LIMITATIONS

These units must be installed in accordance with the following
national and local safety codes:

In U.S.A.:

1. National Electrical Code ANSI/NFPA No. 70.
2. Local electric utility requirements.

In Canada:

1. Current Canadian Electrical Code CSA C22.1.
2. Local electrical codes.
Refer to the Unit Application Data and to thefor Electric Heat
Application Data table.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or the customer’s
expense.

Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of
the Air Conditioning Contractors of America (ACCA).

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. Unit is designed for outdoor installation only.
2. Outdoor coils must have an unlimited supply of air. Where

a choice of location is possible, position the unit on either
north or east side of building.

3. For ground level installation, use a level concrete slab with

a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rail
dimensions. Do not tie slab to the building foundation.

4. Roof structures must be able to support the weight of the

unit and its options and/or accessories. Unit must be
installed on a solid level roof curb or appropriate angle iron
frame.

CAUTION: If a unit is to be installed on a roof curb or

special frame other than a YORK roof curb,
gasketing must be applied to all surfaces that
come in contact with the unit underside.

5. Maintain level tolerance to 1/2" maximum across the entire

length or width of the unit.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the round lifting holes
provided in the base rails. Spreaders, whose length exceeds
the larger dimension across the unit, MUST be used across the
top of the unit. Refer to the Typical Rigging Figure.

Units may also be moved or lifted with a forklift, from the front
or rear only, providing that an accessory skid is used.

LENGTH OF FORKS MUST BE A MINIMUM OF 90".

Refer to the Physical Data tablefor unit weights and to the figure
below for approximate center of gravity.

CLEARANCES

All units require certain clearances for proper operation and
service. Refer to the Dimensions and Clearances Figure for the
clearances required for combustible construction, servicing,
and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct outdoor air discharge outlet.

DUCTWORK

Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize transmission of noise.
The supply and return air duct systems should be designed for
the CFM and static requirements of the job. They should NOT
be sized to match the dimensions of the duct connections on
the unit.
CAUTION: When fastening ductwork to side duct flanges on

the unit, insert screws through duct flanges only.
DO NOT insert screws through casing.
Outdoor ductwor k must be insulated and
waterproofed.

Refer to the Dimensions and Clearances Figure for information
concerning side and bottom supply and return air duct openings.

INSTALLATION

Model Size

15 TON

20 TON

Voltage Variation,

 Min. / Max.

1

208/230-3-60

187 / 253

460-3-60

414 / 506

575-3-60

518 / 630

Supply Air CFM,  Min. / Max.

4500

2

 / 7200

6000 / 9400

Wet Bulb Temperature (

°

F)

of Air on Indoor Coil

Min. / Max.

57 / 72

Dry Bulb Temperature (

°

F)

of Air on Outdoor Coil

Min. / Max.

45 / 120

1

Rated in accordance with ARI Standard 110, utilization range "A".

2

5,000 CFM on 15 ton models with either a 54 or 72 KW heater at 208/230 volts.

TABLE 1 - UNIT APPLICATION DATA

FIG. 1 - TYPICAL RIGGING

OUTDOOR

COIL END

FIG. 2 - CENTER OF GRAVITY

511.06-N3Y

Unitary Products Group

3

Summary of Contents for B1CH180

Page 1: ...in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following referenc...

Page 2: ...10 Blower Motor and Drive Data 13 11 Electrical Data Basic Units 14 12 Electrical Data Units w Elec Heat 14 13 Heat Anticipator Setpoints 16 FIGURES No Description Page 1 Typical Rigging 3 2 Center of...

Page 3: ...ion across the unit MUST be used across the top of the unit Refer to the Typical Rigging Figure Units may also be moved or lifted with a forklift from the front or rear only providing that an accessor...

Page 4: ...ndensate drain operates in a negative pressure in the cabinet The condensate drain line MUST be trapped to provide proper drainage COMPRESSORS Units are shipped with compressor mountings factory adjus...

Page 5: ...same minimum gauge as the replaced wire Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly f...

Page 6: ...the setpoint and minimum position adjusting screws to prevent twisting them off 1 The enthalpy set point may now be set by selecting the desired setpoint shown in the Adjusting Enthalpy Setpoint Figur...

Page 7: ...FIG 6 ENTHALPY SETPOINT ADJUSTMENT 511 06 N3Y Unitary Products Group 7...

Page 8: ...COMPRESSOR Qty Per Unit 7 1 2 TON TANDEM 2 10 TON TANDEM 2 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0...

Page 9: ...TION OUTDOOR SECTION Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 3 With Economizer 4 Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36...

Page 10: ...535 583 559 240 2 390 514 538 684 654 NOTE These weights are with economizer and 36kW electric heat UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2 190 342 358 373 388 372 357 240 2 390 343 359 407 45...

Page 11: ...7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1...

Page 12: ...0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9...

Page 13: ...Access 950 1120 BK110 10 75 10 4 1 3 16 BX80 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because t...

Page 14: ...37 5 75 1 112 6 150 1 133 0 133 0 179 9 179 9 150 150 200 200 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 141 4 141 4 195 5 195 5 150 150 200 200 180A46 460 3 60 E01...

Page 15: ...perature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambient temperature is...

Page 16: ...ler To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances...

Page 17: ...is energized The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes During troubleshooting the defrost tim...

Page 18: ...r equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 t...

Page 19: ...511 06 N3Y Unitary Products Group 19...

Page 20: ...Code SBY 511 06 N3Y 5005 York Drive Norman OK 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved...