TABLE 6 - SUPPLY AIR BLOWER PERFORMANCE (15 TON)

180 MBH - BOTTOM DUCT CONNECTIONS

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

CFM

4500

5250

6000

6750

7200

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE

850

6.0**

0.9

2.4

2.2

0.7

3.0

2.7

0.5

3.2

2.9

-

-

-

-

-

-

870

5.5

1.0

2.5

2.3

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

4.5

1.1

2.6

2.4

0.9

3.4

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

3.5

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

4.9

4.4

980

3.0

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1010

2.0

1.4

3.1

2.8

1.2

3.8

3.4

1.0

4.2

3.8

0.7

5.0

4.5

0.6

5.4

4.8

1040

1.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.2

4.7

0.7

5.7

5.1

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

965

6.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

5.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1025

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.8

5.1

4.6

0.7

5.6

5.0

1065

3.5

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.0

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.0

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.0

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE

870

6.0**

1.0

2.4

2.2

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

5.0

1.1

2.6

2.4

0.9

3.3

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

4.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

3.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

2.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

1.0

1.6

3.3

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

980

6.0

1.3

2.9

2.6

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

4.0

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.5

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.5

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.5

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

4.0

3.6

2.1

4.8

4.3

2.0

5.7

5.1

-

-

-

-

-

-

  NOTES: 1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry indoor coil and no electric heat.

 

  2. Refer to Page 12 for additional static resistances.

  ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted
  from the total static pressure of the blower.

 * 

Do 

NOT close the pulley below 1 turn open.

  ** Factory setting.

511.06-N3Y

Unitary Products Group

11

Summary of Contents for B1CH180

Page 1: ...in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following referenc...

Page 2: ...10 Blower Motor and Drive Data 13 11 Electrical Data Basic Units 14 12 Electrical Data Units w Elec Heat 14 13 Heat Anticipator Setpoints 16 FIGURES No Description Page 1 Typical Rigging 3 2 Center of...

Page 3: ...ion across the unit MUST be used across the top of the unit Refer to the Typical Rigging Figure Units may also be moved or lifted with a forklift from the front or rear only providing that an accessor...

Page 4: ...ndensate drain operates in a negative pressure in the cabinet The condensate drain line MUST be trapped to provide proper drainage COMPRESSORS Units are shipped with compressor mountings factory adjus...

Page 5: ...same minimum gauge as the replaced wire Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly f...

Page 6: ...the setpoint and minimum position adjusting screws to prevent twisting them off 1 The enthalpy set point may now be set by selecting the desired setpoint shown in the Adjusting Enthalpy Setpoint Figur...

Page 7: ...FIG 6 ENTHALPY SETPOINT ADJUSTMENT 511 06 N3Y Unitary Products Group 7...

Page 8: ...COMPRESSOR Qty Per Unit 7 1 2 TON TANDEM 2 10 TON TANDEM 2 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0...

Page 9: ...TION OUTDOOR SECTION Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 3 With Economizer 4 Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36...

Page 10: ...535 583 559 240 2 390 514 538 684 654 NOTE These weights are with economizer and 36kW electric heat UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2 190 342 358 373 388 372 357 240 2 390 343 359 407 45...

Page 11: ...7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1...

Page 12: ...0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9...

Page 13: ...Access 950 1120 BK110 10 75 10 4 1 3 16 BX80 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because t...

Page 14: ...37 5 75 1 112 6 150 1 133 0 133 0 179 9 179 9 150 150 200 200 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 141 4 141 4 195 5 195 5 150 150 200 200 180A46 460 3 60 E01...

Page 15: ...perature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambient temperature is...

Page 16: ...ler To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances...

Page 17: ...is energized The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes During troubleshooting the defrost tim...

Page 18: ...r equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 t...

Page 19: ...511 06 N3Y Unitary Products Group 19...

Page 20: ...Code SBY 511 06 N3Y 5005 York Drive Norman OK 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved...

Reviews: