background image

COMBUSTION AIR

All installations must comply with Section 5.3, Air for Combus-
tion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2
Installation Code - latest editions.

An unconfined space is not less than 50 cubic feet per 1000
Btu/hr input rating for all appliances installed in that area.

Rooms communicating directly with the space containing the
appliances are considered part of the unconfined space, if
openings are not furnished with doors.

A confined space is an area with less than 50 cubic feet per
1000 Btu/hr input rating for all appliances installed in that area.

The following must be considered to obtain proper air for
combustion and ventilation in confined spaces. 

Air Source from Inside the Building - 
Two permanent openings, one within 12 inches of the top of the
confined space and one within 12 inches of the bottom, shall
each have a free area of not less than one square inch per
1,000 Btuh of total input rating of all appliances located in the
space. The openings shall communicate freely with interior
areas having adequate infiltration from the outside.

NOTE: At least 100 square inches free area shall be used for

each opening.

Air Source from Outdoors - 

1.  Two permanent openings, one within 12 inches  of the top

of the confined space and one within 12 inches  of the
bottom, shall communicate directly, or by means of ducts,
with the outdoors or to such crawl or attic spaces that freely
communicate with the outdoors.

a.  Vertical Ducts - Each opening must have a free area of

not less than one square inch per 4,000 Btuh of total
input of all appliances located in the space.

EXAMPLE:

Total Input of All Appliances  

=  Square Inches Free Area

          4000

b.  Horizontal Ducts - Each opening must have a free area

of not less than one square inch per 2,000 Btuh of total
input of all appliances located in the space.

NOTE: Ducts must have the same cross-sectional area as the free

area in the opening to which they are connected. The minimum
dimension of rectangular ducts shall be three inches.

2.  One permanent opening, commencing within 12 inches of

the top of the enclosure shall be permitted where the
equipment has clearances of at least 1 inch from the sides
and back and 6 inches from the front of the appliance. The
opening shall communicate through a vertical or horizontal
duct to the outdoors, or spaces (crawl or attic) that freely
communicate with the outdoors and shall have a minimum
free area of:

a.  1 sq. in. per 3000 Btu per hr of the total input rating of

all equipment located in the enclosure.

b.  Not less than the sum of the areas of all vent connectors

in the confined space.

3.  Louvers, Grilles and Screens

a.  In calculating free area, consideration must be given to

the blocking effects of louvers, grilles and screens.

b.  If the free area of a specific louver or grille is not known,

refer to Table 6 to estimate free area.

NOTE: If mechanically operated louvers are used, a means to

prevent main burner ignition and operation must be pro-
vided should louvers close during startup or operation.

Special Combustion and Ventilation Considerations

Operation of a mechanical exhaust, such as an exhaust fan,
kitchen ventilation system, clothes dryer or fireplace may cre-
ate conditions requiring special attention to avoid unsatisfac-
tory operation of gas appliances.

Specially Engineered Installations

The above requirements shall be permitted to be waived where
special engineering, approved by the authority having jurisdic-
tion, provides an adequate supply of air for combustion, venti-
lation and dilution of flue gases.

Y

W

R

G

C

C O O L
H E A T

P A R K
P A R K

L I N E
X F M R

E A C
H U M

C I R

L I N E

X F M R

E A C

H U M

V E N T   P I P E   P A S S E S

T H R O U G H   T O P   P A N E L

C O M B U S T I O N   A I R

G A S   P I P I N G

K N O C K O U T S

FIGURE 23 - DOWNFLOW/HORIZONTAL 
      VENT 

PIPE 

CONNECTION

ESTIMATED FREE AREA

Wood or Metal

Louvers or Grilles

Wood 20 - 25%*

Metal 60 - 70%*

Screens**

1/4" mesh or larger 100%

  * Do not use less than 1/4" mesh
  ** Free area or louvers and grilles varies widely. Installer
    should follow louver or grillle manufacturer’s instructions.

TABLE 6 - ESTIMATED FREE AREA

650.75-N4U

Unitary Products Group

15

Summary of Contents for 65075-N4U

Page 1: ...r other flammable vapors and liquids in the vicinity of this or any other appliance WARNING IMPROPER INSTALLATION ADJUSTMENT AL TERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE RE F...

Page 2: ...ce since it requires separate properly sized air intake and vent lines The furnace shall not be connected to any type of B BW or L vent or vent connector and not connected to any portion of a factory...

Page 3: ...e access is required for passage to the front when servicing or for inspection or replacement of flue vent connections NOTE In all cases accessibility clearances shall take prece dence over clearances...

Page 4: ...95 2000 C 21 19 3 4 16 5 8 2 2 120 112 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 140 130 2000 D 24 1 2 23 1 4 20 1 8 3 2 3 Vent pipe must be increased to 3 on this model INPUT MBH OUTPUT MBH NOM CFM CAB WIDTH...

Page 5: ...75 1200 17 1 2 91 0 35 65 1370 165 11 8 1 2 9 0 20 14 80 75 1600 21 91 0 30 60 1563 160 11 8 3 4 12 0 20 14 100 95 2000 21 91 0 40 70 1582 170 11 10 1 12 0 20 14 120 112 2000 24 1 2 91 0 40 70 1885 1...

Page 6: ...ambient temperature may drop below 32 F a UL listed self regulated heat tape must be installed It is recommended that self regulating heat tape rated at 3 watts per foot be used This must be installe...

Page 7: ...r sides of the cabinet wall NOTE Air velocity through throw away type filters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters Side Return External...

Page 8: ...n sions Install the plenum following instructions under Ductwork in this instruction SUPPLY AIR DUCTS Installations on combustible material or floors must usea combus tible floor base shown in Figure...

Page 9: ...ezing are possible refer to Page 6 Below Freezing Locations GAS PIPING The gas supply must be installed in accordance with the current National Fuel Gas Code ANSI Z223 1 in the U S or CAN CGA B149 1 o...

Page 10: ...switch should be close to the unit for convenience in servicing With the disconnect switch in the OFF position check all wiring against the unit wiring label Also see the wiring diagram in this instru...

Page 11: ...nnection top right of unit back to the outdoors See Figure 13 or 14 The intake vent should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be t...

Page 12: ...roofor sidewall NOTE Accessory concentric intake vent terminations models 1CT0302 and 1CT0303 are available and approved for use with these furnaces Refer to Form 650 75 N2 4V for installation details...

Page 13: ...ning at the furnace 2 Deburr the piping inside and outside 3 Chamfer the outer edges of the piping 4 Dry fit the entire vent combustion air piping assembly 5 Disassemble the piping and apply cement pr...

Page 14: ...the furnace This may be from within the space in a non confined location or it may be brought into the furnace area from outdoors It is not directly ducted into the furnace A single properly sized pi...

Page 15: ...m dimension of rectangular ducts shall be three inches 2 One permanent opening commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least...

Page 16: ...t connections NOTE An offset using two 45 degree elbows may be required for plenum clearance when the vent is increased to 3 1 Long radius elbows are required for all units 2 Elbows are assumed to be...

Page 17: ...on may require seal ing or shielding of building surfaces with a corrosive resistant material due to vent system corrosive combus tion products PIPING ASSEMBLY The final assembly procedure for the ven...

Page 18: ...e allowable locations shown in Figure 24 and Section 7 8 in the National Fuel Gas Code ANSI Z223 1 current edition Follow all local agency and utility requirements if more restrictive than those shown...

Page 19: ...w the instructions with the coil for trapping the drain SAFETY CONTROLS Control Circuit Fuse A 3 amp fuse is provided to protect the 24 volt transformer from overload caused by control circuit wiring...

Page 20: ...blower motor failure START UP AND ADJUSTMENTS The initial start up of the furnace requires the following addi tional procedures 1 When the gas supply is initially connected to the furnace the gas pip...

Page 21: ...MPLE CHECKING GAS INPUT It is found by measurement that it takes 26 seconds for the hand on the 1 cubic foot dial to make a revolution with only a 120 000 Btuh furnace running Using this information l...

Page 22: ...and electrical supplies ON Start furnace and observe manifold pressure on manometer 5 Adjust manifold pressure by adjusting gas valve regulator screw for natural gas set at 3 5 W C If gas valve regula...

Page 23: ...or lead Place all unused motor leads on Park terminals Two Park terminals are provided CAUTION Do not energize more than one motor speed at a time or damage to the motor will result ADJUSTMENT OF FAN...

Page 24: ...the thermostat circuit opens the ignition control is deener gized Withtheignitioncontroldeenergized thegasflowstopsand the burner flames are extinguished The venter continues to operate for 15 seconds...

Page 25: ...me Lift filter slightly to dislodge and remove for service 3 Remove the filter and follow the cleaning instructions above DO NOT remove the filter stiffener rods if provided When reinstalling the filt...

Page 26: ...blower and the condensate pan The turbulators can then be gently re moved from the secondary heat exchanger 3 With a stiff wire brush brush out loose scale or soot 4 Vacuum the secondary heat exchang...

Page 27: ...e is lost 5 times during the heating cycle This could be caused by low gas pressure or faulty gas valve 9 FLASH TI61F 2 CONTROL ONLY Indicates reversed line voltage polarity Check incoming power wirin...

Page 28: ...985 835 757 665 450 MED 900 887 851 810 752 693 609 403 LOW 581 577 569 542 468 60 55 1000 B HI 1220 1200 1190 1152 1115 1065 1012 950 872 771 MED 920 915 900 880 842 803 740 650 LOW 725 729 715 700...

Page 29: ...UNIT WIRING DIAGRAM UPFLOW 650 75 N4U Unitary Products Group 29...

Page 30: ...UNIT WIRING DIAGRAM DOWNFLOW HORIZONTAL...

Page 31: ...NOTES 650 75 N4U Unitary Products Group 31...

Page 32: ...ect to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved 650 75 N4U Supercedes 650 75 N4U 498 5005 York Drive Norman OK 73069 Unitary Products Group 6...

Reviews: