3
Additional R-22 Charge / Orifice Size for Various Matched Systems
ADDITIONAL R-22 CHARGE / ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS
Outdoor Unit
AM012M1021
AM018M1021
AM024M1021
AM030M1021
Unit Orifice (s)
1
47
51
59
63
Factory R-22 Charge, lbs-oz
3 - 2
3 - 1
3 - 4
3 - 9
Indoor Coil
Coil Orifice
2
System Orifice - Additional Charge, Oz
G2FD024(S,H)14/17
61
47 + 8
51 + 7
59 + 2
—
G2FD030(S,H)17
65
—
—
—
63 + 2
G2FD035(S,H)14
65
—
—
—
63 + 1
G1HD024
59
47 + 7
53 + 6
59 + 3
—
G1HD036
69
—
—
—
63 + 7
G1FA/G1UA024S14/17
59
47 + 6
51 + 5
59 + 0
—
G1FA/G1UA030S14
65
—
—
—
63 + 3
G1FA/G1UA036S14
73
—
—
59 + 6
63 + 3
G1FA/G1UA03617/21
73
—
—
—
63 + 1
G1NA024S17G
51
47 + 0
51 + 0
—
—
G1NA030S17H
57
—
—
59 + 2
—
G1NA030S17K
63
—
—
—
63 + 2
G1NA030S21B
57
—
—
59 + 2
—
G1NA030S21M
63
—
—
—
63 + 2
G1NF024SOF
63
—
—
59 + 2
63 + 0
F2RP/F2FP018
53
47 + 3
51 + 1
—
—
F2RP/F2FP024
61
—
51 + 7
59 + 2
—
F2RP/F2FP030
65
—
—
—
63 + 2
F2RP/F2FP036
75
—
—
—
63 + 8
MDD30BSD
57
—
—
59 + 2
—
MDD30MSD
63
—
—
—
63 + 2
FOOTNOTES:
1. These orifices are packed in the customer packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor, and 15 feet of inter-
connecting line tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Add charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
eva adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.