036-21528-007-A-1205                                                                                                                                                                                                                                     

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

                    

 

®  

AFFINITY™ SERIES

SINGLE PACKAGE
HEAT PUMPS

BHP024 THRU 060
2 THRU 5 NOMINAL TONS
13 SEER

FACTORY MOUNTED TXV

DESCRIPTION

York

®

 Affinity™ Series packaged heat pumps are designed 

for outdoor installation. Only utility and duct connections 
are required at the point of installation.

Field-installed electric heater accessories are available to 
provide electric heat, if required.

STANDARD FEATURES / BENEFITS

OPERATING EFFICIENCY

All units provide high operating efficiencies of 13 SEER, 3.3 
COP or greater, and 7.7 HSPF. All efficiencies exceed leg-
islated minimum levels.

ON SITE FLEXIBILITY

All model sizes share a common, compact design cabinet 
with a single footprint. The installer has the flexibility of set-
ting one curb or pad and placing the proper tonnage unit 
after the internal load has been determined. Field convert-
ible duct connections, from side shot to down shot, allows 
the installer greater flexibility and the need to carry less 
inventory.

LOWER INSTALLATION COST

Installation time and costs are reduced by easy power and
control wiring connections. The small base dimension
means less space is required on the ground or roof. Plus,
the installer can fit this unit between the wheel wells of full
size pick-up truck. All models are under 500 pounds.

All units are completely wired, charged with R-22 and 
tested prior to shipment. Unique test stations, are used to 
insure product quality. Refrigerant charge, and component 
part numbers are verified via computers at manufacturing 
point. Vital run test statistics, such as, system pressure, 
motor currents, air velocity and temperature unit vibration 
are monitored and recorded by the system to insure unit 
performance.

Equal size, side supply and return duct connections allow 
easy hook-up of ducts to match low crawl spaces without 
transition pieces.

UTILITY CONNECTIONS MADE EASY

Electrical utility knockouts are provided through the bottom, 
as well as the side of the unit. Utility connections can be 
made quickly and with a minimum amount of field labor. A 
field supplied and  field installed electrical disconnect 
switch must be installed.

CONVERTIBLE AIRFLOW DESIGN

The bottom duct openings are covered when they leave the 
factory.  They are ready for a side supply / side return appli-
cation. If a bottom supply / bottom return application is 
desired, you simply remove the two panels from the bottom 
of the unit and place them in the side supply / side return 
duct openings. No panel cutting is required and no acces-
sory panel is necessary. Convertible airflow design allows 
maximum field flexibility and minimum inventory.

Summary of Contents for AFFINITY BHP024

Page 1: ...the installer can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...e designed for single point and dual con nection TABLE OF CONTENTS Description 1 Standard Features Benefits 1 Field installed Accessories 3 Unit Cut Away 5 Ratings 5 Physical Data 5 Cooling Capacities...

Page 5: ...E PHASE THREE PHASE 024 24 4 13 0 11 3 7 7 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 7 77 28 2 3 40 16 5 2 20 5 0 7 5 10 0 15 0 10 0 15 0 036 35 0 13 0 11 3 7 7 77 32 0 3 30 18 9 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...WER INPUT kW 5 64 5 52 5 37 5 28 6 17 6 04 5 88 5 77 Sensible Capacity MBH 1 Entering Dry Bulb F 86 36 7 45 7 46 8 47 2 41 9 49 9 46 3 46 7 83 32 0 41 1 46 8 47 2 35 9 45 9 46 3 46 7 80 27 3 36 4 46 7...

Page 12: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 10 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TE...

Page 13: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 12 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 14: ...66 3 793 4 020 4 247 4 474 80 MBH 13 394 16 579 20 504 25 342 31 304 38 653 47 709 58 871 KW 3 227 3 453 3 680 3 907 4 134 4 361 4 588 4 815 1 These capacities are net capacities the indoor motor heat...

Page 15: ...1 412 494 577 B1HP042 Cooling TB2 A Heating TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B Heating TB2 B 1400 CFM 393 466 544 642 734 B1HP048 Heating TB2 A 1400 CFM 377 427 504 597 683 B1HP0...

Page 16: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 17: ...7 31 0 6 6 8 12 7 20 20 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 7 3 33 4 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 7 3 25 8 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 7 3 16 1 20 20 0...

Page 18: ...48 7 45 50 45 50 2NH04501525 11 3 15 0 31 3 36 1 47 7 63 7 60 70 60 70 036 208 230 3 60 11 4 78 0 1 1 7 3 2NH04501025 7 5 10 0 20 8 24 1 48 7 52 7 60 60 60 60 2NH04501525 11 3 15 0 31 3 36 1 76 7 67 8...

Page 19: ...T OF UNIT CENTER OF GRAVITY B1HP UNIT SIZE SHIPPING WEIGHT OPERATING WEIGHT CORNER WEIGHTS A B C D 024 356 351 97 93 81 84 030 353 348 96 93 81 84 036 388 383 106 102 89 92 042 440 435 120 115 101 104...

Page 20: ...7 A 1205 20 Unitary Products Group FIGURE 5 UNIT DIMENSIONS 5217 5217 OO GLPHQVLRQV DUH LQ LQFKHV 7KH DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 29 5 81 7 6...

Page 21: ...036 21528 007 A 1205 Unitary Products Group 21 FIGURE 6 TYPICAL APPLICATIONS...

Page 22: ...036 21528 007 A 1205 22 Unitary Products Group FIGURE 7 ROOF CURB DIMENSIONS...

Page 23: ...036 21528 007 A 1205 Unitary Products Group 23 FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 24: ...036 21528 007 A 1205 24 Unitary Products Group FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 25: ...036 21528 007 A 1205 Unitary Products Group 25 FIGURE 10 TYPICAL WIRING DIAGRAM 460 575 3 60 POWER SUPPLY...

Page 26: ...be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height 8...

Page 27: ...ing the normal system operation pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for r...

Page 28: ...Printed in U S A 036 21528 007 A 1205 Copyright by Unitary Products Group 2005 All rights reserved Supersedes 036 21528 006 A 1005 Unitary 5005 Norman Products York OK Group Drive 73069 ISO 9001 Cert...

Reviews: