TABLE 8 - STATIC RESISTANCES

1

TABLE 9 - POWER EXHAUST PERFORMANCE

MOTOR

SPEED

STATIC RESISTANCE OF RETURN DUCTWORK, IWG

0.2

0.3

0.4

0.5

0.6

CFM

KW

CFM

KW

CFM

KW

CFM

KW

CFM

KW

HIGH*

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

*

Factory Setting

  Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.

MODEL

SIZE

DRIVE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP FRAME

EFF.

(%)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

15 TON

Stan-

dard

850/1065

5

184T

83

1VP56

5.35

4.3-
5.3

2

1-1/8

BK90

8.75

8.4

1

BX70

71.8

1

High

Speed

Access

965/1190

BK80

7.75

7.4

1

BX68

69.8

1

20 TON

Stan-

dard

870/1025

7.5

213T

89

1VP68

6.75

5.5-
6.5

2

1-3/8

BK120

11.75

11.4 1-3/16

BX83

84.8

1

High

Speed

Access

950/1120

BK110

10.75

10.4 1-3/16

BX80

81.8

1

1

All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream

  of any heating device.

Do NOT close this pulley below 1 turn open.

TABLE 10 - BLOWER MOTOR AND DRIVE DATA

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

15 TON

20 TON

4500

6000

7200

6000

8000

9400

WET INDOOR COIL

0.1

0.1

0.1

0.1

0.1

0.1

ELECTRIC HEAT OPTIONS

18 KW

0.1

0.1

0.1

0.1

0.1

0.1

36 KW

0.1

0.2

0.3

0.1

0.2

0.3

54 KW

0.2

0.3

0.4

0.2

0.3

0.4

72 KW

0.2

0.4

0.6

0.2

0.4

0.6

ECONOMIZER OPTION

0.1

0.1

0.1

0.1

0.1

0.1

HORIZONTAL DUCT CONNECTIONS

2

0.2

0.3

0.5

0.2

0.3

0.5

1

Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table. (See Note 2 for exception.)

2

Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the

  respective unit’s blower performance table.

511.06-N3Y

Unitary Products Group

13

Summary of Contents for B1CH180

Page 1: ...in writing Refer to Form 50 15 NM for additional information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following referenc...

Page 2: ...10 Blower Motor and Drive Data 13 11 Electrical Data Basic Units 14 12 Electrical Data Units w Elec Heat 14 13 Heat Anticipator Setpoints 16 FIGURES No Description Page 1 Typical Rigging 3 2 Center of...

Page 3: ...ion across the unit MUST be used across the top of the unit Refer to the Typical Rigging Figure Units may also be moved or lifted with a forklift from the front or rear only providing that an accessor...

Page 4: ...ndensate drain operates in a negative pressure in the cabinet The condensate drain line MUST be trapped to provide proper drainage COMPRESSORS Units are shipped with compressor mountings factory adjus...

Page 5: ...same minimum gauge as the replaced wire Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly f...

Page 6: ...the setpoint and minimum position adjusting screws to prevent twisting them off 1 The enthalpy set point may now be set by selecting the desired setpoint shown in the Adjusting Enthalpy Setpoint Figur...

Page 7: ...FIG 6 ENTHALPY SETPOINT ADJUSTMENT 511 06 N3Y Unitary Products Group 7...

Page 8: ...COMPRESSOR Qty Per Unit 7 1 2 TON TANDEM 2 10 TON TANDEM 2 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0...

Page 9: ...TION OUTDOOR SECTION Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 3 With Economizer 4 Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36...

Page 10: ...535 583 559 240 2 390 514 538 684 654 NOTE These weights are with economizer and 36kW electric heat UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2 190 342 358 373 388 372 357 240 2 390 343 359 407 45...

Page 11: ...7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1...

Page 12: ...0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9...

Page 13: ...Access 950 1120 BK110 10 75 10 4 1 3 16 BX80 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because t...

Page 14: ...37 5 75 1 112 6 150 1 133 0 133 0 179 9 179 9 150 150 200 200 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 141 4 141 4 195 5 195 5 150 150 200 200 180A46 460 3 60 E01...

Page 15: ...perature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambient temperature is...

Page 16: ...ler To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances...

Page 17: ...is energized The defrost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes During troubleshooting the defrost tim...

Page 18: ...r equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 t...

Page 19: ...511 06 N3Y Unitary Products Group 19...

Page 20: ...Code SBY 511 06 N3Y 5005 York Drive Norman OK 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved...

Reviews: