TABLE 13: HEATING CAPACITIES - 4 TON (BHP048)
CFM
RETURN
AIR °F
CAP
1
& KW
OUTDOOR AIR TEMPERATURE, °F (72% RH)
-10
0
10
20
30
40
50
60
1200
55
MBH
13.911
17.096
21.021
25.859
31.821
39.170
48.226
59.388
KW
2.342
2.568
2.795
3.022
3.249
3.476
3.703
3.930
70
MBH
11.264
14.449
18.374
23.212
29.174
36.523
45.579
56.741
KW
2.726
2.952
3.179
3.406
3.633
3.860
4.087
4.314
80
MBH
9.676
12.861
16.786
21.624
27.586
34.935
43.991
55.153
KW
3.067
3.293
3.520
3.747
3.974
4.201
4.428
4.655
1600
55
MBH
16.349
19.534
23.459
28.297
34.259
41.608
50.664
61.826
KW
2.408
2.634
2.861
3.088
3.315
3.542
3.769
3.996
70
MBH
13.702
16.887
20.812
25.650
31.612
38.961
48.017
59.179
KW
2.792
3.018
3.245
3.472
3.699
3.926
4.153
4.380
80
MBH
12.114
15.299
19.224
24.062
30.024
37.373
46.429
57.591
KW
3.133
3.359
3.586
3.813
4.040
4.267
4.494
4.721
2000
55
MBH
17.629
20.814
24.739
29.577
35.539
42.888
51.944
63.106
KW
2.502
2.728
2.955
3.182
3.409
3.636
3.863
4.090
70
MBH
14.982
18.167
22.092
26.930
32.892
40.241
49.297
60.459
KW
2.886
3.112
3.339
3.566
3.793
4.020
4.247
4.474
80
MBH
13.394
16.579
20.504
25.342
31.304
38.653
47.709
58.871
KW
3.227
3.453
3.680
3.907
4.134
4.361
4.588
4.815
1.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.
TABLE 14: HEATING CAPACITIES - 5 TON (BHP060)
CFM
RETURN
AIR °F
CAP
1
& KW
OUTDOOR AIR TEMPERATURE, °F (72% RH)
-10
0
10
20
30
40
50
60
1950
55
MBH
16.136
19.904
24.617
30.513
37.889
47.115
58.657
73.095
KW
2.403
2.771
3.140
3.509
3.877
4.246
4.615
4.983
70
MBH
15.014
18.782
23.495
29.391
36.767
45.993
57.535
71.973
KW
2.967
3.335
3.704
4.073
4.441
4.810
5.179
5.547
80
MBH
11.066
14.834
19.547
25.443
32.819
42.045
53.587
68.025
KW
3.368
3.736
4.105
4.474
4.842
5.211
5.580
5.948
2000
55
MBH
16.054
19.822
24.535
30.431
37.807
47.033
58.575
73.013
KW
2.411
2.779
3.148
3.517
3.885
4.254
4.623
4.991
70
MBH
14.932
18.700
23.413
29.309
36.685
45.911
57.453
71.891
KW
2.975
3.343
3.712
4.081
4.449
4.818
5.187
5.555
80
MBH
10.984
14.752
19.465
25.361
32.737
41.963
53.505
67.943
KW
3.376
3.744
4.113
4.482
4.850
5.219
5.588
5.956
1.
These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have
been added.