rails shall be removable, when required, to lower unit height. 
Filters shall be furnished and be accessible through a 
removable access door, sealed airtight. Units vertical discharge 
and return duct configuration shall be designed to fit between 
standard 24” O.C. beams without modification to building 
structure, duct work and base unit. Condensate pan shall be 
internally sloped and conform to ASHRAE 62-89 self-draining 
standards, with 3/4” NPTI copper, ridged mount connection.

Indoor (Evaporator) Fan Assembly

Fan shall be direct drive design. Fan wheel shall be double-inlet 
type with forward-curved blades, dynamically balanced to 
operate smoothly throughout the entire range of operation. 
Airflow design shall be constant air volume. Bearings shall be 
sealed and permanently lubricated for longer life and no 
maintenance. Fan assembly shall be “Slip Track” (slide-out) 
design for easy removal and cleaning.

Outdoor (Condenser) Fan Assembly

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be statically 
balanced for smooth operation. The outdoor fan motor shall be 
totally enclosed with permanently lubricated bearings and 
internally protected against overload conditions.

Refrigerant Components

Compressors:

a. Shall be fully hermetic type, direct drive, internally 

protected with internal high-pressure relief and over 
temperature protection. The hermetic motor shall be 
suction gas cooled and have a voltage range of +/- 10% 
of the unit nameplate voltage.

b. Shall have internal isolation and sound muffling to 

minimize vibration and noise, and be externally isolated 
on a dedicated, independent mounting.

Coils:

a. Evaporator and condenser coils shall have aluminum 

plate fins mechanically bonded to seamless internally 
enhanced copper tubes with all joints brazed.

b. Evaporator coil shall be of the direct expansion, blow 

through design, while condenser coil shall be draw 
through design.

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a. Shall include independent fixed orifice expansion 

devices.

b. Shall include filter/strainer to eliminate any foreign 

matter.

Gas Heating Section (If Equipped)

Heat exchanger and exhaust system shall be constructed of 
aluminized steel and shall be designed with induced draft 
combustion with post purge logic and redundant main gas 
valve. The heat exchanger shall be of the tubular type, 
constructed of T1-40 aluminized steel for corrosion resistance 
and allowing minimum mixed air entering temperature of 40 ºF. 
Burners shall be of the in-shot type, constructed of aluminum-
coated steel. All gas piping shall enter the unit cabinet at a 
single location through either the side or bottom, without any 
field modifications. An integrated control board shall provide 
timed control of evaporator fan functioning and burner ignition. 
Heating section shall be provided with the following minimum 
protection:

a. Primary and auxiliary high-temperature limit switches.

b. Induced draft pressure sensor.

c. Flame roll out switch (manual reset).

d. Flame proving controls.

Summary of Contents for AFFINITY R-410A DNX

Page 1: ...nstallation Only utility and duct connections are required at the point of installation The single or two stage gas fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignit...

Page 2: ...ube Aluminum Fin Evaporator Coil Highly Efficient Enhanced Copper Tube Aluminum Fin Condenser Coil Decorative Protective Coil Guard High Efficiency Compressor Rigidly Mounted Pilot Assembly High Grade...

Page 3: ...design allows maximum field flexibility and minimum inventory Condensate Pan A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate L...

Page 4: ...the unit will lock out preventing any further operation until reset or problem is corrected Exclusive Coil Design Grooved copper tubes and enhanced aluminum fin construction improves heat transfer fo...

Page 5: ...ronic and electro mechanical thermostats All units can operate with single stage heat single stage cool thermostats with or without the economizer Low Ambient Kit Kit provides necessary hardware to co...

Page 6: ...emperature protection The hermetic motor shall be suction gas cooled and have a voltage range of 10 of the unit nameplate voltage b Shall have internal isolation and sound muffling to minimize vibrati...

Page 7: ...8 49 1 8 Width 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 Height 33 1 2 33 1 2 33 1 2 41 1 2 41 1 2 41 1 2 OPERATING WT lbs 360 395 395 470 470 540 COMPRESSORS Type Scroll 1 spd Scroll 1 spd Scroll 1...

Page 8: ...4 Height 33 1 2 33 1 2 33 1 2 41 1 2 41 1 2 41 1 2 OPERATING WT lbs 360 395 395 470 470 540 COMPRESSORS Type Scroll 1 spd Scroll 1 spd Scroll 1 spd Scroll 1 spd Scroll 1 spd Scroll 1 spd Quantity 1 1...

Page 9: ...60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 DNY DNX 208 230 1 60 187 252 115 208 230 3 60 187 252 115 460 3 60 432 504 115 042 3 5 DNZ 208 230 1 60 187 252 125 208 230 3 60 187 252 1...

Page 10: ...9 1 8 23 6 19 4 15 2 11 0 26 5 2 0 22 9 18 7 14 5 10 3 67 26 0 1 8 26 0 23 2 19 0 14 8 10 6 24 7 1 9 24 7 22 7 18 5 14 3 10 1 62 23 9 1 8 23 9 23 9 23 9 19 7 15 5 11 3 22 7 1 9 22 7 22 7 22 7 18 5 14...

Page 11: ...6 6 16 6 13 1 9 6 6 1 14 4 2 7 14 4 14 4 14 4 11 4 7 7 4 1 57 17 4 2 5 17 4 17 4 17 4 13 9 10 4 6 9 16 0 2 7 16 0 16 0 15 9 12 4 8 8 5 2 900 72 21 4 2 6 19 5 15 7 11 9 8 0 19 8 2 9 18 9 15 1 11 2 7 4...

Page 12: ...2 5 28 2 23 4 18 6 13 8 67 34 1 2 2 34 1 30 3 25 4 20 5 15 6 32 3 2 5 32 3 29 8 25 0 20 2 15 4 62 31 8 2 2 31 8 31 8 31 8 26 9 22 1 17 2 29 8 2 5 29 8 29 8 29 8 25 0 20 2 15 4 57 31 8 2 2 31 8 31 8 3...

Page 13: ...23 2 23 2 23 2 19 4 15 6 11 8 21 2 3 6 21 2 21 2 21 2 17 7 13 8 10 0 57 23 6 3 2 23 6 23 6 23 6 19 8 16 0 12 2 21 6 3 6 21 6 21 6 21 6 18 0 14 0 10 2 1125 72 27 5 3 4 24 6 20 2 15 8 11 5 25 2 3 7 24 0...

Page 14: ...3 2 34 0 28 3 22 5 16 8 67 40 6 2 8 40 6 37 6 31 7 25 9 20 0 38 4 3 2 38 4 36 0 30 2 24 5 18 7 62 36 9 2 8 36 9 36 9 36 9 31 1 25 2 19 3 35 2 3 2 35 2 35 2 35 2 29 4 23 7 17 9 57 38 0 2 7 38 0 38 0 38...

Page 15: ...3 9 28 4 28 4 28 1 23 6 19 0 14 5 26 2 4 2 26 2 26 2 26 2 21 9 17 2 12 6 57 28 8 3 9 28 8 28 8 28 8 24 2 19 7 15 1 26 6 4 2 26 6 26 6 26 6 22 3 17 5 12 9 1350 72 34 5 4 0 30 4 25 1 19 9 14 6 32 4 4 3...

Page 16: ...3 5 39 5 32 8 26 1 19 4 67 46 5 3 2 46 5 43 7 36 3 29 4 22 6 44 4 3 5 44 4 43 0 36 3 29 6 22 9 62 43 4 3 2 43 4 43 4 43 4 36 5 29 7 22 8 41 3 3 5 41 3 41 3 41 3 34 6 27 9 21 2 57 42 7 3 1 42 7 42 7 42...

Page 17: ...4 1 33 1 33 1 33 0 28 5 23 9 19 4 30 4 4 4 30 4 30 4 30 3 25 9 21 2 16 6 57 33 4 4 2 33 4 33 4 33 3 28 8 24 2 19 7 30 7 4 6 30 7 30 7 30 7 26 4 21 5 17 0 1475 72 39 0 4 4 33 9 28 2 22 5 16 7 36 0 4 8...

Page 18: ...4 2 45 6 38 0 30 3 22 7 67 55 2 3 8 55 2 49 4 41 9 34 3 26 8 51 6 4 1 51 6 48 0 40 4 32 8 25 1 62 50 7 3 7 50 7 50 7 50 7 43 2 35 7 28 2 46 9 4 2 46 9 46 9 46 9 39 3 31 6 24 0 57 49 1 3 5 49 1 49 1 49...

Page 19: ...5 0 38 0 38 0 37 6 30 9 24 1 17 4 35 8 5 4 35 8 35 8 35 6 28 9 22 0 15 2 57 39 0 4 9 39 0 39 0 37 1 30 3 23 6 16 8 37 1 5 1 37 1 37 1 35 4 28 7 21 8 15 0 1750 72 43 8 5 2 40 6 33 2 25 9 18 5 39 7 5 7...

Page 20: ...5 1 53 6 45 2 36 8 28 3 67 67 7 4 6 67 7 59 3 51 0 42 7 34 4 62 5 5 1 62 5 56 9 48 5 40 0 31 6 62 62 0 4 3 62 0 62 0 62 0 53 7 45 4 37 1 57 5 4 9 57 5 57 5 57 5 49 0 40 6 32 2 57 60 5 4 2 60 5 60 5 60...

Page 21: ...6 0 44 9 44 9 44 6 37 1 29 6 22 1 41 4 6 5 41 4 41 4 41 4 34 6 26 9 19 3 57 45 0 6 0 45 0 45 0 44 3 36 8 29 4 21 9 41 7 6 6 41 7 41 7 41 2 33 8 26 0 18 3 1925 72 53 1 6 5 46 0 37 8 29 7 21 6 48 4 7 1...

Page 22: ...atic Pressure Inch Water Gauge 0 2 0 4 0 6 0 8 1 0 SCFM W RPM SCFM W RPM SCFM W RPM SCFM W RPM SCFM W RPM 024 2 0 DNZ Low 1 719 115 752 617 130 858 Low Medium 2 781 137 789 691 155 891 Medium 3 902 18...

Page 23: ...atic Pressure Inch Water Gauge 0 2 0 4 0 6 0 8 1 0 SCFM W RPM SCFM W RPM SCFM W RPM SCFM W RPM SCFM W RPM 024 2 0 DNZ Low 1 719 115 752 617 130 858 Low Medium 2 781 137 789 691 155 891 Medium 3 902 18...

Page 24: ...00 0 06 0 02 0 16 1300 0 07 0 03 0 17 036 3 0 DNZ DNY DNX 700 0 01 0 00 0 04 800 0 02 0 01 0 06 900 0 03 0 01 0 08 1000 0 04 0 01 0 10 1100 0 05 0 01 0 13 1200 0 06 0 02 0 16 1300 0 07 0 03 0 17 1400...

Page 25: ...110 2220 D072 700 1350 1110 2220 DNX N065 685 1350 1080 2370 N090 685 1350 1070 1780 D090 685 1350 1070 1780 042 3 5 DNZ N065 1050 1750 1080 2370 N090 1050 1750 1070 1780 D090 1050 1750 1070 1780 048...

Page 26: ...ed at lower voltages Nominal Applied 240 208 0 75 230 0 92 480 460 0 92 600 575 0 92 Outdoor Sound Power Levels Size Tons Model Sound Rating1 dB A 1 Rated in accordance with ARI 270 standard Octave Ba...

Page 27: ...each OD Fan Motors each Supply Blower Motor MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker siz...

Page 28: ...333491 YTG B 0807 Unitary Products Group 43 Typical DNX DNY DNZ024 060 Wiring Diagrams Typical DNZ024 060 Cooling Unit with Single Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 29: ...333491 YTG B 0807 44 Unitary Products Group Typical DNZ024 060 Cooling Unit with Two Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 30: ...333491 YTG B 0807 Unitary Products Group 49 Typical DNZ030 060 Cooling Unit with Single Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 31: ...333491 YTG B 0807 50 Unitary Products Group Typical DNZ030 060 Cooling Unit with Two Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 32: ...333491 YTG B 0807 Unitary Products Group 55 Typical DNZ030 060 Cooling Unit with Single Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 33: ...333491 YTG B 0807 56 Unitary Products Group Typical DNZ030 060 Cooling Unit with Two Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 34: ...5 400 20 24 5 116 84 84 117 DNX 445 440 20 24 5 127 93 93 127 030 2 5 DNZ 395 390 24 24 75 98 99 97 96 036 3 0 DNZ 400 395 24 25 100 101 98 96 DNY 445 440 20 24 25 126 91 93 129 DNX 485 480 20 24 136...

Page 35: ...ance in Top3 3 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 36 Right 12 Front 36 Left 24 Rear 0 Bottom4 4 Units may be installed...

Page 36: ...ions Front and Bottom Unit Dimensions Back and Bottom 5217 6 6833 12 287 137 211 7 21 2 92 7 211 12 287 21 16 7 5 1 137 92 7 211 12 287 2 92 7 211 12 287 92 7 211 12 287 6 5 7851 5 23 1 1 27720 5 7851...

Page 37: ...on Ground Installation Gas Model Shown 522 85 167 7 21 5 5 8 7 522 85 167 7 21 27720 8 7 6 21 5281 167 7 21 MANUAL GAS SHUT OFF VALVE TO GAS SUPPLY LINE FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REA...

Page 38: ...Gas Model Shown Unit Accessory Dimensions Roof Curb1 1 8 Roof Curb also available 0 18 6 6 87 2 9 9 6833 6 211 7 6 7 02817 21 81 7 72 32 5 6833 72 6 6833 1 21752 5 1 72 1 225 7 50267 7 5 7851 5 8 7 68...

Page 39: ...G B 0807 66 Unitary Products Group Roof Curb Cross Section 81 7 6 5 2817 5 6 1 17 675 3 168 7 21 1 522 1 0 7 5 522 1 522 1 0 7 5 168 7 21 85 5 0 0 1 29 1 6 522 22 1 5 81 7 6 6 7 1 25 85 5 0 1 8 7 6833...

Reviews: