036-21573-001 Rev. A (0304)
Unitary Products Group
5
NOTES:
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 1
5°
superheat and 1
5°
sub-cooling at condensing unit.
a. Increase capacity 1% for each
2°
increase in sub-cooling.
b. Decrease capacity 1% for each
2°
decrease in sub-cooling.
3. Sub-cooling in excess of 2
0°
may result in excessively high condensing temperature with air on condenser above 115°F.
Maximum recommended condensing temperature is 140°F.
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
UNIT MODEL
FURNACE
1
COIL
MODEL
COOLING
CFM RANGE
(MIN.-MAX.)
W
RATED CFM
NET MBH
SEER
W/O TXV
SEER + TXV
2
EER
TOTAL
SENS.
AM012M1021
250
650
14,17
G1FA024S14,17
450
14.4
10.3
10.00
-
9.95
-
G1HD024
450
14.6
10.4
10.00
-
10.00
17
G1NA024S17G
450
14.1
10.0
10.00
-
9.80
14,17
G1UA024S14,17
450
14.4
10.3
10.00
-
9.95
14,17
G2FD024(S,H)14,17
450
14.5
10.4
10.00
-
10.00
AM018M1021
575
725
14,17
G1FA024S14,17
650
18.3
13.3
10.00
-
9.40
-
G1HD024
650
18.5
13.5
10.00
-
9.50
17
G1NA024S17G
650
17.7
12.4
10.00
-
9.50
14,17
G1UA024S14,17
650
18.3
13.3
10.00
-
9.40
14,17
G2FD024(S,H)14,17
650
18.6
13.4
10.00
-
9.50
AM024M1021
750
950
14,17
G1FA024S14,17
850
23.0
16.6
10.00
-
9.05
14
G1FA036S14
850
23.8
17.2
10.00
-
9.25
-
G1HD024
850
23.6
17.0
10.00
-
9.25
17
G1NA030S17H
850
23.6
16.5
10.00
-
9.20
21
G1NA030S21B
850
23.6
16.5
10.00
-
9.20
14,17
G1UA024S14,17
850
23.0
16.6
10.00
-
9.05
14
G1UA036S14
850
23.8
17.2
10.00
-
9.25
14,17
G2FD024(S,H)14,17
850
23.4
16.8
10.00
-
9.15
AM030M1021
925
1175
14
G1FA030S14
1050
28.2
20.2
10.00
-
8.95
14
G1FA036S14
1050
28.2
20.2
10.00
-
8.95
17,21
G1FA036S17,21
1050
28.0
20.0
10.00
-
8.95
-
G1HD036
1050
28.4
20.2
10.00
-
9.00
17
G1NA030S17K
1050
28.4
19.9
10.00
-
9.00
21
G1NA030S21M
1050
28.4
19.9
10.00
-
9.00
14
G1UA030S14
1050
28.2
20.2
10.00
-
8.95
14
G1UA036S14
1050
28.2
20.2
10.00
-
8.95
17,21
G1UA036S17,21
1050
28.0
20.0
10.00
-
8.95
17
G2FD030(S,H)17
1050
28.2
20.3
10.00
-
9.00
14
G2FD035(S,H)14
1050
28.0
20.0
10.00
-
8.95
1. Refer to Quick Selection Chart for specific furnace match-up.
2. TXV = Use 1TV700 Series Kit.
COOLING PERFORMANCE
MODEL
SUCT. T/P @
COMPR.
AIR TEMP ON CONDENSER
MODEL
SUCT. T/P @
COMPR.
AIR TEMP ON CONDENSER
75°F
95°F
115°F
75°F
95°F
115°F
TEMP. PSIG MBH KW MBH KW MBH KW
TEMP. PSIG MBH KW MBH KW MBH KW
AM012M1021
35
61.5
13.1
1.01
11.6
1.20
10.1
1.40
AM024M1021
35
61.5
21.0
2.23
17.0
2.46
14.2
2.63
40
68.5
14.5
1.03
12.8
1.23
11.2
1.44
40
68.5
22.9
2.24
19.3
2.52
16.5
2.74
45
76.0
15.9
1.04
14.1
1.26
12.4
1.47
45
76.0
25.0
2.27
21.6
2.58
18.3
2.83
50
84.0
17.4
1.06
15.5
1.28
13.6
1.51
50
84.0
26.8
2.28
23.9
2.63
20.5
2.92
AM018M1021
35
61.5
16.2
1.66
13.1
1.84
11.0
1.96
AM030M1021
35
61.5
25.1
2.68
20.3
2.97
17.0
3.17
40
68.5
17.7
1.67
14.9
1.88
12.8
2.04
40
68.5
27.4
2.70
23.1
3.04
19.7
3.30
45
76.0
19.3
169
16.7
1.92
14.2
2.11
45
76.0
29.9
2.74
25.8
3.10
21.9
3.41
50
84.0
20.8
1.70
18.5
1.96
15.9
2.18
50
84.0
32.1
2.75
28.6
3.17
24.5
3.51