343615-YTG-B-0308
Johnson Controls Unitary Products
21
060
(5.0)
208-1-60 28.8 145.0
45.0
2.3
7.6
0.0
None
-
-
-
45.9
50
E05
4.0
1
19.2
45.9
50
E07
5.6
1
26.9
45.9
50
E10
8.0
1
38.5
57.6
60
E15
11.9
2
57.2
81.0
90
E20
15.9
2
76.4
105.1
110
E30
22.2
2
106.7
142.9
150
230-1-60 28.8 145.0
45.0
2.3
7.6
0.0
None
-
-
-
45.9
50
E05
5.3
1
23.0
45.9
50
E07
7.5
1
32.6
48.6
50
E10
10.6
1
46.1
64.7
70
E15
15.9
2
69.1
92.3
100
E20
21.2
2
92.2
119.9
125
E30
29.6
2
128.7
163.7
175
208-3-60 17.3 123.0
27.0
2.3
7.6
0.0
None
-
-
-
31.5
35
E05
4.0
1
11.1
31.5
35
E07
5.6
1
15.5
31.5
35
E10
8.0
1
22.2
37.3
40
E15
11.9
2
33.0
50.8
60
E20
15.9
2
44.1
64.7
70
E30
22.2
2
61.6
86.5
90
230-3-60 17.3 123.0
27.0
2.3
7.6
0.0
None
-
-
-
31.5
35
E05
5.3
1
13.3
31.5
35
E07
7.5
1
18.8
32.1
35
E10
10.6
1
26.6
41.4
45
E15
15.9
2
39.9
57.3
60
E20
21.2
2
53.2
73.2
80
E30
29.6
2
74.3
98.5
100
460-3-60
9.6
70.0
15.0
1.3
7.6
0.0
None
-
-
-
17.1
20
E07
6.8
1
8.5
17.1
20
E10
10.1
1
12.7
19.9
20
E15
13.6
2
17.1
25.2
25
E20
19.5
2
24.5
34.1
35
E30
28.8
2
36.1
48.1
50
575-3-60
7.4
53.0
11.5
1.3
7.6
0.0
None
-
-
-
13.3
15
E10
10.6
1
10.6
16.5
20
E15
15.9
1
16.0
22.9
25
E20
21.2
2
21.3
29.3
30
E30
30.4
2
30.5
40.4
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps