FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS
- Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER
-
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS
- Special coating process that utilizes
Technicoat 10-1
TM
processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•
ELECTRIC HEATERS
- Wired for single point power
supply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
FILTER OPTIONS
- Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
CONVENIENCE OUTLET -
This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH
- For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
BAS - Building Automation System Controls
Simplicity
®
INTELLI-Comfort™ CONTROL -
The York®
Simplicity
®
INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to per-
form Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to pro-
vide comfortable ventilation air temperature. The pat-
ented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy sav-
ings by recovering the building from the Unoccupied Set-
points to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The
Simplicity
®
INTELLI-Comfort™ balances space temperature, venti-
lation air temperature, CO2 and humidity for ultimate
comfort.
•
Simplicity
®
INTELLI-Comfort™ with MOD LINK CON-
TROL -
The York®
Simplicity
®
INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
•
Novar® BAS CONTROL -
The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
JOHNSON CONTROLS BAS CONTROL -
The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
•
CPC BAS CONTROL -
The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
HONEYWELL BAS CONTROL -
The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
•
SMOKE DETECTORS
- (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
COIL GUARD
- Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a