigeration Institute Using unmatched com ponents may not only affect the performance of the system but may...

Page 2: ...ue to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into the coil The outdoor unit may never go in...

Page 3: ...bing must be done with care to obtain reliable trouble free operation 1 Selection of proper refrigerant tubing grade and size 2 Refrigerant line routing cutting and fitting 3 Insulating the vapor line...

Page 4: ...Recommendations and Refrigerant Line Length for vapor and liquid line sizing cali bration of liquid line pressure loss or gain determination of vapor line velocity elevation limitations orifice connec...

Page 5: ...for volts frequency phase maxi mum fuse size and minimum branch circuit ampacity Refer to the wiring diagram inside the unit control box cover before connecting to power supply 1 The line voltage ser...

Page 6: ...TAGE BOX FAN MOTOR PLUG FIGURE 4 OUTDOOR UNIT CONTROL BOX SINGLE PHASE 10 12 SEER CONTACTOR DUAL RUN FAN CAPACITOR GROUND LUG ADJUSTABLE HIGH VOLTAGE CONDUIT PLATE DEFROST CONTROL BOARD FINGERED BUSHI...

Page 7: ...FIGURE 6 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 036 and 048 Models FIGURE 7 OUTDOOR UNIT CONTROL BOX THREE PHASE 10 SEER 060 Model 515 16 N3Y Unitary Products Group 7...

Page 8: ...D O O R U N I T T H E R M O S T A T I N D O O R U N I T P O W E R W I R I N G 2 0 8 2 3 0 3 6 0 4 6 0 3 6 0 P O W E R W I R I N G 2 4 V C O N T R O L W I R I N G N E C C L A S S 2 L O W V O L T A G E...

Page 9: ...FROST SAFETY LOCKOUT MODE The lock out control opens the circuits to the compressor contactor stopping the compressor in response to 400 High Pressure limit switch opening for more than one second The...

Page 10: ...l remain in defrost until the defrost thermostat opens or 10 minutes expires If the thermostat is open when the short is removed the heat pump will exit defrost immediately 14 SEER WITH DEMAND DEFROST...

Page 11: ...DRYER solid core SHOWN IN COOLING POSITION ORIFICE heating FIGURE 13 FLOW DIAGRAM 060 10 12 SEER Single Phase INDOOR COIL COMPRESSOR 4 WAY REVERSING VALVE SUCTION ACCUMULATOR OUTDOOR COIL COOLING CYCL...

Page 12: ...low the unit to go into a defrost cycle if the compressor is operating When the short is removed the heat pump will remain in defrost until the coil temperature reaches 75 F or 14 minutes expires If t...