036-21573-001 Rev. A (0304)
8
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
AM018M1021
INDOOR COIL MODEL NO.
G1NA024S17G
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
500
650
800
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
20.6
19.1
17.8
20.7
19.5
18.3
20.9
19.9
18.8
S.C.
11.3
11.1
10.8
12.0
12.0
12.1
12.7
13.0
13.4
K.W
1.59
1.58
1.56
1.66
1.64
1.63
1.72
1.71
1.70
85
T.C.
19.7
18.2
16.5
19.9
18.6
17.1
20.1
19.0
17.7
S.C.
11.3
10.9
10.4
12.3
12.2
11.8
13.4
13.5
13.2
K.W
1.70
1.68
1.66
1.77
1.75
1.73
1.84
1.82
1.80
95
T.C.
18.9
17.3
15.2
19.1
17.7
15.9
19.4
18.0
16.5
S.C.
11.3
10.8
9.9
12.6
12.4
11.5
14.0
13.9
13.0
K.W
1.81
1.79
1.76
1.88
1.86
1.83
1.95
1.92
1.90
105
T.C.
17.4
15.5
13.5
17.7
16.0
14.1
18.1
16.6
14.7
S.C.
10.7
10.0
9.2
12.4
11.7
10.8
14.0
13.4
12.3
K.W
1.92
1.88
1.84
1.99
1.95
1.91
2.06
2.02
1.98
115
T.C.
15.9
13.7
11.8
16.4
14.4
12.4
16.9
15.1
12.9
S.C.
10.2
9.2
8.5
12.1
11.1
10.1
14.0
12.9
11.6
K.W
2.02
1.96
1.92
2.09
2.04
1.99
2.17
2.12
2.06
125
T.C.
14.4
11.9
10.1
15.0
12.8
10.6
15.7
13.7
11.1
S.C.
9.7
8.4
7.8
11.8
10.4
9.4
14.0
12.4
10.9
K.W
2.12
2.05
1.99
2.20
2.13
2.07
2.28
2.22
2.15
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB0806
G2FD024(S,H)17
1.05
1.08
1.05
F2RP/F2FP018
0.98
1.02
1.00
F2RP/F2FP024
1.05
1.08
1.05
G1FA024S14,17
1.03
1.07
1.04
G1HD024
1.05
1.09
1.05
G1NA024S17G
1.00
1.00
1.00
G1UA024S14,17
1.03
1.07
1.04
G2FD024(S,H)14,17
1.05
1.08
1.05