246723-YTG-L-0807
Unitary Products Group
13
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
CZB04211
INDOOR COIL MODEL NO.
FC/MC/PC/UC48
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1200
1400
1600
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
36.0
38.4
36.8
40.5
45.9
38.2
39.0
38.3
41.8
46.9
40.3
39.5
39.7
43.2
47.9
S.C.
35.9
34.7
29.1
28.6
22.1
38.1
37.8
31.5
30.8
23.4
40.3
40.9
33.9
33.1
24.8
K.W.
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
75
T.C.
38.9
40.1
40.9
43.9
49.3
40.7
41.2
42.0
45.3
50.7
42.6
42.3
43.1
46.8
52.0
S.C.
38.9
34.9
30.1
29.4
23.4
40.8
37.8
32.5
31.7
24.8
42.6
40.8
34.9
34.1
26.3
K.W.
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
85
T.C.
37.5
39.3
38.9
42.2
47.6
39.5
40.1
40.1
43.6
48.8
41.4
40.9
41.4
45.0
49.9
S.C.
37.4
34.8
29.6
29.0
22.8
39.4
37.8
32.0
31.3
24.1
41.4
40.8
34.4
33.6
25.5
K.W.
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
95
T.C.
35.5
37.0
36.7
39.9
44.8
37.2
37.9
37.7
41.0
45.8
39.0
38.8
38.8
42.1
46.8
S.C.
35.4
33.6
28.6
27.9
21.8
37.2
36.3
30.9
30.2
23.2
38.9
38.9
33.2
32.5
24.5
K.W.
3.6
3.6
3.6
3.6
3.7
3.6
3.6
3.6
3.6
3.7
3.6
3.6
3.6
3.6
3.7
105
T.C.
33.5
34.7
34.5
37.5
42.0
35.0
35.7
35.3
38.4
42.8
36.5
36.7
36.2
39.3
43.6
S.C.
33.4
32.5
27.5
26.9
20.8
34.9
34.8
29.7
29.1
22.2
36.5
37.1
31.9
31.3
23.6
K.W.
4.1
4.1
4.1
4.2
4.2
4.1
4.1
4.1
4.2
4.2
4.1
4.1
4.1
4.2
4.2
115
T.C.
31.6
32.5
32.3
35.3
39.2
32.9
33.6
33.0
35.9
39.9
34.2
34.7
33.7
36.6
40.5
S.C.
31.5
31.3
26.5
25.9
19.9
32.8
33.3
28.6
28.1
21.2
34.0
35.3
30.7
30.3
22.6
K.W.
4.6
4.6
4.6
4.7
4.7
4.6
4.6
4.6
4.7
4.7
4.7
4.7
4.6
4.7
4.7
125
T.C.
29.7
30.3
30.2
33.0
36.5
30.7
31.8
30.7
33.4
37.0
31.8
32.7
31.2
33.8
37.5
S.C.
29.6
30.2
25.5
24.8
18.9
30.6
31.8
27.5
27.0
20.3
31.6
33.5
29.5
29.2
21.7
K.W.
5.2
5.1
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA16C
FC/MC48C
1.00
1.00
1.00
MA14D
FC/MC48D
1.00
1.00
1.00
MV16C
MC48C
1.01
1.00
1.00
MV20D
MC48D
1.01
1.00
1.00
AHP/SHP48
–
1.01
1.00
1.00
AHP/SHP60
–
1.01
1.00
1.00
AV/SV48
–
1.01
1.00
0.95
F*FP048
–
1.00
1.00
1.00
–
HC60
0.98
0.98
1.00
–
HD60
0.97
0.97
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
PV8*C16
FC/MC/PC48C
1.00
1.00
1.00
PV8*C20
FC/MC/PC48C
1.00
1.00
1.00
P(C,V)9*C16
FC/MC/PC48C
1.00
1.00
1.00
P(C,V)9*C20
FC/MC/PC48C
1.00
1.00
1.00
P(C,V)9*D20
FC/MC/PC48D
1.00
1.00
1.00
PV8*C20
HC60
0.98
0.98
1.00
P(C,V)9*C20
HC60
0.98
0.98
1.00
PV8*C16
HD60
0.98
0.98
1.00
PV8*C20
HD60
0.98
0.98
1.00
P(C,V)9*C16
HD60
0.98
0.98
1.00
P(C,V)9*C20
HD60
0.98
0.98
1.00
P(C,V)9*D20
HD60
0.98
0.98
1.00