background image

271002-UUM-A-0407

Unitary Products Group

5

FURNACE MAINTENANCE SECTION

The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.

1.

The vent terminal screen (if applicable).

2.

The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.

3.

The furnace burners, ignitor and flame sensor.

FURNACE CLEANING SECTION

NOTE: 

The cleaning operations listed below must be performed only by

a qualified service agency.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box
cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

8.

Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

Lower Heat Exchanger Access

1.

Turn off the electrical power to the unit and turn off gas supply at
the shutoff valve.

2.

Remove the blower and burner compartment access doors. Dis-
connect the gas supply piping at the union to permit removal of the
entire burner and gas control assembly from the vestibule panel.
Use the wrench boss on the gas valve when removing or installing
this piping. See Figure 4.

3.

Unplug the igniter from the wire harness. Disconnect sensor and
rollout switch wires located on top of the air shield. Identify and
note the location of all leads for ease of reinstallation. Also discon-
nect the wires at the side rollout switches (upflow only) and the
gas valve wires.

4.

Remove the screws holding the burner assembly to the vestibule
panel and remove this assembly. Handle the assembly carefully
since it contains the igniter, which is fragile and easily broken. The
lower portion of the heat exchanger will now be exposed. To clean
the burner assembly, use a vacuum cleaner, or remove the burn-
ers as outlined in burner cleaning, and clean in hot water.

Upper Heat Exchanger Access

1.

Perform steps 1-4 above.

2.

Disconnect vent piping from the vent motor assembly at the top
panel on the furnace (upflow only). On downflow models, the vent
pipe is attached to the vent motor outlet. Remove this screw
before proceeding.

3.

Unplug the vent motor wires and ground wire. Remove the pres-
sure switch tubing at the tap on the vent motor housing.

NOTE: 

It is recommended that replacement gaskets be available

before removing vent motor.

4.

Remove six mounting screws that hold the vent motor to the
restrictor plate. The surface is gasketed and gasket can be reused
if it is carefully removed. It is necessary to remove this assembly to
gain access to the restrictor plate mounting holes. The assembly
may be vacuumed if cleaning is necessary. If any vent assembly
parts are damaged, replace with an entire new assembly (except
for gaskets).

5.

Remove the perimeter screws attaching the restrictor plate assem-
bly to the vestibule panel. The surface is also gasketed. The
assembly, including the flue baffle plate (rear) may be vacuumed
or cleaned with hot water if necessary.

6.

The upper portion of the heat exchanger is now accessible. With a
long flexible wire brush, clean inside each tube at both the top and
bottom. The brush must pass around the rear heat exchanger
tubes. Vacuum loose scale and dirt from each tube.

7.

Clean - Replace all components in reverse order. Re-gasket all
surfaces which required a gasket. Reconnect all wiring. Reattach
vent pipe and gas supply lines before restoring service to furnace.
Restore electrical power, check gas supply piping for leaks, and
then verify furnace operation.

SEQUENCE OF OPERATION

The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.

1.

Call for 1st stage only

• On a call for 1st stage heat, the thermostat closes a circuit

between R and W1.

• The Microprocessor in the Furnace Control runs a ‘Self Check’.
• The Control checks the Primary Limit, Auxiliary Limit, and Roll-

out Switches for closed contacts.

• The Control checks that the Low Fire Pressure Switch (1LP) is

open.

• The Inducer Motor is energized on high speed, closing the con-

tacts of 1LP.

• The Control checks that 1LP is closed.
• The Igniter is energized for 17 seconds.
• The Gas Valve is energized on 1st Stage (Low Fire).
• Flame Rectification is recognized within 7 seconds.
• The Inducer is switched to low speed.
• 30 seconds after flame is proven, the ‘Heat Low’ relay is ener-

gized providing 120 Volts AC to the Blower Motor.

• At the same time, the EAC and Hum relays are energized, pro-

viding 120 Volts AC to the EAC Hot and Hum terminals.

2.

Call for 2nd Stage after 1st Stage is operating

• A call for 2nd Stage can be made by a 2-Stage thermostat, or by

the W2 delay timer on the furnace control.

• The Inducer Motor is shifted to high speed by the control, closing

the contacts of 2LP (The High Fire Pressure Switch.).

• The Control checks that 2LP is closed.
• The Gas Valve is energized on 2nd Stage (High Fire).
• The Control simultaneously de-energizes the Heat Low relay

and energizes the Heat High relay, providing 120 Volts AC to a
different speed of the Blower Motor.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.

Summary of Contents for AHV8 UH Series

Page 1: ...t or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop erty damage Do not store or use gasoline or other f...

Page 2: ...he ducts ter minate outside the space containing the furnace 4 Examine the furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure...

Page 3: ...s 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control switch to the OFF position...

Page 4: ...with cleanable filter s at this time Cleanable filter s may be cleaned as described in the manufacturer instructions or as described below and then re installed To replace the filter after cleaning y...

Page 5: ...et Remove this screw before proceeding 3 Unplug the vent motor wires and ground wire Remove the pres sure switch tubing at the tap on the vent motor housing NOTE It is recommended that replacement gas...

Page 6: ...e Y2 circuit for high cooling CONTROL BOARD Variable speed motors will adjust the motor speed in order to maintain the indoor fan CFM The control board is used to control the blower speed thus the CFM...

Page 7: ...higher speed will take 30 seconds and any ramp down to a lower speed or off will take 60 seconds Tap D is the normal profile best suited for most of the country where neither excessive humidity nor ex...

Page 8: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the f...

Page 9: ...DUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC TRIAL...

Page 10: ...271002 UUM A 0407 10 Unitary Products Group SECTION III REPLACEMENT PARTS LIST 39 29 38 43 21 25 35 31 27 23 22 20 24 30 44 26 53 42 28 18 2 4 11 6 9 5 17 16 12 7 8 3 12A 7 36 25 37 12 20 11...

Page 11: ...ITER 22 DECK BLOWER Rear 23 DECK FRONT 24 HEAT EXCHANGER ASS Y 25 MANIFOLD GAS 26 PANEL UPPER ACCESS Burner Magnet FABRICATED PARTS Continued 27 PAN BASE 28 PANEL BLOWER ACCESS Magnet 29 PANEL TOP 30...

Page 12: ...1BR0121 BOTTOM RETURN FILTER KIT 1 FILTER 21 CABINETS 1BR0221 BOTTOM RETURN FILTER KIT 1 4 FILTER 21 CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1 FILTER 24 1 2 CABINETS 1BR0224 BOTTOM RETURN FILTER KIT...

Page 13: ...271002 UUM A 0407 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 14: ...271002 UUM A 0407 14 Unitary Products Group NOTES...

Page 15: ...271002 UUM A 0407 Unitary Products Group 15 NOTES...

Page 16: ...to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing...

Reviews: