York 65075-N4U Installation Instructions Manual Download Page 27

All flash code sequences are broken by a 2 second "off" period.

CONTINUOUS FLASHING (1 sec "on" - 1 sec "off")
This indicates that flame was sensed when there was not a call
for heat. With this fault code the control will also turn on both
the inducer motor and supply air blower. This fault would
typically be caused by a gas valve that leaks through or is slow
closing.

2 FLASH
This indicates that the normally open pressure switch contacts
are stuck in the closed position. The control confirms these
contacts are open at the beginning of each heat cycle. This
would indicate a faulty pressure switch or mis-wiring.

3 FLASH
This indicates the normally open pressure switch contact did
not close at the beginning of the heat cycle. This could be
caused by a number of problems; faulty inducer, blocked vent
pipe, high winds at vent terminal, broken pressure switch hose
or faulty pressure switch.

4 FLASH
This indicates the auxiliary limit switch has opened its normally
closed contacts. With this fault code the control will operate the
supply air blower and inducer. This condition may be caused
by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

5 FLASH
This fault is indicated if the normally closed contacts in the
rollout switch opens. The rollout control is manually reset. If it
has opened, check for proper combustion air, proper inducer
operation, primary heat exchanger failure or burner problem.
Be sure to reset the switch after correcting the failure condition.

6 FLASH
This indicates that after the unit was operating, the pressure
switch opened 5 times during the call for heat. This could be
caused by a number of problems; blocked vent or combustion
air intake, high winds at vent terminal, faulty inducer, cracked
pressure switch hose, or a blockage in the condensate drain-
age system.

7 FLASH
This fault code indicates that flame could not be established.

This no-light condition occurred 3 times during the call for heat
before locking out. This may be caused by low gas pressure,
faulty gas valve, faulty hot surface igniter or burner problem.

8 FLASH
This fault is indicated if the flame is lost 5 times during the
heating cycle. This could be caused by low gas pressure or
faulty gas valve.

9 FLASH (TI61F-2 CONTROL ONLY)
Indicates reversed line voltage polarity.  Check incoming power
wiring.

LED ON CONSTANTLY
This indicated an internal fault in the furnace control discovered
during its self-check procedure. Replace the control.

60 MINUTE AUTOMATIC RESET FROM LOCKOUT
This control includes a "watchdog" type circuit that will reset
from a lockout condition after 60 minutes. Operational faults 6,
7 & 8 will be reset. This provides protection to an unoccupied
structure if a temporary conditions exists causing a unit mal-
function. An example would be a low incoming gas supply
pressure condition preventing unit operation. When the gas
pressure was restored, at some point the "watchdog" would
restart the unit and provide heat for the house.

NOTE: The control will blink one time when initially powered.

This is normal and not an indication of any malfunction.

RESET FROM LOCKOUT
To reset the control from any lockout condition break the line
voltage supply 

or 24 volt signal from the thermostat for 30

seconds.

WARNING: Do not try to repair controls. Replace
defective controls with Source 1 Parts.

WARNING: Never adjust pressure switch to allow
furnace operation.

WARNING: Never jump pressure switch or rewire in
an attempt to allow furnace operation. To do so will
allow furnace to operate under potentially hazardous
conditions.

  50A50-241 IGNITION CONTROL (P/N 031-01266-000)
    Normal 

flame 

sense 

current 

is 

approximately.

          2.0 microamps DC (

µ

a)

    Low 

flame 

signal 

control 

lockout 

point 

is 

     0.15 

microamps 

DC 

(

µ

a)

POWER SUPPLY POLARITY 
( W-R 50A50-241 Control Only)
If the power supply polarity is reversed, the following unit
operation will occur. On a call for heat, the inducer will run,
the HSI will glow and the gas valve will energize and the
burners will ignite. The burners will immediately extinguish
and the unit will recycle. This will occur 3 times and then the
unit will lockout. A "7" flash code will be displayed. This code
means the flame could not be established. This occurs be-
cause the control cannot sense flame with the power supply
polarity reversed.

      6IF-2 IGNITION CONTROL (P/N 031-01267-000)
    Normal 

flame 

sense 

current 

is 

approximately.

          3.7 microamps DC (

µ

a)

    Low 

flame 

signal 

control 

lockout 

point 

is 

          0.9 microamps DC (

µ

a)

650.75-N4U

Unitary Products Group

27

Summary of Contents for 65075-N4U

Page 1: ...r other flammable vapors and liquids in the vicinity of this or any other appliance WARNING IMPROPER INSTALLATION ADJUSTMENT AL TERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE RE F...

Page 2: ...ce since it requires separate properly sized air intake and vent lines The furnace shall not be connected to any type of B BW or L vent or vent connector and not connected to any portion of a factory...

Page 3: ...e access is required for passage to the front when servicing or for inspection or replacement of flue vent connections NOTE In all cases accessibility clearances shall take prece dence over clearances...

Page 4: ...95 2000 C 21 19 3 4 16 5 8 2 2 120 112 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 140 130 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 Vent pipe must be increased to 3 on this model INPUT MBH OUTPUT MBH NOM CFM CAB WIDTH...

Page 5: ...75 1200 17 1 2 91 0 35 65 1370 165 11 8 1 2 9 0 20 14 80 75 1600 21 91 0 30 60 1563 160 11 8 3 4 12 0 20 14 100 95 2000 21 91 0 40 70 1582 170 11 10 1 12 0 20 14 120 112 2000 24 1 2 91 0 40 70 1885 1...

Page 6: ...ambient temperature may drop below 32 F a UL listed self regulated heat tape must be installed It is recommended that self regulating heat tape rated at 3 watts per foot be used This must be installe...

Page 7: ...r sides of the cabinet wall NOTE Air velocity through throw away type filters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters Side Return External...

Page 8: ...n sions Install the plenum following instructions under Ductwork in this instruction SUPPLY AIR DUCTS Installations on combustible material or floors must usea combus tible floor base shown in Figure...

Page 9: ...ezing are possible refer to Page 6 Below Freezing Locations GAS PIPING The gas supply must be installed in accordance with the current National Fuel Gas Code ANSI Z223 1 in the U S or CAN CGA B149 1 o...

Page 10: ...switch should be close to the unit for convenience in servicing With the disconnect switch in the OFF position check all wiring against the unit wiring label Also see the wiring diagram in this instru...

Page 11: ...nnection top right of unit back to the outdoors See Figure 13 or 14 The intake vent should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be t...

Page 12: ...roofor sidewall NOTE Accessory concentric intake vent terminations models 1CT0302 and 1CT0303 are available and approved for use with these furnaces Refer to Form 650 75 N2 4V for installation details...

Page 13: ...ning at the furnace 2 Deburr the piping inside and outside 3 Chamfer the outer edges of the piping 4 Dry fit the entire vent combustion air piping assembly 5 Disassemble the piping and apply cement pr...

Page 14: ...the furnace This may be from within the space in a non confined location or it may be brought into the furnace area from outdoors It is not directly ducted into the furnace A single properly sized pi...

Page 15: ...m dimension of rectangular ducts shall be three inches 2 One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least...

Page 16: ...t connections NOTE An offset using two 45 degree elbows may be required for plenum clearance when the vent is increased to 3 1 Long radius elbows are required for all units 2 Elbows are assumed to be...

Page 17: ...on may require seal ing or shielding of building surfaces with a corrosive resistant material due to vent system corrosive combus tion products PIPING ASSEMBLY The final assembly procedure for the ven...

Page 18: ...e allowable locations shown in Figure 24 and Section 7 8 in the National Fuel Gas Code ANSI Z223 1 current edition Follow all local agency and utility requirements if more restrictive than those shown...

Page 19: ...w the instructions with the coil for trapping the drain SAFETY CONTROLS Control Circuit Fuse A 3 amp fuse is provided to protect the 24 volt transformer from overload caused by control circuit wiring...

Page 20: ...blower motor failure START UP AND ADJUSTMENTS The initial start up of the furnace requires the following addi tional procedures 1 When the gas supply is initially connected to the furnace the gas pip...

Page 21: ...MPLE CHECKING GAS INPUT It is found by measurement that it takes 26 seconds for the hand on the 1 cubic foot dial to make a revolution with only a 120 000 Btuh furnace running Using this information l...

Page 22: ...and electrical supplies ON Start furnace and observe manifold pressure on manometer 5 Adjust manifold pressure by adjusting gas valve regulator screw for natural gas set at 3 5 W C If gas valve regula...

Page 23: ...or lead Place all unused motor leads on Park terminals Two Park terminals are provided CAUTION Do not energize more than one motor speed at a time or damage to the motor will result ADJUSTMENT OF FAN...

Page 24: ...the thermostat circuit opens the ignition control is deener gized Withtheignitioncontroldeenergized thegasflowstopsand the burner flames are extinguished The venter continues to operate for 15 seconds...

Page 25: ...me Lift filter slightly to dislodge and remove for service 3 Remove the filter and follow the cleaning instructions above DO NOT remove the filter stiffener rods if provided When reinstalling the filt...

Page 26: ...blower and the condensate pan The turbulators can then be gently re moved from the secondary heat exchanger 3 With a stiff wire brush brush out loose scale or soot 4 Vacuum the secondary heat exchang...

Page 27: ...e is lost 5 times during the heating cycle This could be caused by low gas pressure or faulty gas valve 9 FLASH TI61F 2 CONTROL ONLY Indicates reversed line voltage polarity Check incoming power wirin...

Page 28: ...985 835 757 665 450 MED 900 887 851 810 752 693 609 403 LOW 581 577 569 542 468 60 55 1000 B HI 1220 1200 1190 1152 1115 1065 1012 950 872 771 MED 920 915 900 880 842 803 740 650 LOW 725 729 715 700...

Page 29: ...UNIT WIRING DIAGRAM UPFLOW 650 75 N4U Unitary Products Group 29...

Page 30: ...UNIT WIRING DIAGRAM DOWNFLOW HORIZONTAL...

Page 31: ...NOTES 650 75 N4U Unitary Products Group 31...

Page 32: ...ect to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved 650 75 N4U Supercedes 650 75 N4U 498 5005 York Drive Norman OK 73069 Unitary Products Group 6...

Reviews: