Checking Supply Air CFM

To check the supply air CFM after the initial balancing has

been completed:

1.Remove the two ¼ inch dot plugs in the duct panel.

2.Insert at least 8 inches of ¼ inch tubing into each of these

holes for sufficient penetration into the airflowon both sides

of the indoor coil.

3.Using an inclined manometer, determine the pressure drop

across the dry evaporator coil. Since the moisture on an

evaporator coil may vary greatly, measuring the pressure

drop across a wet coil under field conditions would be inac-

curate. To ensure a dry coil, the compressors should be de-

activated while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual

CFM through the unit can be determined from the curve in

Coil Delta P vs. Supply Air CFM figure.

WARNING!

Failure to properly adjust the total system air

quantity can result in extensive system damage.

After readings have been obtained, remove the tubes and

reinstall the two ¼ inch plugs removed in Step 1.

NOTE:

De-energize the compressors before taking any test

measurements to ensure a dry indoor coil.

035-16004-001-A-0202

Unitary Products Group

9

B1HA Coil Delta

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0

500

1000

1500

2000

2500

Airflow (CFM)

D

el

taS

ta

tic(

IW

G

)

B1HA018
B1HA024
B1HA042
B1HA030-36
B1HA048-60
Linear (B1HA018)
Linear (B1HA024)
Linear (B1HA030-36)
Linear (B1HA042)
Linear (B1HA048-60)

B1HA024

B1HA030-36

B1HA018

B1HA048-60

B1HA042

Summary of Contents for B1HA018A06

Page 1: ...refer ence forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory RENEWAL PARTS Refer to Replacement Parts Manual for complete listing of...

Page 2: ...with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO T...

Page 3: ...Refer to Figure 3 for information concerning rear and bottom supply and return air duct openings FILTERS Single phase units are shipped without a filter and is the responsi bility of the installer to...

Page 4: ...shipped with compressor mountings factory adjusted for shipping Caution Loosen compressor bolts half turn before operating unit 035 16004 001 A 0202 4 Unitary Products Group TABLE 2 PHYSICAL DATA MOD...

Page 5: ...wances for a dry indoor coil and no filters For additional pressure drops refer to the Additional Static Pressure Resistance table 208 volts MODEL NO BHA MOTOR SPEED EXTERNAL STATIC PRESSURE IWG 10 20...

Page 6: ...1 103 7 114 1 126 3 140 2 148 8 166 2 90 100 110 125 150 150 150 175 90 100 110 125 150 150 150 175 060 208 230 1 60 28 9 165 0 1 5 7 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5 10 0...

Page 7: ...04501558 2NH04502058 2NH04502558 1 1 2 2 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 21 3 27 3 33 3 39 3 25 30 35 40 25 30 35 40 060 575 3 60 6 4 50 0 0 6 2 8 2NH04501058 2NH04501558 2NH04502058 2NH0450255...

Page 8: ...4 0 36 0 50 50 96 40 060 208 230 1 60 187 253 28 9 165 0 1 5 7 0 44 6 60 60 96 40 036 208 230 3 60 187 253 10 9 78 0 1 1 3 5 18 2 25 25 96 75 042 208 230 3 60 187 253 14 1 110 0 1 1 3 5 22 2 30 30 96...

Page 9: ...test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit can be determined from the curve in Coil Delta P vs Supply Air CFM figure WARNING Failure to properly ad...

Page 10: ...14 2 18 8 23 4 28 0 32 5 37 1 37 3 37 5 37 7 37 9 75 10 1 14 0 17 9 21 8 25 7 29 5 33 4 34 3 35 2 36 1 37 0 80 10 5 13 7 17 0 20 2 23 4 26 6 29 8 31 4 33 0 34 6 36 2 85 11 0 13 5 16 0 18 5 21 1 23 6 2...

Page 11: ...5 19 4 23 9 28 3 95 5 5 6 6 7 8 12 5 17 3 22 1 26 8 100 5 4 6 3 10 4 14 6 18 7 22 9 105 8 3 11 8 15 4 19 0 110 6 2 9 1 12 1 15 0 115 6 4 8 8 11 1 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 5...

Page 12: ...105 5 6 6 2 8 7 11 3 13 9 16 4 110 5 8 7 9 10 0 12 2 115 6 2 7 9 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 71 73 75 65 34 0 34 2 34 4 34 6 34 8 35 0 35 2 36 2 37 3 38 4 39...

Page 13: ...1 6 8 7 5 8 2 9 1 10 1 11 0 11 9 110 5 5 6 3 7 2 8 0 8 9 9 8 10 7 11 6 115 5 9 6 9 7 8 8 7 9 5 10 4 11 2 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 71 73 75 65 26 7 27 6 28...

Page 14: ...PENING SIDE SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 15 14 1 2 283 8 33 8 31 2 289 16 23 8 13 4 13 4 13 4 31 2 15 14 1 2 14 1 2 BOTTOM SUPPLY AIR OPENING 23 8 33 4 471 4 LOW VOLTAGE CONN 7 8 DIA K...

Page 15: ...n the indoor blower will continue to run If the fan switch is in the AUTO position the K1 relay will open and de energize the indoor blower motor after the appropriate time delay Please refer to Table...

Page 16: ...TER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT 1 2 SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON SY...

Page 17: ...LE 22 THERMOSTAT SIGNALS THREE PHASE UNITS SIGNAL STATE BOARD FUNCTION G ON FAN INSTANT ON OFF FAN INSTANT OFF G Y O ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON AFTER ANTI SHORT CYCLE DELA...

Page 18: ...08 PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POIN...

Page 19: ...Group 19 035 16004 001 A 0202 FIG 5 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 0...

Page 20: ...0 2 1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2 3 4 P 2 S 2 8 0 9 O 8 0 8 B R 2 0 4 B R S E E N O T E 8...

Page 21: ...ELEC HEAT 20 25 ALL KW ELEC HEAT 20 25 KW ELEC HEAT PTCR START ASSIST OPTIONAL DEVICE 20 25 20 25 20 25 CB CIRCUIT BREAKER 24V 3 AMP F7 F8 F9 TB2 TERMINAL BLOCK ECM MOTOR SPEED CONNECTIONS M2 CONTACT...

Page 22: ...22 Unitary Products Group 035 16004 001 A 0202...

Page 23: ...Unitary Products Group 23 035 16004 001 A 0202...

Page 24: ...ry Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved Supersedes 035 16004 000...

Reviews: