ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

LIQUID LINE FILTER-DRIER

The air conditioning unit’s copper spun filter/dryer is located on the liq-
uid line.

NOTE: Replacements for the liquid line drier must be exactly the same

as marked on the original factory drier. See Source 1 for O.E.M.
replacement driers.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade (ACR) copper tubing that is
internally clean and dry. Units should be installed only with the tubing
sizes for approved system combinations as specified in tabular data
sheet. The charge given is applicable for total tubing lengths up to 15
feet. See Application Data Part Number 036-61920-000 for installing
tubing of longer lengths and elevation differences.

NOTE: Using a larger than specified line size could result in oil return

problems. Using too small a line will result in loss of capacity
and other problems caused by insufficient refrigerant flow. Slope
horizontal vapor lines at least 1" every 20 feet toward the out-
door unit to facilitate proper oil return.

OIL TRAPPING

When the outdoor unit is above the indoor coil, oil trapping is necessary.
An oil trap should be provided for every 20 ft. of rise. See Figure 2.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2" foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humid-
ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow
tube metal-to-metal contact. See Figure 3.

6.

Use PVC piping as a conduit for all underground installations as
shown in Figure 4. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown

7.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

8.

For systems with total line length exceeding 50 ft., see APPLICA-
TION DATA and worksheet  "General Piping Recommendations
and Refrigerant Line Length" for vapor and liquid line sizing, cali-
bration of liquid line pressure loss or gain, determination of vapor
line velocity, elevation limitations, orifice connections, system
charging, traps, etc.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

R-22

Filter-Drier

Source 1 Part No.

Apply with Models

AY / AM

029-22156-000

All Models

 FIGURE 2:  Oil Trap

INDOOR

COIL

OUTDOOR COIL

20 Ft.

20 Ft.

10 In.

6 In.

 FIGURE 3:  Installation of Vapor Line

 FIGURE 4:  Underground Installation

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

TO INDOOR COIL

Liquid Line

PVC
Conduit

Insulated
Vapor Line

TO OUTDOOR UNIT

Cap

Summary of Contents for AY012-036 SERIES

Page 1: ...ded could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe prac...

Page 2: ...he system for 10 hours Monitor the suction drier pressure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suc...

Page 3: ...ant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rub ber insulation Armaflex or equivalent Liquid lines that w...

Page 4: ...out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an additional 1...

Page 5: ...plate Total system charge is determined as follows 1 Determine outdoor unit charge from tabular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge using...

Page 6: ...F Pressure PSIG Temp F 80 48 110 64 140 78 170 91 200 101 230 111 82 49 112 65 142 79 172 91 202 102 232 112 84 50 114 66 144 80 174 92 204 103 234 112 86 51 116 67 146 81 176 93 206 103 236 113 88 5...

Page 7: ...seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat FIGURE 7 Typical Air Handler Thermostat Wiring FIGURE 8 Typi...

Page 8: ...er furnace or air handler will be operating dis charging cool air from the ducts Coils or other parts in the air cir cuit should be cleaned as often as necessary to keep the unit clean Use a brush vac...