![York B1HA018A06 Installation Instruction Download Page 6](http://html1.mh-extra.com/html/york/b1ha018a06/b1ha018a06_installation-instruction_3622070006.webp)
035-16004-001-A-0202
6
Unitary Products Group
BHA
POWER
SUPPLY
COMPRESSOR
OUTDOOR
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
MAX.
HACR
BREAKER
SIZE
MODEL
RLA
LRA
MODEL NO.
ST
AGE
KW
TOTAL
AMPS
018 208/230-1-60
9.0
48.0
1.1
2.6
2NH04500506
2NH04500706
1
2
3.8/5.0 *
5.6/7.5 *
18.1/20.8
27.1/31.3
37.5/41.0
48.8/54.0
40/45
50/60
40/45
50/60
024 208/230-1-60
11.2
60.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
1
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
18.1/20.8
27.1/31.3
36.1/41.7
40.7/44.2
52.0/57.2
63.3/70.2
45/50
60/60
70/80
45/50
60/60
70/80
030 208/230-1-60
14.7
73.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.3/31.3
36.1/41.7
54.2/62.5
44.7/48.2
56.0/61.2
67.3/74.2
89.8/100.3
50/50
60/70
70/80
90/110
50/50
60/70
70/80
90/110
14.7
73.0
1.1
2.6
2ND04501506
2
3.8/5.0
18.1/20.8
44.7/48.2
50/50
50/50
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
036 208/230-1-60
17.3
94.0
1.1
3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
48.8/52.3
60.1/65.3
71.4/78.3
93.9/104.4
60/60
70/70
80/80
100/110
60/60
70/70
80/80
100/110
17.3
94.0
1.1
3.5
2ND04501506
2
3.8/5.0
18.1/20.8
48.8/52.3
60/60
60/60
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
042 208/230-1-60
20.5
120.0
1.1
3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
52.8/56.3
64.1/69.3
75.4/82.3
97.9/108.4
60/70
70/80
80/90
100/110
60/70
70/80
80/90
100/110
20.5
120.0
1.1
3.5
2ND04501506
2
3.8/5.0
18.1/20.8
52.8/56.3
60/70
60/70
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
048 208/230-1-60
24.4
140.0
1.5
4.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
81.1/88.1
103.7/114.1
126.3/140.2
148.8/166.2
90/100
110/125
150/150
150/175
90/100
110/125
150/150
150/175
060 208/230-1-60
28.9
165.0
1.5
7.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
89.8/96.7
112.3/122.8
134.9/148.8
157.5/174.8
100/110
125/125
150/150
175/175
100/110
125/125
150/150
175/175
036 208/230-3-60
10.9
78.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
44.3/48.3
57.3/63.3
45/50
60/70
45/50
60/70
042 208/230-3-60
14.1
110.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
48.3/57.3
61.3/67.3
50/60
70/70
50/60
70/70
048 208/230-3-60
14.1
105.0
1.5
4.0
2NH04501025
2NH04501525
2NH04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
49.2/53.2
62.2/68.2
75.3/83.3
88.3/98.3
50/60
70/70
80/90
90/100
50/60
70/70
80/90
90/100
060 208/230-3-60
16.0
125.0
1.5
7.0
2NH04501025
2NH04501525
2NH04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
54.6/58.6
67.6/73.6
80.7/88.7
93.7/103.7
60/60
70/80
90/90
100/110
60/60
70/80
90/90
100/110
036
460-3-60
5.8
40.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.8
18.0
24.6
32.2
25
35
25
35
042
460-3-60
7.1
54.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.0
18.0
26.2
33.8
30
35
30
35
048
460-3-60
7.1
55.0
0.8
2.0
2NH04501046
2NH04501546
2NH04502046
2NH04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
26.7
34.2
41.7
49.3
30
35
45
50
30
35
45
50
060
460-3-60
8.0
67.0
0.8
3.5
2NH04501046
2NH04501546
2NH04502046
2NH04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
29.4
36.9
44.4
51.9
30
40
45
60
30
40
45
60
= Dual element, time delay type.
* = KW listed is for 240 volts, use table at top of page for 208 or 230 volts.
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table at top of page for 460 volts.
over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table at top of page for 575 volts.
TABLE 5 -
ELECTRICAL DATA
(HEAT PUMP / ELECTRIC HEAT)