background image

271002-UUM-A-0407

6

Unitary Products Group

3.

2nd Stage is satisfied, 1st Stage still calling.

• If a Single Stage Thermostat is used, the Furnace will stay on

High Fire until the thermostat is satisfied.

• When the circuit between R and W2 is opened, the Control

switches the Inducer Motor to low speed, causing the contacts of
2LP to open.

• When 2LP opens, 2nd Stage of the Gas Valve is de-energized.
• 30 seconds later, the Control switches the Blower from Heat

High to Heat Low.

4.

1st Stage Satisfied

• The Thermostat opens the circuit between R and W1
• Immediately the Gas Valve is de-energized and Flame Rectifica-

tion is lost.

• The Inducer Motor is de-energized after a 15 second Post Purge

and the Hum terminal is de-energized.

• The ‘Fan Off Delay’ circuit is initiated. The Delay time can be

field set at 60, 90, 120, or 180 seconds. It comes from the fac-
tory set at 60 seconds.

• The Heat Low terminal is de-energized; stopping the Blower and

the EAC terminal is de-energized.

5.

1st and 2nd Stage called simultaneously

• The 1st stage call is processed as described in paragraph 1

above.

• Once Flame Rectification is established, 2nd Stage is entered

immediately as described in paragraph 2 above.

6.

1st and 2nd Stage satisfied simultaneously

• Both stages of the Gas Valve are de-energized.
• Flame Rectification is lost.
• The Inducer and Hum relays are de-energized after a 15-second

post purge.

• 30 seconds later the Control shifts the Blower from Heat High to

Heat Low.

• After the Blower-Off Delay Circuit is satisfied, the Blower and

EAC are de-energized.

7.

Manual Fan Operation

• With the thermostat in the Fan On position, a circuit is completed

between R and G of the Control.

• The Heat Low and EAC relays are energized by the Control.

8.

Call for Cooling

• The thermostat closes two circuits R to Y/Y2 and R to G. Since

the Outdoor Unit is connected to Y and C at the Control, it is
energized.

• The Cool and EAC relays are energized by the Control.
• A Blower-Off Delay Timing Circuit is energized by the call on Y.

9.

Cooling call satisfied

• The thermostat opens the R to Y/Y2 and R to G circuits.
• The Outdoor Unit is de-energized.
• The 60-second, Blower-Off Delay, timing circuit is initiated.
• After 60 seconds, the Cool and EAC relays are de-energized.

10. Two-stage cooling. This furnace is equipped to handle a two-stage

AC unit. 

The wall thermostat will energize the Y1 circuit for low cooling
and the Y2 circuit for high cooling.

CONTROL BOARD

Variable speed motors will adjust the motor speed in order to maintain
the indoor fan CFM. The control board is used to control the blower
speed thus the CFM when the unit is operating in the heating or cooling
modes. The blower CFM for cooling can be modified by changing the
jumper pin position on the taps selection marked COOL and ADJ.

The blower CFM for heating can be modified by changing the jumper
pin position on the taps selection marked HEAT. The taps selection pins
have been preset at the factory to provide the maximum CFM. “Air Flow
Data” table in the installation manual list the recommended jumper pin
settings.

If a lesser CFM is required for a specific HVAC system the taps selec-
tion pins can be moved to the "B", "C", or "D" positions. Pin "A" will pro-
vide the highest CFM and "D" will provide the lowest CFM. The taps
selection marked DELAY are used for cooling only. The recommended
settings for these jumper pins are listed in Delay taps selection.

HEATING AIRFLOW

The heating airflow has been preset at the factory to provide maximum
CFM. If a lesser CFM is required for a specific HVAC system the
“JUMPER” on the HEAT selection pins on the CFM-Timer Board may
be moved to 

tap “B”, “C”, or “D”.

HEAT Taps Selection on the control board

Pin Position A

: will provide the highest CFM.

Pin Position B and C: 

are the medium and medium low CFM settings.

Pin Position D:

 will provide the lowest CFM.

Refer to “Air Flow Data” table in the installation manual for the
proper “HEAT” Taps Selection for the model furnace you are
installing.

NOTE: 

When changing jumper positions, make sure that the jumper is

pushed all the way on the pins. If the jumper is not making good contact
or is left off completely, the blower will operate as if the jumper were in
the “

A” position

.

NOTE: 

Power to the blower must be removed for at least 4 seconds

after a heat or cool tap selection change, in order for the motor to recog-
nize an adjustment. The fixed blower on delay and adjustable blower-off
delay will function as described in the “OPERATION AND MAINTE-
NANCE" Section in the Users Information Manual.

ADJUSTMENT OF FAN CONTROL SETTINGS

Heating Indoor Fan Off Delay

Changing the blower delay jumper on the Furnace Control Board can
change the indoor fan “OFF” time delay. Refer to Figure 7 for the jumper
settings to obtain the desired fan OFF delay. The blower off delay must
be long enough to adequately cool the furnace, but not so long that cold
air is blown into the living space.

The blower on delay is fixed at 30 seconds and cannot be adjusted.

Summary of Contents for AHV8 UH Series

Page 1: ...t or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop erty damage Do not store or use gasoline or other f...

Page 2: ...he ducts ter minate outside the space containing the furnace 4 Examine the furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure...

Page 3: ...s 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control switch to the OFF position...

Page 4: ...with cleanable filter s at this time Cleanable filter s may be cleaned as described in the manufacturer instructions or as described below and then re installed To replace the filter after cleaning y...

Page 5: ...et Remove this screw before proceeding 3 Unplug the vent motor wires and ground wire Remove the pres sure switch tubing at the tap on the vent motor housing NOTE It is recommended that replacement gas...

Page 6: ...e Y2 circuit for high cooling CONTROL BOARD Variable speed motors will adjust the motor speed in order to maintain the indoor fan CFM The control board is used to control the blower speed thus the CFM...

Page 7: ...higher speed will take 30 seconds and any ramp down to a lower speed or off will take 60 seconds Tap D is the normal profile best suited for most of the country where neither excessive humidity nor ex...

Page 8: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the f...

Page 9: ...DUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC TRIAL...

Page 10: ...271002 UUM A 0407 10 Unitary Products Group SECTION III REPLACEMENT PARTS LIST 39 29 38 43 21 25 35 31 27 23 22 20 24 30 44 26 53 42 28 18 2 4 11 6 9 5 17 16 12 7 8 3 12A 7 36 25 37 12 20 11...

Page 11: ...ITER 22 DECK BLOWER Rear 23 DECK FRONT 24 HEAT EXCHANGER ASS Y 25 MANIFOLD GAS 26 PANEL UPPER ACCESS Burner Magnet FABRICATED PARTS Continued 27 PAN BASE 28 PANEL BLOWER ACCESS Magnet 29 PANEL TOP 30...

Page 12: ...1BR0121 BOTTOM RETURN FILTER KIT 1 FILTER 21 CABINETS 1BR0221 BOTTOM RETURN FILTER KIT 1 4 FILTER 21 CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1 FILTER 24 1 2 CABINETS 1BR0224 BOTTOM RETURN FILTER KIT...

Page 13: ...271002 UUM A 0407 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 14: ...271002 UUM A 0407 14 Unitary Products Group NOTES...

Page 15: ...271002 UUM A 0407 Unitary Products Group 15 NOTES...

Page 16: ...to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing...

Reviews: