PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-
necting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the Physical and Electri-
cal Data Table.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evap adder for line set.
Additional R-410A Charge / TXV Size for Various Matched Systems
Outdoor Unit
CZB01811
CZB02411
CZB03011
CZB03611
CZB04211
CZB04811
CZB06011
Unit Orifice (s)
1TVM901
1TVM903
1TVM903
1TVM903
1TVM904
1TVM4C1
1TVM905
1TVM905
Factory R-410A Charge, lbs-oz
5-13
6-4
7-4
6-4
8-13
8-12
13-9
Indoor Coil
1,2
Additional Charge, Oz
FC/MC/PC/UC18A3X
5
–
–
–
–
–
–
FC/MC/PC/UC18B3X
5
–
–
–
–
–
–
FC/MC/PC/UC24A3X
5
6
–
–
–
–
–
FC/MC/PC/UC24B3X
5
6
–
–
–
–
–
FC/MC/PC/UC30A3X
5
6
3
–
–
–
–
FC/MC/PC/UC30B3X
5
6
3
–
–
–
–
FC/MC/PC/UC36A3X
–
–
3
3
–
–
–
FC/MC/PC/UC36B3X
–
–
3
3
–
–
–
FC/MC/PC/UC36C3X
–
–
3
3
–
–
–
FC/MC/PC35B3X
–
–
–
3
–
–
–
FC/MC/PC35C3X
–
–
–
3
–
–
–
FC/MC/PC/UC42B3X
–
–
–
3
–
–
–
FC/MC/PC/UC42C3X
–
–
–
3
–
–
–
FC/MC/PC/UC48C3X
–
–
–
–
6
–
–
FC/MC/PC/UC48D3X
–
–
–
–
6
–
–
FC/PC/UC60C3X
–
–
–
–
–
12
4
FC/MC/PC/UC60D3X
–
–
–
–
–
12
4
MC61D3X
–
–
–
–
–
–
4
HC18A3X
5
–
–
–
–
–
–
HC30A3X
–
6
–
–
–
–
–
HC36B3X
–
–
3
3
–
–
–
HC60D3X
–
–
–
–
6
12
4
HD24A3X
–
–
–
–
–
–
–
HD36B3X
–
–
3
3
–
–
–
HD48C3X
–
–
–
–
6
–
–
HD60D3X
–
–
–
–
–
12
4
AHP18B3X
5
–
–
–
–
–
–
AHP24B3X
5
6
–
–
–
–
–
AHP30B3X
–
–
3
–
–
–
–
AHP36C3X
–
–
3
3
–
–
–
AHP42C3X
–
–
–
3
–
–
–
AHP/SHP48D3X
–
–
–
–
6
12
–
AHP/SHP60D3X
–
–
–
–
6
12
4
AV24B3X
5
6
–
–
–
–
–
AV36C3X
–
–
3
3
–
–
–
AV/SV48D3X
–
–
–
–
6
12
–
AV/SV60D3X
–
–
–
–
–
12
4
FOOTNOTES:
1
Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2
PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.