343615-YTG-B-0308
Johnson Controls Unitary Products
15
TABLE 16: DY036 COOLING CAPACITIES (3 TON)
Air on Evap-
orator Coil
Temperature of Air on Condenser Coil
75°F
85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
900
72 44
2.3
24
21
19
16
14
-
-
41
2.5
23
20
18
15
12
-
-
67 42
2.3
30
28
25
23
20
18
15
38
2.5
29
26
24
21
18
16
13
62 40
2.3
40
35
33
30
28
25
23
35
2.5
35
32
30
27
25
22
20
57 39
2.3
39
37
35
32
30
27
25
35
2.5
35
34
31
28
26
23
21
1050
72 44
2.2
26
23
20
17
14
-
-
42
2.5
25
22
19
16
13
-
-
67 42
2.3
33
30
27
24
21
18
15
39
2.5
31
28
25
22
19
16
13
62 40
2.3
40
38
35
32
29
26
23
35
2.5
35
34
32
29
26
23
20
57 39
2.3
39
38
37
34
31
28
25
35
2.5
35
35
33
30
27
24
21
1200
72 44
2.2
28
25
21
18
14
-
-
43
2.5
27
24
20
17
13
-
-
67 43
2.3
35
32
28
25
21
18
14
40
2.5
34
31
27
24
20
17
13
62 40
2.3
40
40
37
33
30
26
23
36
2.5
36
36
34
31
27
24
20
57 39
2.3
39
39
39
36
32
29
25
36
2.5
36
36
36
32
29
25
22
1350
72 45
2.2
30
26
22
18
14
-
-
43
2.5
29
25
21
17
13
-
-
67 43
2.3
37
33
29
25
21
18
14
40
2.5
36
32
28
24
20
16
12
62 41
2.3
41
41
39
35
31
27
23
37
2.5
37
37
36
32
28
24
20
57 40
2.3
40
40
40
36
32
28
24
36
2.5
36
36
36
32
28
24
20
1500
72 46
2.3
32
27
23
18
14
-
-
44
2.5
31
27
22
18
13
-
-
67 44
2.3
40
35
31
26
22
17
13
41
2.5
39
34
30
25
21
16
12
62 42
2.3
42
42
42
37
33
28
24
37
2.5
37
37
37
33
28
24
19
57 41
2.3
41
41
41
36
32
27
23
37
2.5
37
37
37
32
28
23
19
95°F
105°F
900
72 38
2.7
21
19
16
14
11
-
-
35
3.0
20
17
15
12
10
-
-
67 35
2.7
27
24
22
19
17
14
12
31
2.9
25
23
20
18
15
12
10
62 30
2.7
30
29
27
24
22
19
17
27
3.0
27
26
24
21
19
16
14
57 30
2.7
30
30
27
25
22
19
17
27
3.0
27
27
25
22
20
17
15
1050
72 39
2.7
24
21
18
15
12
-
-
36
3.0
22
19
16
13
10
-
-
67 36
2.7
30
27
24
21
18
15
12
32
2.9
28
25
22
19
16
13
10
62 31
2.7
31
31
30
26
23
20
17
28
2.9
28
28
26
23
20
17
14
57 31
2.7
31
31
30
27
24
21
18
28
2.9
28
28
27
24
21
18
15
1200
72 41
2.7
26
23
19
16
12
-
-
37
2.9
25
21
18
14
11
-
-
67 37
2.7
33
30
26
23
19
16
12
33
2.8
31
28
24
21
17
14
10
62 32
2.7
32
32
32
29
25
22
18
29
2.9
29
29
29
25
22
18
15
57 32
2.7
32
32
32
29
25
22
18
29
2.9
29
29
30
26
23
19
16
1350
72 41
2.7
28
24
20
16
12
-
-
37
3.0
27
23
19
15
11
-
-
67 37
2.7
35
31
27
23
19
15
11
33
2.9
32
29
25
21
17
13
9
62 32
2.7
32
32
32
28
24
20
16
29
2.9
29
29
29
25
21
17
13
57 33
2.7
33
33
33
29
25
21
17
29
2.9
29
29
30
26
22
18
14
1500
72 42
2.7
30
26
21
17
12
-
-
37
3.1
28
24
20
15
11
-
-
67 38
2.7
38
33
29
24
20
15
11
33
2.9
33
31
27
22
18
13
9
62 33
2.7
33
33
33
28
24
19
15
29
3.0
29
29
29
24
20
15
11
57 33
2.7
33
33
33
29
24
20
15
29
3.0
29
29
29
25
20
16
11
115°F
125°F
900
72 32
3.3
18
16
13
11
8
-
-
28
3.7
17
14
12
9
7
-
-
67
27
3.1
23
21
18
16
13
11
8
24
3.3
22
19
17
14
11
9
6
62 24
3.2
24
23
21
18
16
13
11
21
3.5
21
20
18
15
13
10
8
57 25
3.2
25
25
23
20
17
15
12
22
3.5
22
22
20
18
15
13
10
1050
72 32
3.3
21
18
15
12
9
-
-
29
3.5
19
16
13
10
7
-
-
67
28
3.0
26
23
20
17
14
11
8
24
3.2
24
22
18
15
12
9
6
62 25
3.1
25
24
23
20
17
14
11
21
3.4
21
21
20
17
14
11
8
57 25
3.1
25
25
25
22
19
16
13
22
3.4
22
22
22
19
16
13
10
1200
72 33
3.2
23
20
16
13
9
-
-
29
3.4
21
18
14
11
7
-
-
67
29
3.0
29
26
22
19
15
12
8
25
3.1
25
24
20
17
13
10
6
62 25
3.1
25
25
25
22
18
15
11
22
3.3
22
22
22
18
15
11
8
57 26
3.1
26
26
27
24
20
17
13
22
3.3
22
22
22
21
18
14
11
1350
72 33
3.3
25
21
17
13
9
-
-
29
3.6
23
19
15
11
7
-
-
67
29
3.1
29
27
23
19
15
11
8
24
3.2
24
24
21
17
13
10
6
62
25
3.2
25
25
25
21
17
13
9
21
3.4
21
21
21
17
13
9
5
57 26
3.2
26
26
26
22
18
14
10
22
3.4
22
22
22
19
15
11
7
1500
72 33
3.4
27
22
18
13
9
-
-
28
3.8
25
20
16
11
7
-
-
67
28
3.2
28
28
25
20
16
11
7
24
3.4
24
24
23
18
14
9
5
62
25
3.3
25
25
25
20
16
11
7
21
3.6
21
21
21
16
12
7
3
57
25
3.3
25
25
25
21
16
12
8
22
3.6
22
22
22
17
13
8
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.