036-21528-007-A-1205

12

Unitary Products Group

TABLE 9: HEATING CAPACITIES - 2 TON (BHP024)

CFM

RETURN

AIR °F

CAP

1

& KW

OUTDOOR AIR TEMPERATURE, °F (72% RH)

-10

0

10

20

30

40

50

60

600

55

MBH

10.216

11.748

13.601

15.843

18.554

21.834

25.801

30.601

KW

1.214

1.307

1.401

1.494

1.588

1.681

1.775

1.868

70

MBH

7.317

8.849

10.702

12.944

15.655

18.935

22.902

27.702

KW

1.363

1.456

1.550

1.643

1.737

1.830

1.924

2.017

80

MBH

7.205

8.737

10.590

12.832

15.543

18.823

22.790

27.590

KW

1.423

1.516

1.610

1.703

1.797

1.890

1.984

2.077

800

55

MBH

10.206

11.738

13.591

15.833

18.544

21.824

25.791

30.591

KW

1.227

1.320

1.414

1.507

1.601

1.694

1.788

1.881

70

MBH

7.307

8.839

10.692

12.934

15.645

18.925

22.892

27.692

KW

1.376

1.469

1.563

1.656

1.750

1.843

1.937

2.030

80

MBH

7.195

8.727

10.580

12.822

15.533

18.813

22.780

27.580

KW

1.436

1.529

1.623

1.716

1.810

1.903

1.997

2.090

1000

55

MBH

11.377

12.909

14.762

17.004

19.715

22.995

26.962

31.762

KW

1.339

1.432

1.526

1.619

1.713

1.806

1.900

1.993

70

MBH

8.478

10.010

11.863

14.105

16.816

20.096

24.063

28.863

KW

1.488

1.581

1.675

1.768

1.862

1.955

2.049

2.142

80

MBH

8.366

9.898

11.751

13.993

16.704

19.984

23.951

28.751

KW

1.548

1.641

1.735

1.828

1.922

2.015

2.109

2.202

1.

These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have 
been added.

TABLE 10: HEATING CAPACITIES - 2-1/2 TON (BHP030)

CFM

RETURN

AIR °F

CAP

1

& KW

OUTDOOR AIR TEMPERATURE, °F (72% RH)

-10

0

10

20

30

40

50

60

750

55

MBH

10.876

12.808

15.078

17.744

20.877

24.556

28.879

33.958

KW

1.847

1.917

1.987

2.057

2.127

2.198

2.268

2.338

70

MBH

10.046

11.978

14.248

16.914

20.047

23.726

28.049

33.128

KW

2.135

2.205

2.275

2.345

2.415

2.486

2.556

2.626

80

MBH

9.054

10.986

13.256

15.922

19.055

22.734

27.057

32.136

KW

2.377

2.447

2.517

2.587

2.657

2.728

2.798

2.868

1000

55

MBH

11.886

13.818

16.088

18.754

21.887

25.566

29.889

34.968

KW

1.731

1.801

1.871

1.941

2.011

2.082

2.152

2.222

70

MBH

11.056

12.988

15.258

17.924

21.057

24.736

29.059

34.138

KW

2.019

2.089

2.159

2.229

2.299

2.370

2.440

2.510

80

MBH

10.064

11.996

14.266

16.932

20.065

23.744

28.067

33.146

KW

2.261

2.331

2.401

2.471

2.541

2.612

2.682

2.752

1250

55

MBH

13.978

15.910

18.180

20.846

23.979

27.658

31.981

37.060

KW

1.881

1.951

2.021

2.091

2.161

2.232

2.302

2.372

70

MBH

13.148

15.080

17.350

20.016

23.149

26.828

31.151

36.230

KW

2.169

2.239

2.309

2.379

2.449

2.520

2.590

2.660

80

MBH

12.156

14.088

16.358

19.024

22.157

25.836

30.159

35.238

KW

2.411

2.481

2.551

2.621

2.691

2.762

2.832

2.902

1.

These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have 
been added.

Summary of Contents for AFFINITY BHP024

Page 1: ...the installer can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...e designed for single point and dual con nection TABLE OF CONTENTS Description 1 Standard Features Benefits 1 Field installed Accessories 3 Unit Cut Away 5 Ratings 5 Physical Data 5 Cooling Capacities...

Page 5: ...E PHASE THREE PHASE 024 24 4 13 0 11 3 7 7 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 7 77 28 2 3 40 16 5 2 20 5 0 7 5 10 0 15 0 10 0 15 0 036 35 0 13 0 11 3 7 7 77 32 0 3 30 18 9 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...WER INPUT kW 5 64 5 52 5 37 5 28 6 17 6 04 5 88 5 77 Sensible Capacity MBH 1 Entering Dry Bulb F 86 36 7 45 7 46 8 47 2 41 9 49 9 46 3 46 7 83 32 0 41 1 46 8 47 2 35 9 45 9 46 3 46 7 80 27 3 36 4 46 7...

Page 12: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 10 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TE...

Page 13: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 12 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 14: ...66 3 793 4 020 4 247 4 474 80 MBH 13 394 16 579 20 504 25 342 31 304 38 653 47 709 58 871 KW 3 227 3 453 3 680 3 907 4 134 4 361 4 588 4 815 1 These capacities are net capacities the indoor motor heat...

Page 15: ...1 412 494 577 B1HP042 Cooling TB2 A Heating TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B Heating TB2 B 1400 CFM 393 466 544 642 734 B1HP048 Heating TB2 A 1400 CFM 377 427 504 597 683 B1HP0...

Page 16: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 17: ...7 31 0 6 6 8 12 7 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 7 3 25 8 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 7 3 16 1 20 20 0...

Page 18: ...48 7 45 50 45 50 2NH04501525 11 3 15 0 31 3 36 1 47 7 63 7 60 70 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 7 5 10 0 20 8 24 1 48 7 52 7 60 60 60 60 2NH04501525 11 3 15 0 31 3 36 1 76 7 67 8...

Page 19: ...T OF UNIT CENTER OF GRAVITY B1HP UNIT SIZE SHIPPING WEIGHT OPERATING WEIGHT CORNER WEIGHTS A B C D 024 356 351 97 93 81 84 030 353 348 96 93 81 84 036 388 383 106 102 89 92 042 440 435 120 115 101 104...

Page 20: ...7 A 1205 20 Unitary Products Group FIGURE 5 UNIT DIMENSIONS 5217 5217 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 29 5 81 7 6...

Page 21: ...036 21528 007 A 1205 Unitary Products Group 21 FIGURE 6 TYPICAL APPLICATIONS...

Page 22: ...036 21528 007 A 1205 22 Unitary Products Group FIGURE 7 ROOF CURB DIMENSIONS...

Page 23: ...036 21528 007 A 1205 Unitary Products Group 23 FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 24: ...036 21528 007 A 1205 24 Unitary Products Group FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 25: ...036 21528 007 A 1205 Unitary Products Group 25 FIGURE 10 TYPICAL WIRING DIAGRAM 460 575 3 60 POWER SUPPLY...

Page 26: ...be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height 8...

Page 27: ...ing the normal system operation pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for r...

Page 28: ...Printed in U S A 036 21528 007 A 1205 Copyright by Unitary Products Group 2005 All rights reserved Supersedes 036 21528 006 A 1005 Unitary 5005 Norman Products York OK Group Drive 73069 ISO 9001 Cert...

Reviews: