background image

036-21528-007-A-1205                                                                                                                                                                                                                               

Unitary Products Group

19

TABLE 19: APPLICATION DATA

MODEL

BHP

024

030

036

042

048

060

MINIMUM AIR FLOW

(CFM)

COOLING

800

1000

1050

1300

1500

1500

HEATING

800

1000

1050

1400

1400

1500

MAXIMUM AIR FLOW

(CFM)

COOLING

900

1125

1200

1400

1600

2050

HEATING

900

1125

1200

1500

1600

2050

MINIMUM OPERATING TEMPERATURE IN COOLING MODE

(AMBIENT, 

°

F)

45

45

45

45

45

45

MIMINIM MIXED AIR IN COOLING MODE

(RETURN AIR, DB 

°

F/WB 

°

F)

68 / 57

68 / 57

68 / 57

68 / 57

68 / 57

68 / 57

MINIMUM MIXED AIR IN HEATING MODE

(RETURN AIR, 

°

F)

55

55

55

55

55

55

  

FIGURE 3 - CENTER OF GRAVITY AND WEIGHTS

49-1/8

26

23-1/2

47-1/4

A

B

C

D

FRONT

OF

UNIT

CENTER OF GRAVITY

B1HP

UNIT

SIZE

SHIPPING

WEIGHT

OPERATING

WEIGHT

CORNER WEIGHTS

A

B

C

D

024

356

351

97

93

81

84

030

353

348

96

93

81

84

036

388

383

106

102

89

92

042

440

435

120

115

101

104

048

485

480

132

127

111

115

060

495

490

135

130

113

117

FIGURE 4 - UNIT CLEARANCES

CLEARANCES

NOTE: FOR UNITS APPLIED WITH A ROOF CURB, THE 

MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 
INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF 
CURB MATERIAL AND THE SUPPLY DUCT.

UNIT CLEARANCES

(MINIMUM)

Front

12”

Back

0”

Left Side (Filter Access)

24”

Right Side

24”

Below Unit

1

1.

Units may be installed on combustible floors made from 
wood or class A, B or C roof covering.

0”

Above Unit

2

2.

Units must be installed outdoors. Overhanging structures 
or shrubs should not obstruct outdoor air discharge outlet.

36” (For Condenser

Air Discharge)

              

               

                

          

           

              

            

     

       

   

Summary of Contents for AFFINITY BHP024

Page 1: ...the installer can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...e designed for single point and dual con nection TABLE OF CONTENTS Description 1 Standard Features Benefits 1 Field installed Accessories 3 Unit Cut Away 5 Ratings 5 Physical Data 5 Cooling Capacities...

Page 5: ...E PHASE THREE PHASE 024 24 4 13 0 11 3 7 7 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 7 77 28 2 3 40 16 5 2 20 5 0 7 5 10 0 15 0 10 0 15 0 036 35 0 13 0 11 3 7 7 77 32 0 3 30 18 9 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...WER INPUT kW 5 64 5 52 5 37 5 28 6 17 6 04 5 88 5 77 Sensible Capacity MBH 1 Entering Dry Bulb F 86 36 7 45 7 46 8 47 2 41 9 49 9 46 3 46 7 83 32 0 41 1 46 8 47 2 35 9 45 9 46 3 46 7 80 27 3 36 4 46 7...

Page 12: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 10 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TE...

Page 13: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 12 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 14: ...66 3 793 4 020 4 247 4 474 80 MBH 13 394 16 579 20 504 25 342 31 304 38 653 47 709 58 871 KW 3 227 3 453 3 680 3 907 4 134 4 361 4 588 4 815 1 These capacities are net capacities the indoor motor heat...

Page 15: ...1 412 494 577 B1HP042 Cooling TB2 A Heating TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B Heating TB2 B 1400 CFM 393 466 544 642 734 B1HP048 Heating TB2 A 1400 CFM 377 427 504 597 683 B1HP0...

Page 16: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 17: ...7 31 0 6 6 8 12 7 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 7 3 25 8 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 7 3 16 1 20 20 0...

Page 18: ...48 7 45 50 45 50 2NH04501525 11 3 15 0 31 3 36 1 47 7 63 7 60 70 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 7 5 10 0 20 8 24 1 48 7 52 7 60 60 60 60 2NH04501525 11 3 15 0 31 3 36 1 76 7 67 8...

Page 19: ...T OF UNIT CENTER OF GRAVITY B1HP UNIT SIZE SHIPPING WEIGHT OPERATING WEIGHT CORNER WEIGHTS A B C D 024 356 351 97 93 81 84 030 353 348 96 93 81 84 036 388 383 106 102 89 92 042 440 435 120 115 101 104...

Page 20: ...7 A 1205 20 Unitary Products Group FIGURE 5 UNIT DIMENSIONS 5217 5217 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 29 5 81 7 6...

Page 21: ...036 21528 007 A 1205 Unitary Products Group 21 FIGURE 6 TYPICAL APPLICATIONS...

Page 22: ...036 21528 007 A 1205 22 Unitary Products Group FIGURE 7 ROOF CURB DIMENSIONS...

Page 23: ...036 21528 007 A 1205 Unitary Products Group 23 FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 24: ...036 21528 007 A 1205 24 Unitary Products Group FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 25: ...036 21528 007 A 1205 Unitary Products Group 25 FIGURE 10 TYPICAL WIRING DIAGRAM 460 575 3 60 POWER SUPPLY...

Page 26: ...be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height 8...

Page 27: ...ing the normal system operation pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for r...

Page 28: ...Printed in U S A 036 21528 007 A 1205 Copyright by Unitary Products Group 2005 All rights reserved Supersedes 036 21528 006 A 1005 Unitary 5005 Norman Products York OK Group Drive 73069 ISO 9001 Cert...

Reviews: