background image

5292154-UIM-A-0317

2

Johnson Controls Unitary Products

INSPECTION

As soon as a coil is received, it should be checked to insure it is still
under pressure per Figure 1. The coil should be inspected for possible
damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information. Check drain pan for cracks or break-
age.

CLEARANCES

During Installation

Dimensions for indoor coils are provided in Tables 1 and 2. Clearance
must be provided for: 

1.

Refrigerant piping and connections

2.

Maintenance and servicing access - including cleaning the coil

3.

Condensate drain line

4.

Removal of coil assembly

 CAUTION

This product must be installed in strict compliance with the enclosed
installation instructions and any applicable local, state, and national
codes including, but not limited to building, electrical, and mechanical
codes.

 FIGURE 1:  

Pressure Check

 FIGURE 2:  

Component Location - Cased Coil CF Model

!

$

'(35(666&+5$'(5
&25(72&+(&.)25
35(6685(21(7,0(

127(

9HULI\WKDWWKHFRLOLVXQGHU
SUHVVXUHZKHQUHFHLYHG

A

0

267-

001

CO

IL A

CC

E

SS

PANEL

VERTI

C

AL P

OS

ITI

O

N -

S

E

CO

NDARY DRAIN

VERTI

C

AL

O

R

H

O

RIZ

O

NTAL

P

OS

ITI

O

N -

PRI

M

ARY DRAIN

H

O

RIZ

O

NTAL

P

OS

ITI

O

N -

S

E

CO

NDARY

DRAIN

VAP

O

R LINE

LI

Q

UID LINE

L

OC

ATI

O

N

TABLE 1: 

Dimensions - CF Upflow/Downflow Full Cased Coils

Models

1

1.

Asterisk (*)

 denotes coil model is available as a flex coil or with factory 

installed TXV.

Dimensions

 2

2. All dimensions are in inches.

Refrigerant 

Connections

3,4,5

3. Refrigerant line sizes may require larger lines for extended line lengths. See 

Application Data part number 247077.

4. Adapter fitting must be field installed for other line set size. 
5. See outdoor unit technical guide for proper line set size. 

Height

Width Opening Widths

A

B

C

D

Liquid

Vapor

CF18A*

19-1/2

14-1/2

13-1/2

13-1/2

 3/8

 3/4

CF18B*

19

17-1/2

16-1/2

16-1/2

CF24A*

19-1/2

14-1/2

13-1/2

13-1/2

CF24B*

19

17-1/2

16-1/2

16-1/2

CF24C

21

21

20

20

CF30A*

21-5/8

14-1/2

13-1/2

13-1/2

CF30B*

23

17-1/2

16-1/2

16-1/2

CF30C

21

21

20

20

CF30D

25

24/1/2

23-1/2

23-1/2

CF36A

25-1/2

14-1/2

13-1/2

13-1/2

CF36B*

25-5/8

17-1/2

16-1/2

16-1/2

CF36C

23

21

20

20

CF36D

25

24-1/2

23-1/2

23-1/2

CF42B*

25

17-1/2

16-1/2

16-1/2

 7/8

CF42C*

25

21

20

20

CF42D

25

24-1/2

23-1/2

23-1/2

CF48C*

27

21

20

20

CF48D

27

24-1/2

23-1/2

23-1/2

CF60C*

33

21

20

20

CF60D*

32-3/4

24-1/2

23-1/2

23-1/2

CF64D

32-3/4

24-1/2

23-1/2

23-1/2

$

´
23(1,1*

&23(1,1*

'23(1,1*

´

$

%2772023(1,1*
',0(16,216

´

%

Summary of Contents for CF18A

Page 1: ...ure Drop for CF Models 12 SECTION I GENERAL This instruction covers the installation of the following coils with fur naces or MP ME MVC modular air handlers The coils have sweat connect fittings All coils are shipped with a low psi nitrogen holding charge See Figures 1 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for per...

Page 2: ...HQ UHFHLYHG A0267 001 COIL ACCESS PANEL VERTICAL POSITION SECONDARY DRAIN VERTICAL OR HORIZONTAL POSITION PRIMARY DRAIN HORIZONTAL POSITION SECONDARY DRAIN VAPOR LINE LIQUID LINE LOCATION TABLE 1 Dimensions CF Upflow Downflow Full Cased Coils Models1 1 Asterisk denotes coil model is available as a flex coil or with factory installed TXV Dimensions 2 2 All dimensions are in inches Refrigerant Conne...

Page 3: ... CM18A 19 1 2 14 1 2 13 1 2 13 1 2 3 8 3 4 CM18B 19 17 1 2 16 1 2 16 1 2 CM24A 19 1 2 14 1 2 13 1 2 13 1 2 CM24B 19 17 1 2 16 1 2 16 1 2 CM24C 21 21 20 20 CM25B 25 5 8 17 1 2 16 1 2 16 1 2 CM30A 25 1 2 14 1 2 13 1 2 13 1 2 CM30B 23 17 1 2 16 1 2 16 1 2 CM30C 23 21 20 20 CM30D 25 24 1 2 23 1 2 23 1 2 CM36A 25 1 2 14 1 2 13 1 2 13 1 2 CM36B 25 5 8 17 1 2 16 1 2 16 1 2 CM36C 25 21 20 20 CM36D 25 24 1...

Page 4: ...ront of cabinet 2 Remove two screws from top front side of cabinet 3 Remove transition angle rotate angle 180 end for end and secure to top front side of cabinet 4 For installation with modular air handling unit remove the transition angle and discard it FIGURE 3 Component Location Cased Coil CM Model TABLE 3 Coil Air Flow Limits Coil 1 Size 1 Asterisk denotes coils only available with Factory Mou...

Page 5: ...Drain Connections for further installation instruction Horizontal right conversion CM Models only 1 Remove coil access panel 2 Slide coil drain pan assembly out of coil cabinet 3 Install the front and the back coil blow off wings apply only to N coils in accordance with the following a Locate 4 screws 2 front side and 2 back side securing the coil delta plates to the coil drain pan b Loosen each s...

Page 6: ... system or filter and will not be exposed to freezing temperatures Instruct the owner that the indoor coil drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage Coils should be installed level or pitched slightly toward the drain end Suggested pitch should not exceed 1 4 inch per foot of coil Drain plugs can be removed using a standard 3 8 drive socket rat...

Page 7: ...nd isolated by using appropriate hangers or strapping SECTION VIII COIL METERING DEVICES A piston or a TXV flex coil models is to be installed in the field There is an installation manual that comes with the TXV kit It is recommended to install the piston or TXV kit prior to installation of coil and brazing of line set Until brazing is completed and cooled the TXV sensing bulb must not be installe...

Page 8: ...the distributor assembly with supplied fittings Ensure Teflon washer is seated in distributor Hand tighten and turn an additional 1 4 turn to seal Do not over tighten fittings See Figure 16 5 Slide the nut removed in step 3 over the supplied liquid line Place supplied Teflon washer from TXV kit in place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so li...

Page 9: ...ILS Coils equipped with an EEV are available for use with a fully modulating matched system The EEV and controls are factory installed The installer only has to connect the included communication 4 wire cable to the communicating 4 pin connector on the furnace or modular blower control board See Figure 21 22 for connection diagrams and Figure 23 for wiring diagram FIGURE 16 TXV Installation WARNIN...

Page 10: ... 1 2 203 570 17 FFHVV SDQHO UHPRYHG 1 7 5 1 7 5 9 7521 2 9 35 0 5 5 1 137 9 325 5 5 5 17 1 211 7 21 48 5 5 5 17 1 211 7 21 25 217 5 1 3 1 6 21 5 5 1 25 217 2 1 7 21 3 3 7 5 137 6 21 5 5 1 83 2 137 9 57 5 1 3 1 2 203 570 17 FFHVV SDQHO UHPRYHG 1 7 5 1 7 5 9 7521 2 5217 9 2 2 25 0 02 9 1 225 2 35 6685 75 16 8 5 1 225 2 35 6685 75 16 8 5 FIGURE 21 Communicating Port of the ECM Modular Blower Control ...

Page 11: ...S ONLY IF ALUMINUM CONDUCTORS ARE PRESENT ALL APPLICABLE LOCAL AND NATIONAL CODES MUST BE FOLLOWED IPT INDOOR COIL PRESSURE TRANSDUCER ITS INDOOR COIL 7 03 5 785 SENSOR EEV ELECTRONIC EXPANSION VALVE 5292155 UWD B 0117 EEV MOTOR PR1 1 T1 GRN RED BLK WHT BLU BLU IPT YEL WHT BLK EEV RED BLU ORG WHT YEL ITS LED INDICATORS EEV CONTROL BOARD A C R B LEGEND EEV CONTROL LED DIAGNOSTIC CODES Control failu...

Page 12: ...48D 1250 1820 2250 2500 2795 3062 3307 CM49C 690 1150 1420 1630 1820 1990 2150 CM49D 970 1410 1740 2050 2290 2510 2710 CM50C 990 1440 1700 1950 2180 2390 2580 CM50D 940 1470 1890 2170 2430 2660 2870 CM60C 910 1551 1930 1820 2035 2229 2408 CM60D 1220 1730 2140 2440 2728 2988 3228 CM61C 990 1440 1700 1950 2180 2390 2580 CM61D 940 1470 1890 2220 2490 2720 2940 CM64D 970 1540 1800 1940 2169 2376 2566 ...

Page 13: ... 33 7 21 2 1 2 33 7 21 35 0 5 5 1 75 3 211 7 21 6 21 5 5 1 75 3 211 7 21 5 1 3 8 25 25 217 6 21 5 5 1 0 21 35 0 5 5 1 75 3 211 7 21 2 2 5 7 2 33 7 21 7 2 33 7 21 2 2 5 1 3 8 25 9 57 6 21 5 5 1 851 851 851 851 127 9HULI WKDW DOO GUDLQV DUH WUDSSHG RU SOXJJHG 83 2 33 7 21 2 1 2 33 7 21 5 1 5 2 5 1 5 2 5 7 2 33 7 21 7 2 33 7 21 2 5 1 5 2 5 1 5 25 0 35 0 5 5 1 75 3 211 7 21 6 21 5 5 1 75 3 211 7 21 5 ...

Page 14: ... change without notice Published in U S A 5292154 UIM A 0317 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 1187005 UIM G 0816 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: