background image

Subject to change without notice. Printed in U.S.A.

126115-UIM-D-0306

Copyright

 ©

 by York International Corp. 2006. All rights reserved.

Supersedes: 126115-UIM-C-0106

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

CFM SELECTION BOARD SETTINGS

For proper system operation the CFM Selection Board jumpers must be
set properly. 

Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.

Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.

The HUMIDISTAT jumper must also be removed if a dehumidistat is
installed.

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 6-9. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

INDICATIONS OF PROPER OPERATION

Cooling

1.

The outdoor fan should be running, with warm air being dis-
charged from the top of the unit.

2.

The indoor blower (furnace or air handler) will be operating, dis-
charging cool air from the ducts. Coils or other parts in the air cir-
cuit should be cleaned as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment, or other suitable
means.

3.

The vapor line at the outdoor unit will feel cool to the touch.

4.

The liquid line at the outdoor unit will feel warm to the touch.

Instructing the Owner

Assist owner with processing warranty cards. Review Owners Guide
and provide a copy to the owner and guidance on proper operation and
maintenance. Instruct the owner or the operator how to start, stop and
adjust temperature setting.

When applicable, instruct the owner that the compressor is equipped
with a crankcase heater to prevent the migration of refrigerant to the
compressor during the “OFF” cycle. The heater is energized only when
the unit is not running. If the main switch is disconnected for long peri-
ods, do not attempt to start the unit until 8 hours after the switch has
been connected. This will allow sufficient time for all liquid refrigerant to
be driven out of the compressor.

The installer should also instruct the owner on proper operation and
maintenance of all other system components.

Maintenance

1.

Dirt should not be allowed to accumulate on the outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.

2.

The outdoor fan motor is permanently lubricated and does not
require periodic oiling.

3.

If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.

4.

Refer to the furnace or air handler instructions for filter and blower
motor maintenance.

5.

The indoor coil drain pan should be inspected and cleaned regu-
larly to prevent odors and assure proper drainage.

 FIGURE 10:  CFM Selection Board

CFM SELECTION BOARD

TAP SELECTION

D
C
B
A

D
C
B
A

COOL

HEAT

ADJ

DELAY

REMOVE FOR

HEAT PUMP

HUMIDISTAT

Summary of Contents for AY012-036 SERIES

Page 1: ...ded could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe prac...

Page 2: ...he system for 10 hours Monitor the suction drier pressure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suc...

Page 3: ...ant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rub ber insulation Armaflex or equivalent Liquid lines that w...

Page 4: ...out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an additional 1...

Page 5: ...plate Total system charge is determined as follows 1 Determine outdoor unit charge from tabular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge using...

Page 6: ...F Pressure PSIG Temp F 80 48 110 64 140 78 170 91 200 101 230 111 82 49 112 65 142 79 172 91 202 102 232 112 84 50 114 66 144 80 174 92 204 103 234 112 86 51 116 67 146 81 176 93 206 103 236 113 88 5...

Page 7: ...seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat FIGURE 7 Typical Air Handler Thermostat Wiring FIGURE 8 Typi...

Page 8: ...er furnace or air handler will be operating dis charging cool air from the ducts Coils or other parts in the air cir cuit should be cleaned as often as necessary to keep the unit clean Use a brush vac...