661693-UIM-E-1212
10
Johnson Controls Unitary Products
d
AHR30B
AHR42C
6HK(0,1)6500206
10.0
14.6
16.3
15
20
12
12
6HK(0,1)6500506
20.0
25.4
28.8
30
30
10
10
6HK(0,1)6500806
32.0
38.4
43.8
40
45
8
8
6HK(0,1)6501006
40.0
47.1
53.8
50
60
6
6
6HK(1,2)6501306
52.0
60.1
68.8
70
70
6
4
6HK(1,2)6501506
60.0
68.8
78.8
70
80
4
4
AHR36B
AHR48D
6HK(0,1)6500206
10.0
14.6
16.3
15
20
12
12
6HK(0,1)6500506
20.0
25.4
28.8
30
30
10
10
6HK(0,1)6500806
32.0
38.4
43.8
40
45
8
8
6HK(0,1)6501006
40.0
47.1
53.8
50
60
8
6
6HK(1,2)6501306
52.0
60.1
68.8
70
70
6
4
6HK(1,2)6501506
60.0
68.8
78.8
70
80
4
4
6HK(1,2)6501806
72.0
81.8
93.8
90
100
4
3
6HK(1,2)6502006
80.0
90.4
103.8
100
110
3
2
AHR60D
6HK(0,1)6500206
10.0
14.6
16.3
15
20
12
12
6HK(0,1)6500506
20.0
25.4
28.8
30
30
10
10
6HK(0,1)6500806
32.0
38.4
43.8
40
45
8
8
6HK(0,1)6501006
40.0
47.1
53.8
50
60
8
6
6HK(1,2)6501306
52.0
60.1
68.8
70
70
6
4
6HK(1,2)6501506
60.0
68.8
78.8
70
80
4
4
6HK(1,2)6501806
72.0
81.8
93.8
90
100
4
3
6HK(1,2)6502006
80.0
90.4
103.8
100
110
3
2
6HK(1,2)6502506
100.0
112.1
128.8
125
150
2
1
1. (0,1) - maybe 0 (no circuit breaker) or 1 (with circuit breaker).
2. (1,2) maybe 1 (with circuit breaker, no breaker jumper bar) or 2 (with circuit breaker & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°
C
ambient, copper wire is used, consult applicable tables of the
NEC and local codes.
TABLE 6:
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
Min Wire Size (AWG)
4
208V
230V
208V
230V
208V
230V
TABLE 7:
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air
Handlers
Models
Heater
Models
Total
Heater
Amps
@240V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
Circuit
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
AHR24B
6HK16501306
52.0
20.6 37.6
-
23.4 43.3
-
25
40
-
25
45
-
10
8
-
10
8
-
6HK16501506
60.0
23.5 43.3
-
26.8 50.0
-
25
45
-
30
50
-
10
8
-
10
8
-
AHR30B
AHR42C
6HK16501306
52.0
22.6 37.6
-
25.4 43.3
-
25
40
-
30
45
-
10
8
-
10
8
-
6HK16501506
60.0
25.5 43.3
-
28.8 50.0
-
30
45
-
30
50
-
10
8
-
10
8
-
AHR36B
AHR48D
6HK16501306
52.0
22.6 37.6
-
25.4 43.3
-
25
40
-
30
45
-
10
8
-
10
8
-
6HK16501506
60.0
25.5 43.3
-
28.8 50.0
-
30
45
-
30
50
-
10
8
-
10
8
-
6HK16501806
72.0
42.8 39.0
-
48.8 45.0
-
45
40
-
50
45
-
8
8
-
8
8
-
6HK16502006
80.0
47.1 43.3
-
53.8 50.0
-
50
45
-
60
50
-
8
8
-
6
8
-
AHR60D
6HK16501306
52.0
22.6 37.6
-
25.4 43.3
-
25
40
-
30
45
-
10
8
-
10
8
-
6HK16501506
60.0
25.5 43.3
-
28.8 50.0
-
30
45
-
30
50
-
10
8
-
10
8
-
6HK16501806
72.0
42.8 39.0
-
48.8 45.0
-
45
40
-
50
45
-
8
8
-
8
8
-
6HK16502006
80.0
47.1 43.3
-
53.8 50.0
-
50
45
-
60
50
-
8
8
-
6
8
-
6HK16502506
100
47.1 43.3 21.7 53.8 50.0 25.0
50
45
25
60
50
25
6
6
10
6
8
10
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.
Summary of Contents for 41HP AHR18B
Page 1: ......