background image

036-21573-001 Rev. A (0304)

Unitary Products Group

7

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

AM012M1021

INDOOR COIL MODEL NO.

G1NA024S17G

CONDENSER 

ENTERING AIR 

TEMPERATURE

ID CFM

400

450

500

ID DB (°F)

85

80

70

85

80

70

85

80

70

ID WB (°F)

72

67

57

72

67

57

72

67

57

75

T.C.

15.4

14.6

13.8

15.4

14.7

14.0

15.5

14.8

14.2

S.C.

9.6

9.6

9.2

10.0

9.9

9.7

10.3

10.3

10.2

K.W

1.21

1.21

1.21

1.23

1.22

1.22

1.25

1.24

1.24

85

T.C.

15.2

14.2

13.1

15.3

14.4

13.3

15.4

14.6

13.6

S.C.

9.8

9.5

9.0

10.1

10.0

9.5

10.5

10.4

10.1

K.W

1.32

1.31

1.31

1.34

1.33

1.33

1.36

1.35

1.35

95

T.C.

15.1

13.8

12.4

15.2

14.1

12.7

15.3

14.4

13.0

S.C.

9.9

9.5

8.8

10.3

10.0

9.3

10.7

10.5

9.9

K.W

1.43

1.42

1.42

1.45

1.44

1.44

1.47

1.46

1.46

105

T.C.

14.2

13.0

11.6

14.3

13.2

11.9

14.5

13.4

12.1

S.C.

9.5

9.0

8.3

10.0

9.6

8.8

10.5

10.1

9.4

K.W

1.56

1.55

1.53

1.58

1.57

1.55

1.60

1.59

1.57

115

T.C.

13.3

12.1

10.9

13.5

12.2

11.1

13.6

12.4

11.2

S.C.

9.2

8.6

7.7

9.8

9.1

8.3

10.4

9.7

8.9

K.W

1.69

1.67

1.65

1.71

1.70

1.67

1.73

1.72

1.69

125

T.C.

12.5

11.3

10.2

12.6

11.3

10.3

12.8

11.3

10.4

S.C.

8.8

8.1

7.2

9.5

8.7

7.8

10.2

9.2

8.4

K.W

1.82

1.80

1.76

1.84

1.82

1.78

1.86

1.85

1.81

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

N1AHB0806

G2FD024(S,H)17

1.03

1.04

1.01

F2RP018

1.03

1.06

1.04

G1FA024S14,17

1.02

1.03

1.01

G1HD024

1.04

1.04

1.01

G1UA024S14,17

1.02

1.03

1.01

G2FD024(S,H)14,17

1.03

1.04

1.01

Summary of Contents for AM012M1021

Page 1: ...essors are internally protected against high pressure and tempera ture This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the comp...

Page 2: ...1 100 1 075 1 075 Nominal CFM 1 600 1 550 1 750 1 750 Coil Face Area Sq Ft 7 22 7 22 7 22 7 94 Rows Deep 1 1 1 1 Fins Inch 14 16 20 20 Liquid Line OD 3 8 3 8 3 8 3 8 Vapor Line OD 5 8 5 8 5 8 3 4 Uni...

Page 3: ...3 51 1 F2RP F2FP024 61 51 7 59 2 F2RP F2FP030 65 63 2 F2RP F2FP036 75 63 8 MDD30BSD 57 59 2 MDD30MSD 63 63 2 FOOTNOTES 1 These orifices are packed in the customer packet of each outdoor unit 2 These...

Page 4: ...18 6 13 4 10 00 9 50 AM024M1021 N1AHB0806 10 17 G2FD024 S H 17 850 23 4 16 8 10 00 9 15 AM030M1021 N1AHB1206 10 15 18 17 G2FD030 S H 17 1050 28 2 20 3 10 00 9 00 1 PH 10 SEER AC F2RP 4 5 AM012M1021 F2...

Page 5: ...20 14 17 G1UA024S14 17 850 23 0 16 6 10 00 9 05 14 G1UA036S14 850 23 8 17 2 10 00 9 25 14 17 G2FD024 S H 14 17 850 23 4 16 8 10 00 9 15 AM030M1021 925 1175 14 G1FA030S14 1050 28 2 20 2 10 00 8 95 14 G...

Page 6: ...TH PERMAGUM OR EQUIVALENT CONTROL ACCESS PANEL NOTE ALL OUTDOOR WIRING MUST BE WEATHERPROOF ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE NEC AND OR LOCAL CODES POWER WIRING 208 230...

Page 7: ...14 6 13 6 S C 9 8 9 5 9 0 10 1 10 0 9 5 10 5 10 4 10 1 K W 1 32 1 31 1 31 1 34 1 33 1 33 1 36 1 35 1 35 95 T C 15 1 13 8 12 4 15 2 14 1 12 7 15 3 14 4 13 0 S C 9 9 9 5 8 8 10 3 10 0 9 3 10 7 10 5 9 9...

Page 8: ...11 8 13 4 13 5 13 2 K W 1 70 1 68 1 66 1 77 1 75 1 73 1 84 1 82 1 80 95 T C 18 9 17 3 15 2 19 1 17 7 15 9 19 4 18 0 16 5 S C 11 3 10 8 9 9 12 6 12 4 11 5 14 0 13 9 13 0 K W 1 81 1 79 1 76 1 88 1 86 1...

Page 9: ...8 2 43 2 38 2 57 2 53 2 47 95 T C 25 1 22 8 21 0 25 5 23 6 21 5 25 9 24 4 21 9 S C 15 2 14 4 13 1 17 1 16 5 15 2 19 0 18 6 17 2 K W 2 53 2 46 2 39 2 63 2 57 2 50 2 72 2 68 2 60 105 T C 23 1 20 7 18 5...

Page 10: ...3 95 T C 29 9 27 7 25 3 30 6 28 4 26 0 31 2 29 0 26 7 S C 18 9 18 5 18 0 20 4 19 9 19 4 21 9 21 3 20 7 K W 3 14 3 06 2 98 3 24 3 16 3 09 3 35 3 27 3 20 105 T C 27 9 25 6 22 9 28 6 26 2 23 6 29 3 26 9...

Page 11: ...ION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE A...

Page 12: ...to change without notice Printed in U S A 036 21573 001 Rev A 0304 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: