Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recom-
mended. Applications above 0.5" are not recommended.

Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recom-
mended. Applications above 0.5" are not recommended.

SECTION XI: INSTALLATION 

VERIFICATION

Prior to and during the accomplishment of the installation procedures,
verify all tasks are accomplished as illustrated in Figures 4 - 19.

TABLE 4: 

Air Flow Data - Static Pressure Drop for CM Models

Coil

1

Size

1. Asterisk # denotes coils only available with Factory Mount EEV.

CFM @ Static Pressure Drop - IWG

(Based on dry coil)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

CM18A

500

700

840

997

1115

1221

1319

CM18B

670

960

1180

1340

1498

1641

1773

CM24A

490

710

850

980

1096

1200

1296

CM24B

760

1050

1330

1520

1699

1862

2011

CM24C

910

1330

1640

1820

2035

2229

2408

CM25B

710

1020

1210

1420

1588

1739

1878

CM30A

520

750

950

1040

1163

1274

1376

CM30B

670

1000

1230

1340

1498

1641

1773

CM30C

970

1410

1710

1940

2169

2376

2566

CM30D

1180

1720

2100

2360

2639

2890

3122

CM36A

520

740

920

1040

1163

1274

1376

CM36B

710

1020

1210

1420

1588

1739

1878

CM36C

980

1420

1690

1960

2191

2400

2593

CM36D

1210

1750

2150

2420

2706

2964

3201

CM37B

#

710

1020

1210

1420

1588

1739

1878

CM37C

#

980

1420

1690

1960

2191

2400

2593

CM38B

TBD

TBD

TBD

TBD

TBD

TBD

TBD

CM38C

#

690

1150

1420

1630

1820

1990

2150

CM42C

970

1420

1750

1940

2169

2376

2566

CM42D

1190

1730

2130

2380

2661

2915

3148

CM48C

970

1450

1910

1940

2169

2376

2566

CM48D

1250

1820

2250

2500

2795

3062

3307

CM49C

#

690

1150

1420

1630

1820

1990

2150

CM49D

#

970

1410

1740

2050

2290

2510

2710

CM50C

#

990

1440

1700

1950

2180

2390

2580

CM50D

#

940

1470

1890

2170

2430

2660

2870

CM60C

910

1551

1930

1820

2035

2229

2408

CM60D

1220

1730

2140

2440

2728

2988

3228

CM61C

#

990

1440

1700

1950

2180

2390

2580

CM61D

#

940

1470

1890

2220

2490

2720

2940

CM64D

970

1540

1800

1940

2169

2376

2566

TABLE 5: 

Air Flow Data - Static Pressure Drop for CF Models

Coil

Size

CFM @ Static Pressure Drop - IWG

(Based on dry coil)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

CF18A

515

720

870

1030

1152

1261

1363

CF18B

700

1000

1220

1400

1565

1715

1852

CF24A

500

730

880

1000

1118

1225

1323

CF24B

780

1090

1380

1560

1744

1911

2064

CF24C

950

1380

1700

1900

2124

2327

2513

CF30A

540

780

990

1080

1207

1323

1429

CF30B

690

1040

1280

1380

1543

1690

1826

CF30C

1000

1470

1780

2000

2236

2449

2646

CF30D

1230

1790

2180

2460

2750

3013

3254

CF36A

540

770

960

1080

1207

1323

1429

CF36B

740

1060

1250

1480

1655

1813

1958

CF36C

1020

1470

1260

2040

2281

2498

2699

CF36D

1250

1820

2330

2500

2795

3062

3307

CF42B

750

1100

1370

1500

1677

1837

1984

CF42C

1010

1470

1810

2020

2258

2474

2672

CF42D

1240

1790

2210

2480

2773

3037

3281

CF48C

1010

1500

1980

2020

2258

2474

2672

CF48D

1300

1890

2340

2600

2907

3184

3439

CF60C

950

1600

2000

1900

2124

2327

2513

CF60D

1270

1800

2220

2540

2840

3111

3360

CF64D

1010

1590

1870

2020

2258

2474

2672

 FIGURE 24:  

Drain Traps

THERMAL EXPANSION VALVE (TXV) CHECK LIST

Is coil metering device installed correctly?

 

Was correct TXV installed per the outdoor unit Technical Guide?

Is TXV temperature bulb positioned correctly?

Is TXV temperature bulb insulated? 

Is equalizer line connected? 

3” MINIMUM

HANDMADE TRAP

PREMADE TRAPS

SECONDARY

PRIMARY

WERE THE PRIMARY AND SECONDARY DRAINS TRAPPED CORRECTLY?

A0272-001

PLUG
(UNUSED
SECONDARY
DRAIN)

Summary of Contents for CF18A

Page 1: ...ure Drop for CF Models 12 SECTION I GENERAL This instruction covers the installation of the following coils with fur naces or MP ME MVC modular air handlers The coils have sweat connect fittings All coils are shipped with a low psi nitrogen holding charge See Figures 1 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for per...

Page 2: ...HQ UHFHLYHG A0267 001 COIL ACCESS PANEL VERTICAL POSITION SECONDARY DRAIN VERTICAL OR HORIZONTAL POSITION PRIMARY DRAIN HORIZONTAL POSITION SECONDARY DRAIN VAPOR LINE LIQUID LINE LOCATION TABLE 1 Dimensions CF Upflow Downflow Full Cased Coils Models1 1 Asterisk denotes coil model is available as a flex coil or with factory installed TXV Dimensions 2 2 All dimensions are in inches Refrigerant Conne...

Page 3: ... CM18A 19 1 2 14 1 2 13 1 2 13 1 2 3 8 3 4 CM18B 19 17 1 2 16 1 2 16 1 2 CM24A 19 1 2 14 1 2 13 1 2 13 1 2 CM24B 19 17 1 2 16 1 2 16 1 2 CM24C 21 21 20 20 CM25B 25 5 8 17 1 2 16 1 2 16 1 2 CM30A 25 1 2 14 1 2 13 1 2 13 1 2 CM30B 23 17 1 2 16 1 2 16 1 2 CM30C 23 21 20 20 CM30D 25 24 1 2 23 1 2 23 1 2 CM36A 25 1 2 14 1 2 13 1 2 13 1 2 CM36B 25 5 8 17 1 2 16 1 2 16 1 2 CM36C 25 21 20 20 CM36D 25 24 1...

Page 4: ...ront of cabinet 2 Remove two screws from top front side of cabinet 3 Remove transition angle rotate angle 180 end for end and secure to top front side of cabinet 4 For installation with modular air handling unit remove the transition angle and discard it FIGURE 3 Component Location Cased Coil CM Model TABLE 3 Coil Air Flow Limits Coil 1 Size 1 Asterisk denotes coils only available with Factory Mou...

Page 5: ...Drain Connections for further installation instruction Horizontal right conversion CM Models only 1 Remove coil access panel 2 Slide coil drain pan assembly out of coil cabinet 3 Install the front and the back coil blow off wings apply only to N coils in accordance with the following a Locate 4 screws 2 front side and 2 back side securing the coil delta plates to the coil drain pan b Loosen each s...

Page 6: ... system or filter and will not be exposed to freezing temperatures Instruct the owner that the indoor coil drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage Coils should be installed level or pitched slightly toward the drain end Suggested pitch should not exceed 1 4 inch per foot of coil Drain plugs can be removed using a standard 3 8 drive socket rat...

Page 7: ...nd isolated by using appropriate hangers or strapping SECTION VIII COIL METERING DEVICES A piston or a TXV flex coil models is to be installed in the field There is an installation manual that comes with the TXV kit It is recommended to install the piston or TXV kit prior to installation of coil and brazing of line set Until brazing is completed and cooled the TXV sensing bulb must not be installe...

Page 8: ...the distributor assembly with supplied fittings Ensure Teflon washer is seated in distributor Hand tighten and turn an additional 1 4 turn to seal Do not over tighten fittings See Figure 16 5 Slide the nut removed in step 3 over the supplied liquid line Place supplied Teflon washer from TXV kit in place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so li...

Page 9: ...ILS Coils equipped with an EEV are available for use with a fully modulating matched system The EEV and controls are factory installed The installer only has to connect the included communication 4 wire cable to the communicating 4 pin connector on the furnace or modular blower control board See Figure 21 22 for connection diagrams and Figure 23 for wiring diagram FIGURE 16 TXV Installation WARNIN...

Page 10: ... 1 2 203 570 17 FFHVV SDQHO UHPRYHG 1 7 5 1 7 5 9 7521 2 9 35 0 5 5 1 137 9 325 5 5 5 17 1 211 7 21 48 5 5 5 17 1 211 7 21 25 217 5 1 3 1 6 21 5 5 1 25 217 2 1 7 21 3 3 7 5 137 6 21 5 5 1 83 2 137 9 57 5 1 3 1 2 203 570 17 FFHVV SDQHO UHPRYHG 1 7 5 1 7 5 9 7521 2 5217 9 2 2 25 0 02 9 1 225 2 35 6685 75 16 8 5 1 225 2 35 6685 75 16 8 5 FIGURE 21 Communicating Port of the ECM Modular Blower Control ...

Page 11: ...S ONLY IF ALUMINUM CONDUCTORS ARE PRESENT ALL APPLICABLE LOCAL AND NATIONAL CODES MUST BE FOLLOWED IPT INDOOR COIL PRESSURE TRANSDUCER ITS INDOOR COIL 7 03 5 785 SENSOR EEV ELECTRONIC EXPANSION VALVE 5292155 UWD B 0117 EEV MOTOR PR1 1 T1 GRN RED BLK WHT BLU BLU IPT YEL WHT BLK EEV RED BLU ORG WHT YEL ITS LED INDICATORS EEV CONTROL BOARD A C R B LEGEND EEV CONTROL LED DIAGNOSTIC CODES Control failu...

Page 12: ...48D 1250 1820 2250 2500 2795 3062 3307 CM49C 690 1150 1420 1630 1820 1990 2150 CM49D 970 1410 1740 2050 2290 2510 2710 CM50C 990 1440 1700 1950 2180 2390 2580 CM50D 940 1470 1890 2170 2430 2660 2870 CM60C 910 1551 1930 1820 2035 2229 2408 CM60D 1220 1730 2140 2440 2728 2988 3228 CM61C 990 1440 1700 1950 2180 2390 2580 CM61D 940 1470 1890 2220 2490 2720 2940 CM64D 970 1540 1800 1940 2169 2376 2566 ...

Page 13: ... 33 7 21 2 1 2 33 7 21 35 0 5 5 1 75 3 211 7 21 6 21 5 5 1 75 3 211 7 21 5 1 3 8 25 25 217 6 21 5 5 1 0 21 35 0 5 5 1 75 3 211 7 21 2 2 5 7 2 33 7 21 7 2 33 7 21 2 2 5 1 3 8 25 9 57 6 21 5 5 1 851 851 851 851 127 9HULI WKDW DOO GUDLQV DUH WUDSSHG RU SOXJJHG 83 2 33 7 21 2 1 2 33 7 21 5 1 5 2 5 1 5 2 5 7 2 33 7 21 7 2 33 7 21 2 5 1 5 2 5 1 5 25 0 35 0 5 5 1 75 3 211 7 21 6 21 5 5 1 75 3 211 7 21 5 ...

Page 14: ... change without notice Published in U S A 5292154 UIM A 0317 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 1187005 UIM G 0816 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: