343615-YTG-B-0308
Johnson Controls Unitary Products
23
060
(5.0)
208-1-60 28.8 145.0
45.0
2.3
7.6
10.0
None
-
-
-
55.9
60
E05
4.0
1
19.2
55.9
60
E07
5.6
1
26.9
55.9
60
E10
8.0
1
38.5
70.1
80
E15
11.9
2
57.2
93.5
100
E20
15.9
2
76.4
117.6
125
E30
22.2
2
106.7
155.4
175
230-1-60 28.8 145.0
45.0
2.3
7.6
10.0
None
-
-
-
55.9
60
E05
5.3
1
23.0
55.9
60
E07
7.5
1
32.6
61.1
70
E10
10.6
1
46.1
77.2
80
E15
15.9
2
69.1
104.8
110
E20
21.2
2
92.2
132.4
150
E30
29.6
2
128.7
176.2
200
208-3-60 17.3 123.0
27.0
2.3
7.6
10.0
None
-
-
-
41.5
45
E05
4.0
1
11.1
41.5
45
E07
5.6
1
15.5
41.5
45
E10
8.0
1
22.2
49.8
50
E15
11.9
2
33.0
63.3
70
E20
15.9
2
44.1
77.2
80
E30
22.2
2
61.6
99.0
100
230-3-60 17.3 123.0
27.0
2.3
7.6
10.0
None
-
-
-
41.5
45
E05
5.3
1
13.3
41.5
45
E07
7.5
1
18.8
44.6
45
E10
10.6
1
26.6
53.9
60
E15
15.9
2
39.9
69.8
70
E20
21.2
2
53.2
85.7
90
E30
29.6
2
74.3
111.0
125
460-3-60
9.6
70.0
15.0
1.3
7.6
5.0
None
-
-
-
22.1
25
E07
6.8
1
8.5
22.1
25
E10
10.1
1
12.7
26.2
25
E15
13.6
2
17.1
31.4
30
E20
19.5
2
24.5
40.3
40
E30
28.8
2
36.1
54.3
60
575-3-60
7.4
53.0
11.5
1.3
7.6
4.0
None
-
-
-
17.3
20
E10
10.6
1
10.6
21.5
20
E15
15.9
1
16.0
27.9
30
E20
21.2
2
21.3
34.3
35
E30
30.4
2
30.5
45.4
45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps