Unitary Products Group

LIMITATIONS

The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:

1.

Limitations for the indoor unit, coil, and appropriate accessories
must also be observed.

2.

The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.

3.

The maximum and minimum conditions for operation must be
observed to ensure a system that will give maximum performance
with minimum service.

4.

The unit should not be operated at outdoor temperatures below
50° F without an approved low ambient operation accessory kit
installed.

SECTION III: UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, air discharge, and service access. See Figure 1.

NOTE: For multiple unit installations, units must be spaced a minimum

of 18 inches apart (coil face to coil face).

If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit.

Provide an adequate structural support.

ADD-ON REPLACEMENT/RETROFIT

The following steps should be performed in order to insure proper sys-
tem operation and performance.

1.

Change-out the indoor coil, if required, to an approved R-22 coil/
condensing unit combination with the appropriate metering device.

2.

If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier in the suction-line is required, in addition to the factory
installed liquid-line drier. Operate the system for 10 hours. Monitor
the suction drier pressure drop. If the pressure drop exceeds 3
psig, replace both the suction-line and liquid-line driers. After a
total of 10 hours run time where the suction-line pressure drop has
not exceeded 3 psig, replace the liquid line drier, and remove the
suction-line drier. Never leave a suction-line drier in the system
longer than 50 hours of run time.

GROUND INSTALLATION

The unit should be installed on a solid base that is 2” above grade and
will not shift or settle, causing strain on the refrigerant lines and possible
leaks. Maintain the clearances shown in Figure 1 and install the unit in a
level position. The base pad should not come in contact with the foun-
dation or side of the structure because sound may be transmitted to the
residence.

The length of the refrigerant tubing between the outdoor unit and indoor
coil should be as short as possible to avoid capacity and efficiency
losses. Excessive spacing of the outdoor unit from the home can result
in the refrigerant lines being restricted by trampling or being punctured

by lawn mowers. Locate the outdoor unit away from bedroom windows
or other rooms where sound might be objectionable.

Adverse effects of  snow or sleet accumulating on the outdoor coil can
be eliminated by placing the outdoor unit where the prevailing wind
does not blow across the unit. Trees, shrubs, corners of buildings, and
fences standing off from the coil can reduce capacity loss due to wind
chill effect.

Provide ample clearance from shrubs to allow adequate air to pass
across the outdoor coil without leaves or branches being pulled into the
coil.

TABLE 1: Application Limitations

Ambient Air Temperature 

on Outdoor Coil

Air Temperature on

Indoor Coil

Min. DB

Max. DB

Min. WB

Max. WB

50 °F

115 °F

57 °F

72 °F

 FIGURE 1:  Typical Installation

THERMOSTAT

SEAL OPENING(S) WITH

PERMAGUM OR EQUIVALENT

TO INDOOR COIL

TO FURNACE OR

AIR HANDLER

TERMINAL BLOCK

NEC CLASS 2 WIRING

NEC CLASS 1 WIRING

NOTE:ALL OUTDOOR WIRING

MUST BE WEATHERPROOF.

CONTROL ACCESS PANEL

WEATHERPROOF

DISCONNECT

SWITCH

MINIMUM 24” SERVICE ACCESS

CLEARANCE ON ONE SIDE

48” OVERHEAD

CLEARANCE

12” CLEARANCE

AROUND PERIMETER

Summary of Contents for AY012-036 SERIES

Page 1: ...ded could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe prac...

Page 2: ...he system for 10 hours Monitor the suction drier pressure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suc...

Page 3: ...ant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rub ber insulation Armaflex or equivalent Liquid lines that w...

Page 4: ...out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an additional 1...

Page 5: ...plate Total system charge is determined as follows 1 Determine outdoor unit charge from tabular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge using...

Page 6: ...F Pressure PSIG Temp F 80 48 110 64 140 78 170 91 200 101 230 111 82 49 112 65 142 79 172 91 202 102 232 112 84 50 114 66 144 80 174 92 204 103 234 112 86 51 116 67 146 81 176 93 206 103 236 113 88 5...

Page 7: ...seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat FIGURE 7 Typical Air Handler Thermostat Wiring FIGURE 8 Typi...

Page 8: ...er furnace or air handler will be operating dis charging cool air from the ducts Coils or other parts in the air cir cuit should be cleaned as often as necessary to keep the unit clean Use a brush vac...

Reviews: