TYPICAL APPLICATIONS
ACCESSORIES
Refer to Price Manual for specific model numbers where not
shown.
TXV Kits
- TXV kits are available for “Flex-coil” applications and
converting R-22 to R-410A or as a service replacement. All kits
are bolt-on and require no brazing to install.
Electric Heaters -
6HK models shown under electrical data
include sequential operation and temperature dual limit
switches for safe, efficient operation. Circuit breakers are pro-
vided where shown.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60
Air Handler Models
Heater
Models
Heater
Amps
@ 240V
Field Wiring
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
AHE22B
AHE24B
AHE30B
6HK06501025
23.1
28.5
32.4
30
35
10
8
6HK06501525
34.6
41.0
46.8
45
50
8
8
AHE34C
AHE36C
AHE42D
6HK06501025
23.1
30.2
34.0
30
35
10
8
6HK06501525
34.6
42.6
48.4
45
50
8
8
6HK06501825
41.6
50.2
57.1
60
60
6
6
6HK16502025
3
46.2
55.2
62.9
60
70
6
6
AHE48D
6HK06501025
23.1
32.5
36.4
35
40
8
8
6HK06501525
34.6
45.0
50.8
45
60
8
6
6HK06501825
41.6
52.6
59.5
60
60
6
6
6HK16502025
3
46.2
57.6
65.3
60
70
6
4
AHE60D
6HK06501025
23.1
32.5
36.4
35
40
8
8
6HK06501525
34.6
45.0
50.8
45
60
8
6
6HK06501825
41.6
52.6
59.5
60
60
6
6
6HK16502025
3
46.2
57.6
65.3
60
70
6
4
6HK16502525
3
57.7
70.0
79.6
70
80
4
4
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are
given here only for reference if used with field installed single point power modification.
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-3-60
Air Handler Models
Heater
Models
Total Heater
Amps
@ 240V
Min. Circuit Ampacity
MOP
1
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
Min. Wire Size (AWG)
2
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
208V
230V
208V
230V
208V
230V
Circuit
Circuit
Circuit
1st
3
3. 1st Circuit includes the fan motor.
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
AHE34C
AHE36C
AHE42D
6HK16502025
46.2
30.2
25.0
34.0
28.9
35
25
35
30
8
10
8
10
AHE48D
6HK16502025
46.2
32.5
25.0
36.4
28.9
35
25
40
30
8
10
8
10
AHE60D
6HK16502025
46.2
32.5
25.0
36.4
28.9
35
25
40
30
8
10
8
10
6HK16502525
57.7
38.8
31.3
43.6
36.1
40
35
45
40
8
8
8
8
UPFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
HEAT
HEA
T
HEA
T
DOWNFLOW
HEAT