background image

NORMAL MAINTENANCE

CAUTION: Prior to any of the following maintenance proce-

dures, shut off all electric power to the unit to
prevent personal injury.

FILTERS - Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace permanent
type with disposable. The dimensional size of the replacement
filter must be the same as the replaced filter.

MOTORS

Outdoor fan motors are permanently lubricated and require no
maintenance.

Indoor Blower Motor and Drive - The indoor blower motor
features ball bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the
life of components but is optional.

CAUTION: Damage can occur if the bearings are overlubri-

cated. Use grease sparingly.

WARNING: Perform all maintenance operations on the blower

motor with electric power disconnected from the
unit. Do not attempt to lubricate bearings with the
unit in operation.

On an annual basis, check the motor for accumulations
of dust, etc. that may block the cooling slots in the motor
shell. Check for loose, damaged or misaligned drive

components. Check that all mounting bolts are tight. Replace
defective parts as required.

If desired, every three years remove both pipe plugs at each
end shell and clean out any hardened grease or foreign matter.
Replace one plug on each end with a clean grease fitting. Using
a low pressure grease gun, pump grease (Chevron SRI-2 or
equivalent) into the bearing cavity until new grease shows at
the open port. Do not over lubricate. Run the motor for ten
minutes until excess grease is purged from the cavity. Replace
the plugs.

On 20 ton only, units are supplied with blower shaft bearings
that do not require maintenance but may be relubricated if
desired. Every three years, using a low pressure grease gun,
pump grease into the bearing grease fitting until grease just
begins to show at the seals. Do not over lubricate. Use any
lithium base grease recommended for ball bearing service.

OUTDOOR COIL - Dirt should not be allowed to accumulate
on the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep coil clean.
Use a brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean coil, be sure electric power to
the unit is shut off prior to cleaning.

NOTE: Exercise care when cleaning the coil so that the coil

fins are not damaged.

Do not permit the hot outdoor air discharge to be
obstructed by overhanging structures of shrubs.

SECURE OWNER’S APPROVAL

When the system is functioning properly, secure the owner’s approval. Show him the

location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature
settings within the limitations of the system.

MAINTENANCE

FIG. 12 - AMBIENT MODIFIED TIME/TEMPERATURE CONTROL

T1 - 50 MINUTE SETTING

T2 - 80 MINUTE SETTING

T3 - 110 MINUTE SETTING
(Factory Set Point)

SHORTING PEGS TO
OVERRIDE TIMER
FOR SERVICE

MOVABLE JUMPER
WIRE TO CHANGE
DEFROST TIMER

511.06-N3Y

18

Unitary Products Group

Summary of Contents for B1CH180

Page 1: ...in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following referenc...

Page 2: ...10 Blower Motor and Drive Data 13 11 Electrical Data Basic Units 14 12 Electrical Data Units w Elec Heat 14 13 Heat Anticipator Setpoints 16 FIGURES No Description Page 1 Typical Rigging 3 2 Center of...

Page 3: ...ion across the unit MUST be used across the top of the unit Refer to the Typical Rigging Figure Units may also be moved or lifted with a forklift from the front or rear only providing that an accessor...

Page 4: ...ndensate drain operates in a negative pressure in the cabinet The condensate drain line MUST be trapped to provide proper drainage COMPRESSORS Units are shipped with compressor mountings factory adjus...

Page 5: ...same minimum gauge as the replaced wire Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly f...

Page 6: ...the setpoint and minimum position adjusting screws to prevent twisting them off 1 The enthalpy set point may now be set by selecting the desired setpoint shown in the Adjusting Enthalpy Setpoint Figur...

Page 7: ...FIG 6 ENTHALPY SETPOINT ADJUSTMENT 511 06 N3Y Unitary Products Group 7...

Page 8: ...COMPRESSOR Qty Per Unit 7 1 2 TON TANDEM 2 10 TON TANDEM 2 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0...

Page 9: ...TION OUTDOOR SECTION Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 3 With Economizer 4 Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36...

Page 10: ...535 583 559 240 2 390 514 538 684 654 NOTE These weights are with economizer and 36kW electric heat UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2 190 342 358 373 388 372 357 240 2 390 343 359 407 45...

Page 11: ...7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1...

Page 12: ...0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9...

Page 13: ...Access 950 1120 BK110 10 75 10 4 1 3 16 BX80 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because t...

Page 14: ...37 5 75 1 112 6 150 1 133 0 133 0 179 9 179 9 150 150 200 200 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 141 4 141 4 195 5 195 5 150 150 200 200 180A46 460 3 60 E01...

Page 15: ...perature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambient temperature is...

Page 16: ...ler To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances...

Page 17: ...is energized The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes During troubleshooting the defrost tim...

Page 18: ...r equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 t...

Page 19: ...511 06 N3Y Unitary Products Group 19...

Page 20: ...Code SBY 511 06 N3Y 5005 York Drive Norman OK 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved...

Reviews: